SMA Solar Technology AG PV Inverters in Stand-alone Grid Systems<br />

17.1.1 Setting via Rotary Switch with SB 3000TL/4000TL/5000TL.<br />

1. Set the rotary switch, A, with a screwdriver (2.5 mm) to position "E".<br />

2. Set the chosen language via the rotary switch B with a screwdriver (2.5 mm). You can find the<br />

configuration of the switch in the manual of the PV inverter.<br />

☑ Stand-alone grid operation and the desired language have been set.<br />

17.1.2 Setting via Rotary Switch with SB 2000HF/2500HF/<br />

3000HF and STP 10000TL/12000TL/15000TL/17000TL<br />

1. Set the rotary switch, A, with a screwdriver (2.5 mm) to the desired position:<br />

– Position "D" = Stand-alone grid operation at 60 Hz<br />

– Position "E" = Stand-alone grid operation at 50 Hz<br />

2. Set the chosen language via the rotary switch B with a screwdriver (2.5 mm). You can find the<br />

configuration of the switch in the manual of the PV inverter.<br />

☑ Stand-alone grid operation and the desired language have been set.<br />

17.1.3 Setting via Communication or Software<br />

You can set the PV inverter to stand-alone grid operation (OFF-Grid) via communication or software.<br />

Depending on the device type, the stand-alone grid operation (OFF-Grid) is set using the parameter<br />

"CntrySet", "Set country standard" or "Default". Carry out the parameter change as described in the<br />

manual of the communication device or of the software.<br />

Setting the parameter "CntrySet" or "Set country standard"<br />

The setting to stand-alone grid operation using the parameter "CntrySet" or "Set country<br />

standard" can only be performed with the following PV inverters:<br />

• SB 3000TL/4000TL/5000TL<br />

• SB 2000HF/2500HF/3000HF<br />

• STP 10000TL/12000TL/15000TL/17000TL<br />

Setting the "Default" parameter<br />

The setting to stand-alone grid operation using the parameter "Default" can only be<br />

performed with the following PV inverters:<br />

• SB 1200, SB1700, SB 2500, SB 3000, SB 3300, SB 3800, SMC 4600A,<br />

SMC 5000A, SMC 6000A, SMC 7000HV, SMC 6000TL, SMC 7000TL,<br />

SMC 8000TL, SMC 9000TL, SMC 10000TL, SMC 11000TL<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 141