•<br />

U.S. STEEL DUQUESNE WORKS<br />

HAER No. PA-115<br />

(Page 93)<br />

19*-0" high underground concrete basin has a capacity of 110,900<br />

gallons. Two 2400 gpm Wilson-Snyder vertical pumps are located<br />

above ground over the hotwell. A 200 hp U. s. Electrical Titan<br />

Line motor rated at 1185 rpm powers each pump.<br />

Construction and Installation Date: 1980.<br />

Q. Non-Evaporative Spray Water Well and Spray Water Pumps:<br />

Located adjacent to the gas cooler hotwell on its northern side<br />

is the spray water well for the non-evaporative water treatment<br />

recycle system. It is composed of 184,000 gallon capacity<br />

underground concrete basin measuring 32 , -6" wide x 40 f -0" long x<br />

19t-0" high. Sluice gates divide the basin into three cells, a<br />

gas washer spray water cell, a gas cooler spray water cell, and a<br />

standby cell. Three 7000 gpm Wilson-Snyder vertical pumps are<br />

located above ground over each cell. Each pump is powered by a<br />

150 hp U. S. Electrical Titan Line motor rated at 1180 rpm.<br />

Construction and Installation Date: 1980.<br />

R. Non-Evaporative Cooling Tower: The cooling tower for the<br />

non-evaporative water treatment recycle system is located<br />

adjacent to the gas washer hotwell, gas cooler hotwell, and spray<br />

water well on their eastern side. Manufactured by Resorcon Inc.,<br />

it is composed of two wet surface air coolers: one for gas washer<br />

water and one for gas cooler water. Each unit is made up of four<br />

cells sandwiched between two shell and tube type heat exchangers.<br />

The fans at each cell, manufactured by the Tuf-Lite Company, are<br />

each powered by a 60 hp Reliance Duty Master motor rated at<br />

890/1775 rpm. The capacity of the gas washer unit is 3000 gpm.<br />

The capacity of the gas cooler unit is 2400 gpm. Both units are<br />

designed for an inlet temperature of 125 degrees F. and an outlet<br />

temperature of 90 degrees F.<br />

Installation Date: 1980.<br />

S- Dorothy Six Chemical Dispersant Building and Associated<br />

Chemical Feed Equipment: Constructed of cinder block and set on a<br />

concrete foundation, the 16*-0" wide x 20'-8" long x 10*-8" high<br />

chemical dispersant building for the non-evaporative water<br />

treatment recycle system is located just north of the gas cooling<br />

tower at Dorothy Six. Three chemical storage tanks, two with a<br />

capacity of 1000 gallons and one with a capacity of 560 gallons,<br />

are located within the building. The chemical feed pumps which<br />

were associated with each tank have been removed.<br />

Construction and Installation Date: 1979.<br />

T. Non-Evaporative control Building and Associated Chemical<br />

Storage Tanks: Located just north of the non-evaporative cooling<br />

tower, the two story control building is 28*-0" wide x 68'-0"<br />

long. Constructed of cinder block, it is set on a concrete<br />

foundation. The main control panel for the non-evaporative water