Connecting External Sources SMA Solar Technology AG<br />

14.3 Generator and Grid<br />

In addition to the power distribution grid, a generator can also be integrated into a stand-alone grid<br />

system as a secondary protective measure. This is particularly useful in case of long-term grid failures,<br />

even if the battery size is no longer sufficient to bridge the failure after a period of time.<br />

The common solution in such cases is using a transfer switch, which can be purchased as a manual<br />

or automatic switch. By using such a switch, a diesel generator is connected to the AC2 connection,<br />

to which the power distribution grid is normally connected, as displayed in the figure below:<br />

To use such a switch, carry out the installation as follows.<br />

NOTICE!<br />

Destruction of the <strong>Sun</strong>ny Island due to abrupt switch from power distribution grid<br />

to generator and vice versa.<br />

• If an automatic switch is installed, make sure that it completely disconnects the<br />

<strong>Sun</strong>ny Island from the grid and from the generator for at least 5 seconds.<br />

• If a manual switch is installed, leave the switch in OFF-position for at least 5 seconds<br />

before switching to the new position.<br />

• Upon request to the SMA Serviceline, you can obtain the manual on how to install a<br />

switch for connecting the <strong>Sun</strong>ny Island to the power distribution grid and to a<br />

generator.<br />

1. Connect the negative pole of the DigIn connection on the <strong>Sun</strong>ny Island to the negative pole of<br />

the BatVtgOut connection, also located on the <strong>Sun</strong>ny Island.<br />

2. Connect the positive pole of the DigIn connection to a NO connection of an auxiliary contact<br />

of the transfer switch.<br />

128 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>