SMA Solar Technology AG Connecting External Sources<br />

GenMan<br />

Generator request<br />

If the generator is running after being externally started and a generator request occurs,<br />

the GnReq signal is disabled until the generator is externally stopped again and the stop<br />

time has expired.<br />

If a GenMan (generator manager) is integrated into the system, it assumes direct control of the<br />

generator. It is connected between the <strong>Sun</strong>ny Island and the generator. The GenMan is responsible<br />

for controlling the generator (warm up time, cooling off time and autostart).<br />

The <strong>Sun</strong>ny Island requests the generator from the GenMan via the GnReq signal and keeps the signal<br />

active as long as the generator is required. The GenMan returns the GENRDY signal via DigIn when<br />

the generator is ready for operation. Then the <strong>Sun</strong>ny Island synchronizes and connects. If the<br />

generator is no longer required, the <strong>Sun</strong>ny Island disconnects itself and disables the GnReq signal.<br />

The following figure shows the principle of starting the generator via the "GenMan" generator control:<br />

A manual generator start at the GenMan is notified to the <strong>Sun</strong>ny Island via the GENRDY signal.<br />

The device synchronizes and connects.<br />

If the generator is started manually and externally at the GenMan, the <strong>Sun</strong>ny Island blocks the GnReq<br />

signal:<br />

• Manual stop and start at the <strong>Sun</strong>ny Island are ignored.<br />

• Internal requests (e.g. via battery state of charge) are ignored.<br />

The generator was started manually using GenMan.<br />

If the generator has been manually started at the GenMan, it must also be stopped there.<br />

<strong>Technical</strong> <strong>Description</strong> SI<strong>5048</strong>-TB-TEN110340 111