Connecting External Sources SMA Solar Technology AG<br />

14.2.7 Disturbances<br />

Reverse Power<br />

If the defined reverse power ("232.09 GdRvPwr" parameter) is exceeded for the time<br />

"232.10 GdRvTm", the grid is disconnected. After reverse power, connection is blocked for at least<br />

"231.03 ExtLkTm".<br />

Grid failure<br />

If a grid failure is detected (failure on the master phase), the grid is disconnected immediately.<br />

Grid Phase Failure<br />

The failure of a phase (e.g. broken fuse) on a slave device is treated as a phase failure. The slave<br />

device then disconnects this phase. If the phase is detected as being available again, it is reconnected.<br />

The phase failure on the master device is treated as a grid failure (see above).<br />

Slave Device Failure<br />

If a slave device fails, the system continues to operate using the remaining devices of the cluster.<br />

14.2.8 Limits and Power Adjustment<br />

The <strong>Sun</strong>ny Island burdens the grid at each phase with the current defined in the parameter<br />

"232.03 GdCurNom". The power that is not directly used by the consumers flows into the battery for<br />

charging. At the same time, the limits for the AC charging current limit ("210.02 InvChrgCurMax"<br />

parameter) on the <strong>Sun</strong>ny Island and the DC charging current limit ("222.01 BatChrgCurMax"<br />

parameter) are active. If the battery voltage reaches the charging voltage target value, it is also<br />

reduced (see section 13.4 ”Charge Control” (page 99)).<br />

If the current set using the parameter "232.03 GdCurNom" is not sufficient for powering the<br />

consumers, the battery provides support.<br />

Silent mode active<br />

When silent mode is activated, the grid cannot be supported!<br />

The grid may temporarily fail. This way, the voltage fed to the loads will be interrupted for<br />

a short time.<br />

126 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>