SMA Solar Technology AG Connecting External Sources<br />

Feeding Operation<br />

Whether energy is fed from the stand-alone grid system into the power distribution grid is controlled<br />

using the "232.08 GdMod" parameter.<br />

In all cases, make sure to consult your network operator if grid feed-in is possible.<br />

If GridCharge (Default) is set, no energy is fed into the grid. If GridFeed is set, energy is fed into the<br />

grid.<br />

Feeding into the grid on the DC side<br />

In order to allow electricity to be fed from the DC side into the grid, the battery voltage in<br />

a charged battery (on the grid) must be increased by external DC chargers or the<br />

<strong>Sun</strong>ny Island Charger above the nominal charging voltage.<br />

AC feed-in generators on the stand-alone grid side (<strong>Sun</strong>ny Boy) can feed their energy into the grid<br />

through the internal transfer relay of the <strong>Sun</strong>ny Island; for limitations, see section 14.1.6 ”Limits and<br />

Power Adjustment” (page 118).<br />

14.2.6 Grid Failure<br />

A grid failure is characterized by the voltage or frequency being outside of the permissible limits (see<br />

section 14.2.4 ”Grid Reconnection” (page 124)) or the power distribution grid being disconnected.<br />

In this case, the time limits are relevant: Smaller deviations are permitted for longer than large<br />

deviations (see section 14.2.1 ”Voltage and Frequency Limits” (page 123)).<br />

In case of a grid fault/failure, the power distribution grid is disconnected and the inverter starts, from<br />

silent mode.<br />

Waking up from the silent mode<br />

If the <strong>Sun</strong>ny Island is in silent mode when there is a power distribution grid failure, there is<br />

a short grid failure in the stand-alone grid (see section 13.4.5 ”Silent Mode” (page 103)).<br />