Electrical Connection SMA Solar Technology AG<br />

For connection to the relay contact, proceed as follows:<br />

DANGER!<br />

Danger to life due to faulty insulation Death or serious injuries.<br />

• Securely disconnect the relay cable from the communication area and the AC area.<br />

• Strip the insulated conductors of the relay cable.<br />

• Sheathe all relay cables installed using the silicone tube provided.<br />

• Do not operate the device without the silicone tube.<br />

1. Pierce a hole in the rubber connection area at the corresponding position.<br />

2. Starting from the outside, lead the insulated conductors with bootlace ferrules through the hole<br />

in the <strong>Sun</strong>ny Island.<br />

3. Cut an appropriate piece from the silicone tube (included in scope of delivery) and pull it over<br />

the insulated conductors.<br />

4. Connect the corresponding insulated conductors to the 3-pole print terminals included in the<br />

delivery. The pins have the following meaning:<br />

– NC: Normally closed (closed when idle)<br />

– C: Contact (operating contact)<br />

– NO: Normally opened (open when idle)<br />

5. Tighten the terminals.<br />

6. Insert the 3-pole print terminal into the corresponding socket on the <strong>Sun</strong>ny Island.<br />

46 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>