<strong>Fire</strong> Tests UL System Test Criteria Description<br />

Wall Assembly W-L-1064 a<br />

1<br />

2<br />

4<br />

3<br />

3<br />

2<br />

4<br />

Section A–A<br />

A<br />

A<br />

Penetration <strong>Fire</strong> Tests<br />

Caulk-Type Materials<br />

22 <strong>USG</strong> <strong>Fire</strong> <strong>Stop</strong> <strong>Systems</strong><br />

F-Rating<br />

2 Hr.<br />

T-Rating<br />

0 Hr.<br />

1. Gypsum wallboard/stud wall assembly.<br />

2. Metallic pipe or conduit:<br />

A Steel pipe:<br />

4� diameter (or smaller) Schedule 10 (or heavier) steel pipe.<br />

B Conduit:<br />

4� diameter (or smaller) electrical metallic tubing (EMT) or<br />

steel conduit.<br />

The annular space shall be a minimum of 1/4� to a maximum of 1-1/4�.<br />

3. Forming material:<br />

Minimum 2-1/2� thick mineral wool insulation b (minimum 4.0 pcf)<br />

firmly packed into the opening as a permanent form.<br />

4. Type AS or Type SS:<br />

Minimum 1� layer of sealant applied within the opening, flush with<br />

both surfaces of the wall.<br />

Note<br />

(a) Refer to the UL <strong>Fire</strong> Resistance Directory for Through-Penetration <strong>Fire</strong>stop <strong>Systems</strong><br />

or contact United States Gypsum Company for complete information. (b) Bearing the UL<br />

Classification Marking.