Technical Information<br />
<strong>PV</strong> <strong>Inverters</strong><br />
<strong>Use</strong> <strong>of</strong> <strong>PV</strong> <strong><strong>in</strong>verters</strong> <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> <strong>and</strong> <strong>backup</strong> <strong>systems</strong> <strong>in</strong> North <strong>and</strong> South America<br />
Table <strong>of</strong> Contents<br />
Both <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> <strong>and</strong> <strong>in</strong> the event <strong>of</strong> <strong>grid</strong> failures <strong>in</strong> <strong>backup</strong> <strong>systems</strong>, <strong>grid</strong> fluctuations <strong>in</strong> the st<strong>and</strong>-alone<br />
<strong>grid</strong> are possible. This may cause severe deviations <strong>in</strong> nom<strong>in</strong>al voltage <strong>and</strong> nom<strong>in</strong>al frequency. Despite such<br />
fluctuations, all the components <strong>of</strong> the system must function without problems.<br />
This technical <strong>in</strong>formation will <strong>in</strong>form you about the follow<strong>in</strong>g topics:<br />
• Which <strong>PV</strong> <strong><strong>in</strong>verters</strong> you can use <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> <strong>and</strong> <strong>backup</strong> <strong>systems</strong>.<br />
• Which parameters you need to set <strong>in</strong> the <strong>PV</strong> <strong>in</strong>verter.<br />
• What type <strong>of</strong> communication you need to <strong>in</strong>stall <strong>in</strong> <strong>backup</strong> <strong>systems</strong>.<br />
• Which values the parameters <strong>of</strong> <strong>PV</strong> <strong><strong>in</strong>verters</strong> will display <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> operation.<br />
• How the output power <strong>of</strong> the <strong>PV</strong> <strong>in</strong>verter can be limited by the Frequency-Shift Power Control function<br />
(FSPC) <strong>of</strong> the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter.<br />
SB-OffGrid-TI-eng-UUS123813 | Version 1.3 CA US
SMA America, LLC Choos<strong>in</strong>g the <strong>PV</strong> Inverter<br />
1 Choos<strong>in</strong>g the <strong>PV</strong> Inverter<br />
You can use the follow<strong>in</strong>g <strong>PV</strong> <strong><strong>in</strong>verters</strong> <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> or <strong>backup</strong> <strong>systems</strong>:<br />
<strong>PV</strong> <strong>in</strong>verter Off-<strong>grid</strong> system Backup system<br />
Sunny Boy 700-U x*<br />
Sunny Boy 1800-U x*<br />
Sunny Boy 2100-U x*<br />
Sunny Boy 2500-U x*<br />
Sunny Boy 3300-U x*<br />
Sunny Boy 3800-U x*<br />
Sunny Boy 6000-U x*<br />
Sunny Boy 3000-US x* x*<br />
Sunny Boy 4000-US x* x*<br />
Sunny Boy 5000-US x* x*<br />
Sunny Boy 6000-US x* x*<br />
Sunny Boy 7000-US x* x*<br />
Sunny Boy 8000-US x* x*<br />
Sunny Boy 8000TL-US x**<br />
x**<br />
Sunny Boy 9000TL-US x** x**<br />
Sunny Boy 10000TL-US x** x**<br />
* compatible<br />
** compatible as <strong>of</strong> firmware version 1.93<br />
System failures due to excessive power output <strong>of</strong> AC sources <strong>in</strong> the st<strong>and</strong>-alone <strong>grid</strong><br />
If the power <strong>of</strong> the AC sources (e.g., <strong>PV</strong> <strong><strong>in</strong>verters</strong>) <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> or <strong>backup</strong> <strong>systems</strong> is too high, it may<br />
cause system failures.<br />
• Design the total nom<strong>in</strong>al AC power <strong>of</strong> the <strong>PV</strong> <strong><strong>in</strong>verters</strong> to be no more than twice as high as the<br />
nom<strong>in</strong>al AC power <strong>of</strong> the <strong>of</strong>f-<strong>grid</strong> <strong><strong>in</strong>verters</strong>.<br />
• If w<strong>in</strong>d energy <strong><strong>in</strong>verters</strong> feed <strong>in</strong>to the st<strong>and</strong>-alone <strong>grid</strong>, design the total nom<strong>in</strong>al power <strong>of</strong> the AC<br />
