SMA Solar Technology AG Electrical Connection<br />

Power Contactor for Load Shedding<br />

The <strong>Sun</strong>ny Island can automatically disconnect loads to protect the batteries from deep discharge.<br />

To do this, an external (AC or DC) power contactor must be installed between the <strong>Sun</strong>ny Island and<br />

the loads (see also section 12.1 ”Load Shedding” (page 92)).<br />

Installing the power supply of a DC power contactor for load shedding (e.g. Relay2):<br />

Power supply of the DC power contactor<br />

A 48 V voltage is present in the battery-supplied control circuit. The voltage can handle<br />

loads up to a maximum of 600 mA.<br />

1. Wire the A1 coil connector of the power contactor to the connection terminal NO (Relay2).<br />

2. Wire terminal C (Relay2) to the terminal "BatVtgOut +".<br />

3. Wire the A2 coil connector of the power contactor to the terminal "BatVtgOut –".<br />

☑ The control circuit of the power contactor is installed.<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 47