<strong>AS</strong>-<strong>Interface</strong> - Introduction<br />

16<br />

62<br />

Spec 2.1<br />

1.4 <strong>AS</strong>-<strong>Interface</strong> specification 2.1<br />

Functional description of the<br />

<strong>AS</strong>-<strong>Interface</strong> specification 2.1<br />

With the <strong>AS</strong>-<strong>Interface</strong> specification 2.1, which was defined in 1999 by the<br />

<strong>AS</strong>-<strong>Interface</strong> Association as a backwards-compatible extension retaining<br />

the protocol and physical parameters, significant advantages for the user<br />

were introduced:<br />

Number of nodes increased from 31 standard slaves to<br />

62 A/B slaves,<br />

enhanced diagnostic function with peripheral error bit,<br />

simple analogue value transmission with internal data handling,<br />

extension of the ID codes of the nodes.<br />

Devices in accordance with specification 2.1 are denoted on data sheets<br />

with this symbol.<br />

62 nodes on <strong>AS</strong>-<strong>Interface</strong> network<br />

To take advantage of these possibilities, a VB... Master/Gateway is needed.<br />

Standard slaves (as in specification 2.0), thanks to backwards compatibility,<br />

can still be connected to a new master using specification 2.1. However,<br />

two of the 62 possible addresses are occupied by one standard slave. The<br />

use of A/B Slaves on an "old" master is possible, by always setting the select<br />

bit to logical "0". Despite this, we don't recommend it, since a change to<br />

this bit will change the address, and it may thus be impossible to talk to the<br />

slave due to such a configuration error.<br />

The master message is almost unchanged in the specification 2.1. The only<br />

change is that the select bit "SEL" is transmitted in what used to be the<br />

fourth output bit "I3", which in addition to the address bits A0 ... A4 enables<br />

the extended A/B addressing.<br />

Each address can therefore be split into A and B addresses, i.e. in addresses<br />

15A and 15B.<br />

Since the fourth output bit is now used as an additional address bit, only 3<br />

output bits per slave can now be transmitted, that is, per <strong>AS</strong>-<strong>Interface</strong> network<br />

3* 62 = 186 output bits are set. The slave response remains unchanged,<br />

and there are now 4 * 62 = 248 bits of input data available.<br />

Standard slaves can easily be used with a "new" VB... master, however, the<br />

following changes apply:<br />

A standard slave occupies both A and B addresses and thus reduces the<br />

maximum number of nodes by one.<br />

Standard slaves on a "new" VB... master/gateway are recognised using<br />

the identification code (ID code) and can still have 4 output data bits.<br />

Analogue modules and safe modules occupy a full address, even if these<br />

devices are designed to specification 2.1. This allows the response time of<br />

these modules to be kept to a minimum.<br />

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany<br />

Pepperl+Fuchs Group Tel.: Germany +49 621 776-0 USA +1 330 4253555 Singapore +65 67799091 Internet http://www.pepperl-fuchs.com<br />

Issue date 2004-11-19 - Catalogue <strong>AS</strong>-<strong>Interface</strong> 2004/2005

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!