SMA Solar Technology AG Electrical Connection<br />

6.4.4 Multi-function Relay 1 and 2<br />

The <strong>Sun</strong>ny Island offers you several options for the control of internal and external processes. For this<br />

purpose, two multi-function relays are integrated into the <strong>Sun</strong>ny Island to which you can assign<br />

functions using the "241.01 Rly1Op" and "241.02 Rly2Op" parameters (see section 15 ”Relays”<br />

(page 130)).<br />

We recommend connecting the load shedding and generator request functions to the master, since,<br />

if a failure occurs, the slave may be waiting for a confirmation, but the master continues to operate<br />

and the device can at least operate in a limited capacity.<br />

Generator request function during Multicluster operation<br />

The generator request function during Multicluster operation only functions on the main<br />

cluster.<br />

Operating principles of the relays<br />

The relays are changeover contacts; they can be used as break contact (NCC) or as make<br />

contact (NOC).<br />

You can only assign one function to each relay!<br />