System Description RIO / microLine
System Description RIO / microLine
System Description RIO / microLine
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Expansion Modules<br />
Digital • 4 Outputs Relay • AC/DC 24..240 V • 5 A <strong>RIO</strong> 4O R<br />
Slide contacts<br />
for internal bus<br />
Outputs<br />
X3.0 ... X3.3<br />
X4.0 ... X4.3<br />
Supply<br />
voltage:<br />
+24 V DC<br />
0 V DC<br />
Contacts for<br />
internal bus<br />
Channel<br />
monitoring<br />
(yellow: cursor,<br />
green: status)<br />
The <strong>RIO</strong> 4O R digital module provides 4 relay outputs with NO contacts. The<br />
channels are isolated from the internal bus by relay contacts. They switch loads<br />
up to 5 A for individual channels in AC or DC range of 24 to 240 V. The signal<br />
state of each channel can be read on an LED. Additional jumper levels can<br />
be created with the pluggable terminal extension.<br />
Block diagram<br />
Technical Data <strong>RIO</strong> 4O R<br />
Article number R5.364.0030.0<br />
Number of inputs/outputs 4 outputs relay, NO contact<br />
Data width 1 bit per channel I/O<br />
External supply voltage DC 24 V (±20%, max. 5% residual ripple)<br />
Power consumption 2 W from external 24 V supply<br />
0.25 W from internal 5 V supply<br />
Connection system<br />
Outputs<br />
Two-wire (with <strong>RIO</strong> KE 16 terminal extension: four-wire)<br />
Output current per output Max. 5 A<br />
Total current for whole module Max. 12 A<br />
Minimum contact load AC/DC 5 V / 10 mA<br />
Rated operating voltage AC/DC 24 ... 240 V<br />
Utilization category AC-15 Ue AC 230 V, Ie 3 A<br />
DC-13 Ue AC 24 V, Ie 2 A (acc. to IEC 60947-5-1)<br />
Permissible switching frequency ≤ 3600 switching cycles/h<br />
Mechanical service life 30 x 106 switching cycles<br />
Electrical service life 0.12 x 106 switching cycles AC-15 (20/2 A, AC 250 V, cosϕ = 0.3)<br />
Simultaneity 100%<br />
Free-wheeling diode Integrated<br />
Isolation Each channel individually isolated from internal bus by relay contact<br />
Signal delay