sources <strong>in</strong> the st<strong>and</strong>-alone <strong>grid</strong> to be no larger than the nom<strong>in</strong>al AC power <strong>of</strong> the <strong>of</strong>f-<strong>grid</strong> <strong><strong>in</strong>verters</strong>.<br />
• Per 1 000 W nom<strong>in</strong>al AC power <strong>of</strong> the AC sources <strong>in</strong> the st<strong>and</strong>-alone <strong>grid</strong>, allow at least 100 Ah<br />
battery capacity.<br />
SB-OffGrid-TI-eng-UUS123813 2/8
SMA America, LLC Configuration <strong>of</strong> the <strong>PV</strong> <strong>Inverters</strong><br />
2 Configuration <strong>of</strong> the <strong>PV</strong> <strong>Inverters</strong><br />
2.1 Configuration Options<br />
WARNING<br />
Danger to life due to electric shock<br />
If the power distribution <strong>grid</strong> fails, there is a risk <strong>of</strong> backfeed <strong>in</strong> <strong>PV</strong> <strong><strong>in</strong>verters</strong> which are configured for<br />
<strong>of</strong>f-<strong>grid</strong> operation.<br />
• F<strong>in</strong>d out about the st<strong>and</strong>ards <strong>and</strong> guidel<strong>in</strong>es applicable to <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> <strong>and</strong> <strong>backup</strong> <strong>systems</strong> at<br />
your location.<br />
• Only operate <strong>PV</strong> <strong><strong>in</strong>verters</strong> configured for <strong>of</strong>f-<strong>grid</strong> operation <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> <strong>systems</strong> or <strong>backup</strong> <strong>systems</strong>.<br />
• Coord<strong>in</strong>ate the parameter sett<strong>in</strong>gs for <strong>PV</strong> <strong><strong>in</strong>verters</strong> <strong>and</strong> Sunny Isl<strong>and</strong> <strong><strong>in</strong>verters</strong> with the respective <strong>grid</strong><br />
operator.<br />
Configuration with Communication Products<br />
Code required to change <strong>grid</strong>-relevant parameters<br />
To change the <strong>grid</strong>-relevant parameters <strong>in</strong> the <strong>PV</strong> <strong>in</strong>verter, you need a special code. To obta<strong>in</strong> this code,<br />
contact SMA America, LLC on +1 916 625 0870.<br />
You can configure the <strong>PV</strong> <strong><strong>in</strong>verters</strong> with the follow<strong>in</strong>g communication products:<br />
<strong>PV</strong> <strong>in</strong>verter Sunny Boy<br />
Control<br />
Sunny WebBox Computer with<br />
Sunny Data /<br />
Sunny Data<br />
Control s<strong>of</strong>tware<br />
Computer with<br />
Bluetooth<br />
Wireless<br />
Technology ®<br />
<strong>and</strong> Sunny<br />
Explorer<br />
s<strong>of</strong>tware<br />
Sunny Boy 700-U x* x* x**<br />
Sunny Boy 1800-U x* x* x**<br />
Sunny Boy 2100-U x* x* x**<br />
Sunny Boy 2500-U x* x* x**<br />
Sunny Boy 3300-U x* x* x**<br />
Sunny Boy 3800-U x* x* x**<br />
Sunny Boy 6000-U x* x* x** x*<br />
Sunny Boy 3000-US x* x* x** x*<br />
SB-OffGrid-TI-eng-UUS123813 3/8
SMA America, LLC Configuration <strong>of</strong> the <strong>PV</strong> <strong>Inverters</strong><br />
<strong>PV</strong> <strong>in</strong>verter Sunny Boy<br />
Control<br />
Sunny WebBox Computer with<br />
Sunny Data /<br />
Sunny Data<br />
Control s<strong>of</strong>tware<br />
Sunny Boy 4000-US x* x* x** x*<br />
Sunny Boy 5000-US x* x* x** x*<br />
Sunny Boy 6000-US x* x* x** x*<br />
Sunny Boy 7000-US x* x* x** x*<br />
Sunny Boy 8000-US x* x* x** x*<br />
Sunny Boy 8000TL-US x* x* x** x*<br />
Sunny Boy 9000TL-US x* x* x** x*<br />
Sunny Boy 10000TL-US x* x* x** x*<br />
* compatible<br />
** You will also need a service cable for data transmission (USB Service Interface, SMA order number: USBPBS).<br />
Computer with<br />
Bluetooth<br />
Wireless<br />
Technology ®<br />
<strong>and</strong> Sunny<br />
Explorer<br />
s<strong>of</strong>tware<br />
You can configure the <strong>PV</strong> <strong><strong>in</strong>verters</strong> for <strong>of</strong>f-<strong>grid</strong> operation with the parameters "Default" <strong>and</strong> "BackupMode"<br />
