Parameter lists SMA Solar Technology AG<br />

233# Grid Start<br />

Number Name <strong>Description</strong> Value Explanation Default<br />

Value<br />

01 GdSocTm1Str SOC limit for switching on<br />

the grid for time 1<br />

40 %<br />

02 GdSocTm1Stp SOC limit for switching off<br />

the grid for time 1<br />

80 %<br />

03 GdSocTm2Str SOC limit for switching on<br />

the grid for time 2<br />

40 %<br />

04 GdSocTm2Stp SOC limit for switching off<br />

the grid for time 2<br />

80 %<br />

05 GdTm1Str Time 1 for grid request in<br />

hours, minutes and<br />

seconds<br />

Begin time 1, end time 2<br />

06 GdTm2Str Time 2 for grid request in<br />

hours, minutes and<br />

seconds<br />

Begin time 2, end time 1<br />

07 GdPwrStr Grid request starting<br />

capacity<br />

4.0 kW<br />

08 GdPwrStp Grid request<br />

disconnection power limit<br />

2.0 kW<br />

09 GdStrChrgMod Charge start when<br />

connecting to the grid<br />

Off Off Equal<br />

Full Full charge<br />

Equal Equalization<br />

charge<br />

Both Full and<br />

equalization<br />

charge<br />