SMA Solar Technology AG Electrical Connection<br />

6.1 Grounding<br />

Before commissioning the <strong>Sun</strong>ny Island, it must be externally grounded according to the relevant<br />

regulations. To allow different types of grounding, the N connection of the <strong>Sun</strong>ny Island is not<br />

connected to PE at the factory. However, since a connection between N and PE is required for correct<br />

operation, this must be done outside of the device.<br />

Due to filter measures in the <strong>Sun</strong>ny Island, increased leakage currents to PE can always occur. For this<br />

reason, a "fixed terminal" of grounding must be implemented according to EN 50178. Ground the<br />

<strong>Sun</strong>ny Island with a copper conductor (at least 10 mm² cross-section), or with two separate copper<br />

conductors with a cross-section of at least 4 mm² each.<br />

External grounding<br />

External grounding of the positive or negative pole of the batteries (positive or negative<br />

grounding) is generally possible, because the batteries and the grid side are galvanically<br />

isolated within the <strong>Sun</strong>ny Island. In this case, make sure that the high currents that may<br />

occur under fault conditions can be adequately discharged.<br />

Calculating the Required Grounding Cable Cross-section<br />

SMA Solar Technology cannot provide generally valid values for the cross-section of the cable<br />

required for the external grounding of the battery. The cable dimensions depend on the type and size<br />

of the battery connected, the external fuse (DC side) and the material used in the grounding cable.<br />

Determining the Cross-section<br />

Exact calculation of the grounding conductor cross-section must take account of the<br />

regionally applicable standards and guidelines.<br />

The required cross-section of a (copper) grounding conductor can be calculated using the following<br />

formula. Tripping times for short-circuit currents of between 2,000 A and 10,000 A are typically<br />

about 25 ms.<br />

t = Interruption time in seconds<br />

I SC = Maximum battery current (short-circuit current) in<br />

amperes<br />

S = Conductor cross-section in mm 2<br />

A grounding conductor of 16 mm² cross-section is thus adequate for short-circuit currents up to<br />

10,000 A.<br />

The DC grounding conductors must be connected to the connection labeled "Ground". The grounding<br />

conductor is installed in five steps:<br />

1. Loosen the cable gland on the <strong>Sun</strong>ny Island.<br />

2. Thread the grounding conductor through the cable gland.<br />

3. Remove the protective insulation from the conductor and fit a suitable ring terminal lug to the<br />

exposed end of the conductor.<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 31