<strong>Fire</strong> Containment<br />

Curtain Wall System<br />

Aluminum Framed<br />

Curtain Wall <strong>Systems</strong> UL System Description<br />

Design Criteria CW-S-2001 or CW-S-2002<br />

The following checklist contains important details that must be included in a <strong>Fire</strong> Containment System<br />

used in an aluminum-framed curtain wall system with aluminum,glass or stone spandrel panels.(See<br />

specific test design for details.)<br />

2<br />

1<br />

5<br />

4<br />

3<br />

4<br />

glass, aluminum<br />

or stone<br />

stiff-back angle<br />

steel angle clips<br />

THERMAFIBER FIRESPAN<br />

insulation pinned to<br />

mullion covers<br />

1" FIRECODE Compound<br />

4" thick THERMAFIBER<br />

safing insulation<br />

supported by Z-clips<br />

THERMAFIBER FIRESPAN<br />

insulation pinned to<br />

angle clips<br />

aluminium curtain<br />

wall system<br />

37 <strong>USG</strong> <strong>Fire</strong> <strong>Stop</strong> <strong>Systems</strong><br />

3<br />

2<br />

1<br />

5<br />

1. Foil-Faced THERMAFIBER Curtain Wall or FIRESPAN Insulation is mechanically attached to mullions and<br />

transoms using impaling pins, screws or other positive mechanical attachment.<br />

2. Exposed aluminum mullions must be protected with Foil-Faced THERMAFIBER Curtain Wall or FIRESPAN<br />

Insulation mullion covers.<br />

3. Safing insulation is compression fit (minimum 1/2� wider than opening) into safe-off area (2�- 8�)<br />

and supported with safing “Z” clips.<br />

4. A light steel angle or channel is placed horizontally at the safing line,attached to vertical mullions—<br />

either within the insulation at a horizontal splice,or behind the insulation and attached to vertical mullions.This<br />

detail prevents bowing of curtain wall insulation due to the compression fit of the safing<br />

insulation.<br />

5. Minimium 1� thick FIRECODE Compound installed over forming material (Safing Insulation) to form a<br />

tight smoke seal and effective thermal barrier.