Electrical Connection SMA Solar Technology AG<br />

6.2.3 Cable Protection<br />

In addition to the internal DC circuit breaker, install a separate, external fuse as close as possible to<br />

the battery. Install a suitable fuse link for the fuse according to the maximum specified DC currents<br />

(e.g. NH1 with 250 A).<br />

DANGER!<br />

Risk of lethal electric shock. Death or serious burns.<br />

If no external cable protection is available, observe the following:<br />

• Lay the DC cables so that they are ground-fault and short-circuit-proof.<br />

• If there are short-circuit currents of over 10000 A, use an additional thermal fuse.<br />

6.2.4 Connection<br />

DANGER!<br />

Danger to life due to high voltages. Death or serious burns.<br />

• Connect the external fuse and the battery cable to the battery only after all<br />

installation work has been completed.<br />

There is a "DC —" and a "DC +" terminal provided for each tube terminal lug (max. 70 mm²) for the<br />

battery feed cables in the <strong>Sun</strong>ny Island.<br />

34 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>