Parameter lists SMA Solar Technology AG<br />

133# Generator State<br />

Number Name <strong>Description</strong> Value<br />

(Plain text<br />

no.)<br />

Explanation<br />

01 GnDmdSrc Source for generator request: None (1) No request<br />

Bat (2) State-dependent<br />

battery charging<br />

Lod (3) Load-dependent<br />

Tim (4) Time-controlled<br />

Run1h (5) Requested for 1 hour<br />

Start (6) Manually started<br />

ExtSrcReq (7) Requested via an<br />

external source<br />

02 GnStt Generator state Off (1) Off<br />

Init (2) Init<br />

Ready (3) Waiting for request<br />

(ready)<br />

Warm (4) Warming up<br />

Connect (5) Connecting<br />

Run (6) Operation<br />

Retry (7) Restarting<br />

Disconnect (8) Disconnecting<br />

Cool (9) Cooling down<br />

Lock (10) Locked after<br />

operation<br />

Fail (11) Error<br />

FailLock (12) Locked after error<br />

03 GnRmgTm Remaining time of the generator<br />

(minimum run time) in hours,<br />

minutes and seconds<br />

04 GnRnStt Status of the generator<br />

feedback at the <strong>Sun</strong>ny Island<br />

master<br />

Off (1) Off<br />

On (2) On<br />

152 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>