Troubleshooting SMA Solar Technology AG<br />

20 Troubleshooting<br />

In general the <strong>Sun</strong>ny Island distinguishes between events and errors.<br />

• Events describe state changes or transient states (e.g. generator connection).<br />

• Errors describe states that are not permitted or are only permitted up to a certain rate.<br />

This includes warnings, failures and errors. A user interaction is generally required.<br />

20.1 Failure Acknowledgement<br />

If there is a failure or an error, the <strong>Sun</strong>ny Island goes into standby.<br />

Proceed as follows to confirm a failure:<br />

1. Remove the cause.<br />

2. Confirm error with .<br />

3. Start the <strong>Sun</strong>ny Island again.<br />

20.2 Autostart Handling<br />

The <strong>Sun</strong>ny Island has an autostart meter which counts down by 1 with every automatic start. After<br />

10 minutes of normal operation of the <strong>Sun</strong>ny Island, the autostart meter is set back to its original value.<br />

If another fault occurs when the autostart meter is at 0, the <strong>Sun</strong>ny Island waits for 10 minutes and then<br />

attempts to restart. The autostart meter begins to run again.<br />

The number of the autostarts allowed can be set using the "250.01 AutoStr" parameter (in standby<br />

mode).<br />

194 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>