Issue date 2004-11-19 - Catalogue <strong>AS</strong>-<strong>Interface</strong> 2004/2005<br />

Inductive proximity switches<br />

Order code<br />

NBN40+U1+B3B<br />

Features<br />

VariKont ®<br />

Basic series<br />

40 mm not embeddable<br />

NO/NC programmable<br />

Position of the sensor<br />

head adjustable<br />

Oscillator monitoring<br />

ON/Off delay (disconnectable)<br />

A/B slave with extended<br />

addressing possibility for<br />

up to 62 slaves<br />

Technical data<br />

Rated operating distance s n 40 mm<br />

Installation not embeddable<br />

NO/NC programmable NBN40+U1+B3B<br />

Assured operating distance sa 0 ... 32.4 mm<br />

Reduction factor rAl 0.5<br />

Reduction factor rCu 0.45<br />

Reduction factor rV2A 0.85<br />

Operating voltage UB 26.5 ... 31.9 V via <strong>AS</strong>-i<br />

bus system<br />

Operating current Ie 25 mA<br />

Switching frequency f 0 ... 150 Hz<br />

Hysteresis H 1 ... 15 typ. 5 %<br />

Time delay before availability tv ≤ 1000 ms<br />

Operating voltage display LED, green<br />

Indication of the switching<br />

state<br />

LED, yellow<br />

Fault indication LED, red<br />

EMC in accordance with EN 60947-5-2<br />

Standards EN 60947-5-2<br />

Ambient temperature -25 ... 70 °C<br />

Connection type terminal compartment<br />

Core cross-section up to 2.5 mm2 Housing material PBT<br />

Sensing face PBT<br />

Protection degree IP68<br />

Electrical connection:<br />

B3B<br />

I<br />

2<br />

A S-i<br />

1/BN<br />

3/BU<br />

+<br />

-<br />

Programming Instructions<br />

Adress 00 preset, alterable<br />

via Busmaster<br />

or programming units<br />

IO-Code 0<br />

ID-Code A<br />

Data bit<br />

Bit Function<br />

D0 Switching state<br />

D1 not used<br />

D2 Oscillator monitoring<br />

D3 not used<br />

Parameter bit<br />

Bit Function<br />

P0 ON / Off delay<br />

activated* / deactivated<br />

P1 Switching element function<br />

NO* / NC<br />

P2 not used<br />

P3 not used<br />

*Standard setting<br />

NBN40+U1+B3B<br />

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany<br />

Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com<br />

249<br />

Masters and<br />

Gateways<br />

Power Supplies,<br />

Extender, Repeaters<br />

Safety at work<br />

I/O Modules<br />

Control cabinet<br />

I/O Modules<br />

Field application<br />

Analogue modules<br />

Other modules<br />

Inductive sensors<br />

Photoelectric<br />

sensors<br />

Rotary encoders<br />

Accessories

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!