Penetration <strong>Fire</strong> Tests<br />
<strong>Fire</strong> Tests UL System Test Criteria Description<br />
Floor/Wall Assembly C-AJ-1020a 2<br />
4<br />
3<br />
5<br />
2<br />
Floor/Wall Assembly C-AJ-5146 a<br />
4B<br />
4<br />
5<br />
3<br />
4B<br />
3<br />
2<br />
A<br />
A<br />
A<br />
Section A–A<br />
3<br />
1<br />
Section A–A<br />
A<br />
2<br />
4A<br />
Caulk-Type Materials<br />
1<br />
20 <strong>USG</strong> <strong>Fire</strong> <strong>Stop</strong> <strong>Systems</strong><br />
F-Rating<br />
3 Hr.<br />
T-Rating<br />
1 Hr.<br />
F-Rating<br />
2 Hr.<br />
T-Rating<br />
1/2 & 1 Hr.<br />
1. Concrete floor or wall assembly, minimum 4-1/2� thickness<br />
floor/minimum 6-1/2� wall.<br />
2. Steel sleeve (optional).<br />
3. Metallic pipe:<br />
A Steel pipe:<br />
6� diameter (or smaller) Schedule 10 (or heavier) steel pipe.<br />
B Conduit:<br />
4� diameter (or smaller) electrical metallic tubing (EMT) or 6� diameter<br />
rigid steel conduit.<br />
4. Forming material:<br />
Mineral wool insulation b (minimum 4.0 pcf) firmly packed into the<br />
opening as a permanent form; see table below for minimum required<br />
thickness.<br />
5. Type AS or Type SS:<br />
Minimum thickness of sealant as specified in the table below, applied<br />
within the opening, flush with the top surface of the floor or both<br />
surfaces of the wall.<br />
Maximum Maximum Annular Forming Minimum F T<br />
Pipe EMT Space Material Sealant Rating Rating<br />
Diameter (in.) Thickness Thickness (hours) (hours)<br />
(%) (in.) (in.)<br />
1-1/2 — 3/8 to<br />
2-1/8<br />
2-1/2 2 3 1<br />
6 4 3/8 to<br />
3/4<br />
3-1/2 1 3 0<br />
6 4 3/8 to 1 2-1/2 2 3 0<br />
1. Concrete floor or wall assembly, minimum 4-1/2� thickness.<br />
2. Metallic pipe:<br />
A Steel pipe:<br />
8� diameter (or smaller) Schedule 40 (or heavier) steel.<br />
B Iron pipe:<br />
8� diameter (or smaller) cast or ductile iron.<br />
C Copper pipe:<br />
4� diameter (or smaller) regular (or heavier) copper.<br />
D Copper tubing:<br />
4� diameter (or smaller) Type L (or heavier) copper tubing.<br />
3. Pipe covering:<br />
Nominal 1� thick (or less) glass fiber insulation.<br />
4. <strong>Fire</strong>stop treatment:<br />
Pipe Type Annular Space (in.) T Rating (Hours)<br />
Steel Pipe 1/2 to 1 1<br />
Iron Pipe 1/2 to 1 1<br />
Copper Pipe 3/8 to 1-1/2 1/2<br />
Copper Tubing 3/8 to 1-1/2 1/2<br />
4A Forming material:<br />
Minimum 4� thick mineral wool insulation (minimum 4.0 pcf) firmly<br />
packed into the opening as a permanent form.<br />
4B Type A:<br />
Minimum 1/2� thick sealant applied within opening, flush with the top<br />
of the floor or both sides of the wall.<br />
Note<br />
(a) Refer to the UL <strong>Fire</strong> Resistance Directory for Through-Penetration <strong>Fire</strong>stop <strong>Systems</strong><br />
or contact United States Gypsum Company for complete information. (b) Bearing the UL<br />
Classification Marking.