(see <strong>in</strong>stallation manual <strong>of</strong> the respective communication product).<br />
SB-OffGrid-TI-eng-UUS123813 4/8
SMA America, LLC Configuration <strong>of</strong> the <strong>PV</strong> <strong>Inverters</strong><br />
2.2 Parameter Sett<strong>in</strong>g for Off-<strong>grid</strong> Operation<br />
The parameters "Default" <strong>and</strong> "BackupMode" are used to set the <strong>PV</strong> <strong><strong>in</strong>verters</strong> to <strong>of</strong>f-<strong>grid</strong> operation. With the<br />
"Default" parameter, you can set the country data set. With the "BackupMode" parameter you can set whether<br />
the <strong>PV</strong> <strong>in</strong>verter is to form a <strong>backup</strong> system with the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter via RS485.<br />
<strong>PV</strong> <strong><strong>in</strong>verters</strong> <strong>in</strong> an <strong>of</strong>f-<strong>grid</strong> system not connected to the power distribution <strong>grid</strong> must be configured accord<strong>in</strong>g to<br />
the follow<strong>in</strong>g table:<br />
<strong>PV</strong> <strong>in</strong>verter Parameters<br />
"Default" "BackupMode"<br />
Sunny Boy 700-U Off-Grid Not available<br />
Sunny Boy 1800-U Off-Grid Not available<br />
Sunny Boy 2100-U Off-Grid Not available<br />
Sunny Boy 2500-U Off-Grid Not available<br />
Sunny Boy 3300-U Off-Grid Not available<br />
Sunny Boy 3800-U Off-Grid Not available<br />
Sunny Boy 6000-U Off-Grid Not available<br />
Sunny Boy 3000-US Off-Grid Off<br />
Sunny Boy 4000-US Off-Grid Off<br />
Sunny Boy 5000-US Off-Grid Off<br />
Sunny Boy 6000-US Off-Grid Off<br />
Sunny Boy 7000-US Off-Grid Off<br />
Sunny Boy 8000-US Off-Grid Off<br />
Sunny Boy 8000TL-US Off-Grid*<br />
Off*<br />
Sunny Boy 9000TL-US Off-Grid* Off*<br />
Sunny Boy 10000TL-US Off-Grid* Off*<br />
* Can be adjusted as <strong>of</strong> firmware version 1.93<br />
2.3 Parameter Sett<strong>in</strong>gs for Back-up Operation<br />
In a <strong>backup</strong> system, the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter is connected to the power distribution <strong>grid</strong> <strong>and</strong> communicates with the<br />
<strong>PV</strong> <strong><strong>in</strong>verters</strong> via RS485. Therefore, you must equip the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter <strong>and</strong> each <strong>of</strong> the <strong>PV</strong> <strong><strong>in</strong>verters</strong> with an<br />
RS485 Piggy-Back. In a cluster, only the master <strong>of</strong> the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter must be equipped with an RS485<br />
Piggy-Back.<br />
The parameters "Default" <strong>and</strong> "BackupMode" are used to set the <strong>PV</strong> <strong><strong>in</strong>verters</strong> to <strong>of</strong>f-<strong>grid</strong> operation. With the<br />
"Default" parameter, you can set the country data set. With the "BackupMode" parameter you can set whether<br />
the <strong>PV</strong> <strong>in</strong>verter is to form a <strong>backup</strong> system with the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter via RS485.<br />
The <strong>PV</strong> <strong><strong>in</strong>verters</strong> must be configured accord<strong>in</strong>g to the follow<strong>in</strong>g table:<br />
SB-OffGrid-TI-eng-UUS123813 5/8
SMA America, LLC Configuration <strong>of</strong> the <strong>PV</strong> <strong>Inverters</strong><br />
<strong>PV</strong> <strong>in</strong>verter Parameters<br />
"Default" "BackupMode"<br />
Sunny Boy 3000-US UL1741 OnAll**<br />
Sunny Boy 4000-US UL1741 OnAll**<br />
Sunny Boy 5000-US UL1741 OnAll**<br />
Sunny Boy 6000-US UL1741 OnAll**<br />
Sunny Boy 7000-US UL1741 OnAll**<br />
Sunny Boy 8000-US UL1741 OnAll**<br />
Sunny Boy 8000TL-US UL1741*<br />
OnAll***<br />
Sunny Boy 9000TL-US UL1741* OnAll***<br />
Sunny Boy 10000TL-US UL1741* OnAll***<br />
* Can be adjusted as <strong>of</strong> firmware version 1.93<br />
