SMA Solar Technology AG Electrical Connection<br />

For connection, proceed as follows:<br />

Cable cross-section<br />

The maximum cable cross-section for connecting the loads / PV inverters is 16 mm2 .<br />

1. Sheathe the cable gland over the three-conductor cable and then insert the conductor through<br />

the cable opening into the <strong>Sun</strong>ny Island.<br />

2. Install the M25 cable gland (included in scope of delivery) in the "AC1 Loads/<strong>Sun</strong>ny Boys"<br />

cable opening.<br />

– Insert the cable gland with the thread in the cable opening.<br />

– Screw the counter nut onto the cable gland thread on the inside of the enclosure and tighten.<br />

3. Remove the protective insulation from each of the three conductors.<br />

4. Connect PE to the "AC1 Loads/<strong>Sun</strong>ny Boys" according to the label.<br />

5. Connect N and L to the "AC1 Loads/<strong>Sun</strong>ny Boys" according to the label.<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 37