Relays SMA Solar Technology AG<br />

15 Relays<br />

The <strong>Sun</strong>ny Island offers you several options for the control of internal and external processes. For this<br />

purpose, two relays are integrated into the device, to which you can assign functions using the<br />

parameters "241.01 Rly1Op" and "241.02 Rly2Op".<br />

You can find more information on both relays in section 6.4.4 ”Multi-function Relay 1 and 2”<br />

(page 45). The different settings have the following meanings:<br />

Function/Setting Meaning Function description<br />

Off Off Relay remains permanently switched<br />

off (deactivated).<br />

On On Relay remains permanently switched<br />

on (e.g. relay function test during<br />

commissioning)<br />

AutoGn Automatic generator request The generator is automatically<br />

activated due to set criteria (see<br />

section 14.1.5 ”Automatic Generator<br />

Operation” (page 114)).<br />

AutoLodExt Automatic load shedding dependent<br />

on an external source<br />

Automatic connection / disconnection<br />

of loads. Connection occurs if the<br />

device is connected to an external<br />

source (e.g. generator), or if the<br />

Lod1Soc limits are exceeded. See<br />

section 12.1 ”Load Shedding”<br />

(page 92).<br />

AutoLodSoc1 Auto LoadShedding Soc1 Automatic connection / disconnection<br />

of loads. Connection only if Lod1Soc<br />

limits are exceeded. See section<br />

12.1 ”Load Shedding” (page 92).<br />

AutoLodSoc2 Auto LoadShedding Soc2 Automatic load disconnection.<br />

Connection only if Lod2Soc limits are<br />

exceeded. See section 12.1 ”Load<br />

Shedding” (page 92).<br />

Tm1 Timer 1 (time-controlled switching of<br />

relay 1)<br />

Tm2 Timer 2 (time-controlled switching of<br />

relay 2)<br />

Programmable timer (once, daily,<br />

weekly) with duty cycle.<br />

Programmable timer (once, daily,<br />

weekly) with duty cycle.<br />

AptPhs Absorption phase is active Relay switching when battery charge is<br />

in absorption phase.<br />

GnRn Generator active Relay switching when generator is in<br />

operation and connected.<br />

ExtVfOk External voltage and frequency is OK External voltage and frequency are<br />

within the valid range for connection.<br />

130 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>