** Even when the "BackupMode" parameter <strong>of</strong> the <strong>PV</strong> <strong>in</strong>verter is set to "OnAll", the system fulfills the requirements accord<strong>in</strong>g to<br />
UL1741.<br />
*** Even when the "BackupMode" parameter <strong>of</strong> the <strong>PV</strong> <strong>in</strong>verter is set to "OnAll", the system fulfills the requirements accord<strong>in</strong>g to<br />
UL1741. The parameter "BackupMode" can be adjusted as <strong>of</strong> firmware version 1.93.<br />
<strong>PV</strong> <strong><strong>in</strong>verters</strong> without the "BackupMode" parameter<br />
For <strong>PV</strong> <strong><strong>in</strong>verters</strong> without the "BackupMode" parameter, the "Default" parameter must be set to "UL1741".<br />
After these sett<strong>in</strong>gs have been made, the <strong>PV</strong> <strong>in</strong>verter is configured for operation on the power distribution<br />
<strong>grid</strong>. In the event <strong>of</strong> a power distribution <strong>grid</strong> failure, the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter is no longer able to regulate the<br />
<strong>PV</strong> <strong><strong>in</strong>verters</strong> by means <strong>of</strong> Frequency-Shift Power Control (FSPC). If there is an excessive supply <strong>of</strong> energy,<br />
the <strong>PV</strong> <strong><strong>in</strong>verters</strong> will disconnect.<br />
Backup <strong>systems</strong> with SI 4548-US-10, SI 5048U <strong>and</strong> SI 6048-US-10<br />
In the event <strong>of</strong> a power distribution <strong>grid</strong> failure, the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter sets the "Default" parameter <strong>of</strong> the <strong>PV</strong><br />
<strong>in</strong>verter to "OFF_Grid". Thus, if a <strong>grid</strong> failure occurs, the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter is able to regulate the <strong>PV</strong> <strong><strong>in</strong>verters</strong> via<br />
Frequency Shift Power Control (FSPC). When the <strong>grid</strong> returns, the <strong>of</strong>f-<strong>grid</strong> <strong>in</strong>verter sets the "Default" parameter<br />
<strong>of</strong> the <strong>PV</strong> <strong>in</strong>verter back to "UL1741".<br />
Backup <strong>systems</strong> with SI 4248U<br />
For operation with <strong>PV</strong> <strong><strong>in</strong>verters</strong>, you must set the "Sunny Boy" parameter <strong>of</strong> the SI 4248U to Yes <strong>and</strong> the<br />
"GridConnected" parameter to GridFeed<strong>PV</strong>.<br />
In the event <strong>of</strong> a power distribution <strong>grid</strong> failure, the SI 4248U regulates the power <strong>of</strong> the <strong>PV</strong> <strong><strong>in</strong>verters</strong> directly<br />
via RS485.<br />
SB-OffGrid-TI-eng-UUS123813 6/8
SMA America, LLC Values <strong>of</strong> the Parameters <strong>in</strong> Off-<strong>grid</strong> Operation<br />
3 Values <strong>of</strong> the Parameters <strong>in</strong> Off-<strong>grid</strong> Operation<br />
The sett<strong>in</strong>g <strong>of</strong> the "Default" parameter to "OFF_Grid" automatically sets the <strong>PV</strong> <strong>in</strong>verter parameters to the values<br />
listed <strong>in</strong> the follow<strong>in</strong>g table:<br />
Parameters Unit Value<br />
Test current mA Off (MSD=0)<br />
Vac.M<strong>in</strong> V 106 (‒12% Vac nom)<br />
Vac.Max V 132 (+10% Vac nom)<br />
Fac-delta‒ lower range <strong>in</strong> which the Sunny Boy is active Hz ‒3.0 (start<strong>in</strong>g from the base<br />
relative to f0<br />
frequency f0)<br />
Fac-max+ upper range <strong>in</strong> which the Sunny Boy is active Hz +3.0 (start<strong>in</strong>g from the base<br />
relative to f0<br />
frequency f0)<br />
dFac-Max max.rate <strong>of</strong> change Hz 4<br />
Fac-start delta frequency <strong>in</strong>crease <strong>in</strong> relation to f0, at which Hz 1 (start<strong>in</strong>g from the base<br />
po<strong>in</strong>t the frequency-based power adjustment beg<strong>in</strong>s<br />
frequency f0)<br />
