PV Inverters in Stand-alone Grid Systems SMA Solar Technology AG<br />

This function is shown in the following figure:<br />

The different settings have the following meanings:<br />

• fAC = 0 refers to the base frequency of the micro grid created by the <strong>Sun</strong>ny Island.<br />

• fAC Delta‒ and fAC Delta+ refer to the maximum range in which the PV inverter is active relative<br />

to fAC = 0. Fac-delta– and Fac-delta+, for example.<br />

• fAC Start Delta is the frequency increase relative to fAC = 0, at which point the power adjustment<br />

via frequency begins.<br />

• fAC Limit Delta is the frequency increase relative to fAC = 0, at which point the power adjustment<br />

via frequency ends. The power of the PV inverter at this point is 0 W.<br />

If the value is below the fAC Delta– limit or exceeds the fAC Delta+ limit, the PV inverters disconnect<br />

from the grid.<br />

When FSPC is activated and the diesel generator in the stand-alone grid is operating, the diesel<br />

generator determines the frequency, and the PV inverters react to certain changes in the diesel<br />

generator frequency. The diesel generators generally operate at 50 Hz under load. For this reason,<br />

in most cases the PV inverters will deliver their entire power to the stand-alone grid, even when the<br />

generator is running.<br />

If the current battery voltage (V Bat ) is greater than the nominal battery voltage (V Bat, nom )<br />

and is also to be synchronized with an external source (generator), the <strong>Sun</strong>ny Island<br />

temporarily increases the frequency and disconnects the PV inverters using the frequency<br />

shutdown method (overfrequency). Afterwards, it synchronizes with the generator.<br />

144 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>