<strong>Fire</strong> Tests UL System Test Criteria Description<br />

Wall Assembly W-L-7001a 3<br />

4<br />

2<br />

1<br />

Wall Assembly W-L-7002 a<br />

3<br />

4<br />

2<br />

1<br />

Section A–A<br />

Section A–A<br />

2<br />

3<br />

4<br />

2<br />

3<br />

4<br />

19 <strong>USG</strong> <strong>Fire</strong> <strong>Stop</strong> <strong>Systems</strong><br />

A<br />

A<br />

A<br />

A<br />

F-Rating<br />

1 Hr.<br />

T-Rating<br />

0 Hr.<br />

F-Rating<br />

2 Hr.<br />

T-Rating<br />

1/2 Hr.<br />

1. Gypsum wallboard/stud wall assembly.<br />

2. Air duct:<br />

Up to 3� by 10� prefabricated 24 ga. sheet metal air duct. Minimum<br />

7/16� to maximum 1-5/8� annular space between duct and periphery<br />

of opening is required.<br />

3. Forming material:<br />

Minimum 2-1/2� thick mineral wool insulation b (minimum 3.5 pcf)<br />

firmly packed into the opening as a permanent form.<br />

4. Type FC or RFC: Minimum 1/2� thick compound applied within<br />

opening, flush with both surfaces of the wall.<br />

1. Gypsum wallboard/stud wall assembly.<br />

2. Air duct: Up to 4� by 6� prefabricated No. 28 MSG galvanized sheet<br />

metal air duct. Minimum 1/2� to maximum 1-5/8� annular space<br />

between duct and periphery of opening is required.<br />

3. Forming material: Minimum 2-1/2� thick mineral wool insulation b<br />

(minimum 3.5 pcf) firmly packed into the opening as a permanent<br />

form.<br />

4. Type FC or RFC: Minimum 1� thick compound applied within opening,<br />

flush with both surfaces of the wall.<br />

Note<br />

(a) Refer to the UL <strong>Fire</strong> Resistance Directory for Through-Penetration <strong>Fire</strong>stop <strong>Systems</strong><br />

or contact United States Gypsum Company for complete information. (b) Bearing the UL<br />

Classification Marking.