Connecting External Sources SMA Solar Technology AG 14.2.7 Disturbances Reverse Power If the defined reverse power ("232.09 GdRvPwr" parameter) is exceeded for the time "232.10 GdRvTm", the grid is disconnected. After reverse power, connection is blocked for at least "231.03 ExtLkTm". Grid failure If a grid failure is detected (failure on the master phase), the grid is disconnected immediately. Grid Phase Failure The failure of a phase (e.g. broken fuse) on a slave device is treated as a phase failure. The slave device then disconnects this phase. If the phase is detected as being available again, it is reconnected. The phase failure on the master device is treated as a grid failure (see above). Slave Device Failure If a slave device fails, the system continues to operate using the remaining devices of the cluster. 14.2.8 Limits and Power Adjustment The Sunny Island burdens the grid at each phase with the current defined in the parameter "232.03 GdCurNom". The power that is not directly used by the consumers flows into the battery for charging. At the same time, the limits for the AC charging current limit ("210.02 InvChrgCurMax" parameter) on the Sunny Island and the DC charging current limit ("222.01 BatChrgCurMax" parameter) are active. If the battery voltage reaches the charging voltage target value, it is also reduced (see section 13.4 ”Charge Control” (page 99)). If the current set using the parameter "232.03 GdCurNom" is not sufficient for powering the consumers, the battery provides support. Silent mode active When silent mode is activated, the grid cannot be supported! The grid may temporarily fail. This way, the voltage fed to the loads will be interrupted for a short time. 126 SI5048-TB-TEN110340 Technical Description

SMA Solar Technology AG Connecting External Sources 14.2.9 Operation Together with PV Inverters Since electricity is fed into the grid through the relay of the Sunny Island, it must be prevented from overloading. For this reason, reverse power monitoring is used that, if required, disconnects the connection to the power distribution grid if the reverse power limit is exceeded. NOTICE! Damage to the Sunny Island due to high currents. If the current via the relay exceeds the maximum permissible current, the Sunny Island disconnects from the grid (relay protection). • The quantity of PV output installed in the stand-alone grid must never exceed the maximum quantity allowed by the AC input (see section 22 ”Technical Data” (page 217)). If the battery is fully charged, the frequency limits the power output of the AC feeding-in generators (PV inverter) in the stand-alone grid. If the grid is now reconnected, the frequency would be lowered, if required, as the Sunny Island is synchronized with the grid. The AC feed-in generators would then feed additional energy into the system and possibly overload the batteries. In order to prevent this, in this case the stand-alone grid frequency is temporarily increased, in line with the synchronization, until the AC feed-in generators are disconnected from the stand-alone grid system as a result of the grid limits being exceeded. Technical Description SI5048-TB-TEN110340 127

SMA Solar Technology AG Connecting External Sources<br />

14.2.9 Operation Together with PV Inverters<br />

Since electricity is fed into the grid through the relay of the <strong>Sun</strong>ny Island, it must be prevented from<br />

overloading. For this reason, reverse power monitoring is used that, if required, disconnects the<br />

connection to the power distribution grid if the reverse power limit is exceeded.<br />

NOTICE!<br />

Damage to the <strong>Sun</strong>ny Island due to high currents.<br />

If the current via the relay exceeds the maximum permissible current, the <strong>Sun</strong>ny Island<br />

disconnects from the grid (relay protection).<br />

• The quantity of PV output installed in the stand-alone grid must never exceed the<br />

maximum quantity allowed by the AC input (see section 22 ”<strong>Technical</strong> Data”<br />

(page 217)).<br />

If the battery is fully charged, the frequency limits the power output of the AC feeding-in generators<br />

(PV inverter) in the stand-alone grid. If the grid is now reconnected, the frequency would be lowered,<br />

if required, as the <strong>Sun</strong>ny Island is synchronized with the grid. The AC feed-in generators would then<br />

feed additional energy into the system and possibly overload the batteries. In order to prevent this, in<br />

this case the stand-alone grid frequency is temporarily increased, in line with the synchronization, until<br />

the AC feed-in generators are disconnected from the stand-alone grid system as a result of the grid<br />

limits being exceeded.<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 127