SMA Solar Technology AG Connecting External Sources<br />

14 Connecting External Sources<br />

The <strong>Sun</strong>ny Island supports the integration of external energy sources. Here, a distinction is made<br />

between the integration of a generator and the integration of the power distribution grid.<br />

Both the generator as well as the power distribution grid are integrated through the AC2 connection<br />

of the <strong>Sun</strong>ny Island. A single-phase or a three-phase connection is possible. In the case of single-phase<br />

parallel operation, the transfer relays are operated in parallel, making it possible to use a<br />

correspondingly larger current, which in turn allows for a generator or grid connections with a higher<br />

capacity.<br />

Connecting in a single-phase parallel system:<br />

When installing parallel 1-phase systems, the connection cables for AC1 and AC2 of all<br />

<strong>Sun</strong>ny Islands must have the same cable cross-sections and cable lengths.<br />

The <strong>Sun</strong>ny Island has separate parameters for the grid and generator. This generally allows both<br />

operating modes to be used without making additional adjustments. The parameter settings and<br />

display values distinguish between settings or values which are generator-specific or grid-specific and<br />

settings or values (EXT) common to both grid and generator.<br />

14.1 Generator<br />

The <strong>Sun</strong>ny Island can start or stop a generator depending on consumer power or battery state of<br />

charge. In this case, diverse limits and times are taken into consideration (see section<br />

14.1.5 ”Automatic Generator Operation” (page 114)).<br />

Extended Generator Management<br />

If necessary, the <strong>Sun</strong>ny Island and generator supply consumers together. The total of the (nominal)<br />