Connecting External Sources SMA Solar Technology AG<br />

Autostart<br />

This allows autostart generators to be directly integrated. They have a separate internal controller that<br />

controls the start procedure.<br />

The <strong>Sun</strong>ny Island requests the generator via the GnReq signal. If the generator voltage and frequency<br />

are within the set limits (see section 14.1.6 ”Limits and Power Adjustment” (page 118)), the device is<br />

synchronized and connected following the warm up time.<br />

The <strong>Sun</strong>ny Island keeps the request signal active until a disconnection is made and the set follow-up<br />

time has expired.<br />

After-run<br />

Autostart generators can have an internal after-run cycle that is only activated when the<br />

request has been disabled. This can extend the follow-up time accordingly.<br />

Internal warm-up phase<br />

With some generator types, the voltage is only switched to the output after the internal<br />

warm-up phase is finished. Therefore, the time of the generator activation sequence is<br />

monitored internally.<br />

• Time for connection = 10 minutes for GenMan<br />

or<br />

• 2 x "234.12 GnWarmTm" + 2 minutes for manual and automatic start<br />

The following figure shows the wiring for a generator capable of autostart:<br />

If the generator is started manually in this operating mode, the <strong>Sun</strong>ny Island detects the running<br />

generator and connects it once the warm-up time has expired. If the generator is externally stopped,<br />

this is detected, the generator is disconnected and the stand-alone grid system is continued to be<br />

supplied.<br />