Fac-Limit delta frequency <strong>in</strong>crease <strong>in</strong> relation to f0, at which Hz 2 (start<strong>in</strong>g from the base<br />
po<strong>in</strong>t the frequency-based power adjustment ends. The<br />
output <strong>of</strong> the Sunny Boy at this po<strong>in</strong>t is 0W<br />
frequency f0)<br />
SB-OffGrid-TI-eng-UUS123813 7/8
SMA America, LLC Frequency-Shift Power Control (FSPC)<br />
4 Frequency-Shift Power Control (FSPC)<br />
If <strong>PV</strong> <strong><strong>in</strong>verters</strong> are connected on the AC side <strong>in</strong> <strong>of</strong>f-<strong>grid</strong> operation or back-up operation, the Sunny Isl<strong>and</strong> must<br />
be able to limit their output power. This situation can occur when, for example, the Sunny Isl<strong>and</strong>'s batteries are<br />
fully charged <strong>and</strong> the <strong>PV</strong> power available from the <strong>PV</strong> array exceeds the power required by the connected<br />
loads.<br />
To prevent the excess energy from overcharg<strong>in</strong>g the battery, the Sunny Isl<strong>and</strong> recognizes this situation <strong>and</strong><br />
changes the frequency at the AC output. This frequency change is analyzed by the <strong>PV</strong> <strong>in</strong>verter. As soon as the<br />
power frequency <strong>in</strong>creases beyond the value specified by "Fac Start delta", the <strong>PV</strong> <strong>in</strong>verter limits its output<br />
power accord<strong>in</strong>gly.<br />
Figure 1: Operat<strong>in</strong>g pr<strong>in</strong>ciple <strong>of</strong> the FSPC<br />
The terms used here have the follow<strong>in</strong>g mean<strong>in</strong>gs:<br />
• fAC refers to the base frequency <strong>of</strong> the st<strong>and</strong>-alone <strong>grid</strong> (here 60 Hz).<br />
• fAC Delta– <strong>and</strong> fAC Delta+ refer to the maximum range relative to fAC <strong>in</strong> which the <strong>PV</strong> <strong>in</strong>verter is active.<br />
• fAC Start Delta is the frequency <strong>in</strong>crease relative to fAC , at which po<strong>in</strong>t the frequency-based power control<br />
beg<strong>in</strong>s.<br />
• fAC Limit Delta is the frequency <strong>in</strong>crease relative to fAC , at which po<strong>in</strong>t the frequency-based power control<br />
ends. The output power <strong>of</strong> the <strong>PV</strong> <strong>in</strong>verter at this po<strong>in</strong>t is 0 W.<br />
If the value is below the fAC Delta– limit or above the fAC Delta+ limit, the <strong>PV</strong> <strong><strong>in</strong>verters</strong> disconnect from the<br />
power distribution <strong>grid</strong>.<br />
When an external energy source, (e.g., a diesel generator) is operat<strong>in</strong>g <strong>in</strong> the st<strong>and</strong>-alone <strong>grid</strong>, this external<br />
energy source determ<strong>in</strong>es the frequency, <strong>and</strong> the <strong>PV</strong> <strong><strong>in</strong>verters</strong> set to <strong>of</strong>f-<strong>grid</strong> operation react to certa<strong>in</strong> frequency<br />
changes brought about by the external energy source.<br />
When diesel generators are used as external energy source, the output voltage frequency under load is<br />
60 Hz. For this reason, <strong>in</strong> most cases the <strong>PV</strong> <strong><strong>in</strong>verters</strong> will deliver their entire power to the st<strong>and</strong>-alone <strong>grid</strong>, even<br />
when the diesel generator is <strong>in</strong> operation.<br />
If the current battery voltage (VBat ) is greater than the nom<strong>in</strong>al battery voltage (VBat nom ) <strong>and</strong> is also to be<br />
synchronized with an external energy source, the Sunny Isl<strong>and</strong> temporarily <strong>in</strong>creases the frequency <strong>and</strong> the <strong>PV</strong><br />
<strong><strong>in</strong>verters</strong> disconnect via frequency shutdown (overfrequency). Afterwards, the Sunny Isl<strong>and</strong> synchronizes with<br />
the external energy source.<br />
SB-OffGrid-TI-eng-UUS123813 8/8<br />
.