18.01.2013 Views

Sensor systems 2 AS-Interface

Sensor systems 2 AS-Interface

Sensor systems 2 AS-Interface

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Issue date 2004-11-19 - Catalogue <strong>AS</strong>-<strong>Interface</strong> 2004/2005<br />

Model number AirBox K<br />

F-GE-MO<br />

<strong>AS</strong>-<strong>Interface</strong> - AirBox<br />

Pneumatic modules for 3/2-, 4/2, 5/2-, and 5/3-way valves are available as<br />

special versions (data sheets on request). The modules include two integrated<br />

pneumatic change-over contact outputs and are available in monostable<br />

and bistable versions.<br />

AirBox K<br />

F-SW-MO<br />

AirBox K<br />

F-GE-BI<br />

Selected technical data for AirBox K:<br />

Total current consumption < 270 mA,<br />

inputs: low < 1,5 mA / high > 6,5 mA or > 6 V,<br />

current loading 100 mA (200 mA with ext. power supply)<br />

short-circuit protected, max. switching frequency 5 Hz,<br />

pressure range 3 bar ... 8 bar, filtered compressed air (oiled or non-oiled),<br />

air flow 550 standard liter/min,<br />

auxiliary air supply pressure > 3 bar,<br />

protection class IP65,<br />

dimensions 152 mm x 60 mm x 45 mm (HxWxD),<br />

ambient temperature 0 °C ... 55 °C.<br />

All devices have UL, CSA, and <strong>AS</strong>-<strong>Interface</strong> approval.<br />

AirBox K<br />

F-SW-BI<br />

<strong>Sensor</strong> inputs 4 4 4 4<br />

Logical outputs 2 2 2 2<br />

<strong>AS</strong>-<strong>Interface</strong> power supply (yellow cable) ✓<br />

✓ ✓ ✓<br />

Auxiliary power supply (black cable) –<br />

✓ – ✓<br />

Valve function 3/2 NC 2 2 2 2<br />

Valve function 3/2 NO 2 2 2 2<br />

Valve function 4/2 2 2 2 2<br />

Valve function 5/2 2 2 2 2<br />

Valve function 5/3 ✓ ✓ ✓ ✓<br />

Middle position open 1 1 1 1<br />

Middle position ventilated 1 1 1 1<br />

Middle position closed – – – –<br />

Air flow [Nl] 0/6 bar 700 700 700 700<br />

Air flow [Nl] 5/6 bar 500 500 500 500<br />

Pressure range [bar] 3 ... 8 3 ... 8 3 ... 8 3 ... 8<br />

Additional drive air supply ❍<br />

❍ ❍ ❍<br />

Vacuum switchable ❍ ❍ ❍ ❍<br />

Exhaust outlet, filtered ✓ ✓ ✓ ✓<br />

Exhaust outlet, contained – – – –<br />

Manual actuation ✓ ✓ ✓ ✓<br />

tamper-proof ✓ ✓ ✓ ✓<br />

Electrically bistable – – ✓ ✓<br />

Protection class IP65 IP65 IP65 IP65<br />

Food industry ✩<br />

✩ ✩ ✩<br />

<strong>AS</strong>-<strong>Interface</strong> certification ✓ ✓ ✓ ✓<br />

Ident number 93.025 93.027 93.031 93.026<br />

3RK 1408-_ _ _ _ _ -0CA00 0MT00 1MT00 0CT00 1CT00<br />

✓ Standard<br />

– not available<br />

❍ optional<br />

✩ on request<br />

KM K-FK-SW Base for AirBox K module with external power supply over additional<br />

black flat cable, wall-mounted<br />

KM K-HS Tophat rail adaptor for AirBox K base<br />

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany<br />

Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com<br />

217<br />

Masters and<br />

Gateways<br />

Power Supplies,<br />

Extender, Repeaters<br />

Safety at work<br />

I/O Modules<br />

Control cabinet<br />

I/O Modules<br />

Field application<br />

Analogue modules<br />

Other modules<br />

Inductive sensors<br />

Photoelectric<br />

sensors<br />

Rotary encoders<br />

Accessories

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!