Connecting External Sources SMA Solar Technology AG<br />

The generator is disconnected by the <strong>Sun</strong>ny Island after the GENRDY signal has been withdrawn by<br />

the GenMan.<br />

NOTICE!<br />

Occurrence of unpredictable operating states.<br />

• Never carry out a manual start directly at the generator.<br />

• Observe the indications in the GenMan manual.<br />

14.1.3 Generator Operation<br />

The <strong>Sun</strong>ny Island allows automatic operation (depending on state of charge or load)<br />

(see 14.1.5 ”Automatic Generator Operation” (page 114)). In addition, manual operation is also<br />

possible.<br />

14.1.4 Manual Generator Operation<br />

The manual operating modes for the generator management are tripped using the<br />

"540.01 GnManStr" parameter. Here, a distinction is made between the following operating modes:<br />

Auto: In this operating mode, the generator is automatically started due to the settings.<br />

This includes the start via the state of charge or the consumer power or by the<br />

request for a manual equalization charge.<br />

("520.01 ChrgSelMan" = Start).<br />

Stop: The generator is manually stopped. The current generator request is canceled –<br />

immediate disconnection from generator and change to lock state. Once the lockout<br />

time has ended, the generator switches into automatic operation.<br />

Start: Manual generator start – the generator runs "continuously" until stopped.<br />

The generator can only be manually stopped.<br />

Run1h: Operation for one hour. Once the lockout time has expired, the transition back into<br />

automatic mode follows.<br />

An equalization charge can be manually started using the "520.01 ChrgSelMan" parameter.<br />

This sets the battery management (see 13 ”Battery Management” (page 97)) in the equalization<br />

charge state and the generator is requested. This request persists until equalization charge has been<br />

completed.<br />

The following process diagrams provide an overview of the start/stop behavior of the <strong>Sun</strong>ny Island<br />

during manual generator operation:<br />

112 SI<strong>5048</strong>-TB-TEN110340 <strong>Technical</strong> <strong>Description</strong>