Parameter lists SMA Solar Technology AG<br />

Number Name <strong>Description</strong> Value Explanation Default<br />

Value<br />

20 GdAlSns AI sensitivity Low Low Normal<br />

Medium Medium<br />

Normal Normal<br />

High High<br />

235# Generator Start<br />

Number Name <strong>Description</strong> Value Explanation Default<br />

Value<br />

01 GnAutoEna Generator autostart Off Disable On<br />

On Enable<br />

02 GnAutoStr Number of autostarts 3<br />

03 GnSocTm1Str SOC limit for switching<br />

on generator for time 1<br />

40 %<br />

04 GnSocTm1Stp SOC limit for switching<br />

off generator for time 1<br />

80 %<br />

05 GnSocTm2Str SOC limit for switching<br />

on generator for time 2<br />

40 %<br />

06 GnSocTm2Stp SOC limit for switching<br />

off generator for time 2<br />

80 %<br />

07 GnTm1Str Time 1 for generator<br />

request in hours,<br />

minutes and seconds<br />

Begin: Time 1,<br />

End: Time 2<br />

08 GnTm2Str Time 2 for generator<br />

request in hours,<br />

minutes and seconds<br />

09 GnPwrEna<br />

Begin: Time 2,<br />

End: Time 1<br />

Generator request<br />

based on power<br />

10 GnPwrStr Generator request<br />

switch-on power limit<br />

11 GnPwrStp Generator request<br />

switch-off power limit<br />

12 GnPwrAvgTm Average time for<br />

powerrelated generator<br />

start<br />

Off Disable Off<br />

On Enable<br />

4 kW<br />

2 kW<br />

60 sec<br />

166 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>