Construction Joint <strong>Fire</strong> Tests<br />

Static Joints<br />

<strong>Fire</strong> Tests UL System Test Criteria Description<br />

Floor Joint FF-S-0028 a<br />

2<br />

3<br />

1<br />

30 <strong>USG</strong> <strong>Fire</strong> <strong>Stop</strong> <strong>Systems</strong><br />

Assembly Rating<br />

2 Hr.<br />

L-Rating at Ambiant<br />

Less than 1 cfm/lin. ft.<br />

L-Rating at 400 °F<br />

Less than 1 cfm/lin. ft.<br />

1. Concrete floor assembly, minimum 4-1/2� thickness; maximum joint<br />

width 2�.<br />

2. Forming material: Minimum 4� of mineral wool insulation b (minimum<br />

2.5 pcf) firmly packed into the opening as a permanent form.<br />

3. Type A:<br />

Minimum 1/2� wet thickness of sealant applied within the opening,<br />

flush with the top surface of the floor<br />

Head-of-Wall Joint System HW-S-0001a For fluted steel deck/concrete 1. Floor or roof assembly: Maximum 3� deep fluted deck with minimum<br />

floor or roof/ceiling and gypsum 2-1/2� concrete floor or maximum 1-1/2� deep fluted roof deck per<br />

wallboard wall UL Design.<br />

2. Gypsum wallboard/stud wall assembly:<br />

1-hr. or 2-hr. fire-rated wall.<br />

3.<br />

A<br />

Joint treatment system:<br />

Forming material:<br />

Minimum 2-1/2� of mineral wool insulationb Assembly Rating<br />

1 & 2 Hr.<br />

Joint Width<br />

1/2� Maximum<br />

1 3A 3B 3A A 1 3A<br />

(minimum 4.0 pcf) firmly<br />

packed into the flutes of the steel deck as a permanent form.<br />

A<br />

3B<br />

B Fill material: Type FC or RFC:<br />

For 1-hr. rating, minimum 1/2� thick compound is applied on each<br />

2<br />

side of the wall; for 2-hr. rating, minimum 1� thick compound is<br />

applied on each side of the wall.<br />

Section A–A<br />

Note<br />

(a) Refer to the UL <strong>Fire</strong> Resistance Directory for Building Joint <strong>Systems</strong> or contact<br />

United States Gypsum Company for complete information. (b) Bearing the UL<br />

Classification Marking.