Parameter lists SMA Solar Technology AG<br />

19.1.2 Battery Meters (120#)<br />

Number Name <strong>Description</strong> Value<br />

(Plain text<br />

no.)<br />

Explanation<br />

01 BatSoc Momentary state of charge of<br />

battery (SOC) in %<br />

02 BatVtg Battery voltage in V<br />

03 BatChrgVtg Charging voltage target value in V<br />

04 AptTmRmg Remaining absorption time in<br />

hours, minutes and seconds<br />

05 BatChrgOp Active charging process Boost (1) Boost charge<br />

Full (2) Full charge<br />

Float (3;7) Float charge<br />

Equalize<br />

(4;5)<br />

Equalization charge<br />

Silent (6;8) Silent mode (resting<br />

phase)<br />

06 TotBatCur Total battery current of the cluster<br />

in A<br />

07 BatTmp Battery temperature in °C<br />

08 RmgTmFul Remaining time until next full<br />

charge in days<br />

09 RmgTmEqu Remaining time until next<br />

equalization charge in days<br />

10 AptPhs Status of the absorption phase Off (1) Absorption phase not<br />

active<br />

On (2) Absorption phase is<br />

active<br />

11 BatSocErr Estimated error of the state of<br />

charge in %<br />