9.11 DISCHARGE PUMP CIRCUIT<br />
1. Press the reset button on the overloadprotection inside the control panel and turn the<br />
pump on to determine whether the pump motor overloaded and dropped out of the<br />
circuit.<br />
2. Make sure that all overload heater coils on the pump starter are the size specified on<br />
the electric scheme and check setting for current according motor type plate.<br />
3. If the pump will not start and the pump starter is energised, the problem is in the motor<br />
itself, the motor wiring, or the main contacts of the starter.<br />
4. For mechanical malfunctions, check the specific manufacturers documentation<br />
enclosed in this manual.<br />
9.12 ELECTRODE TYPE LEVEL SWITCH<br />
Clean tips of electrodes for dirt or corrosion. Clean with sandpaper, check isolation, for<br />
specific values and test, refer to enclosed documentation for the level relay enclosed with<br />
vendor's data. Function can be tested by simulation of waterlevels, just connect relevant<br />
electrodes temporarily with electric wire. A low, save voltage is used on the levelcontroler.<br />
NOTE: When replacing a defective level switch, the pipe threads must be sealed<br />
with teflon tape or pipe dope.<br />
9.13 HIGHWATERLEVEL<br />
1. Silence the alarm<br />
2. If the problem cannot be isolated and repaired quickly, bypass the sewage<br />
overboard.<br />
3. Make sure that all valve settings and control settings are in accordance with<br />
section „SET UP FOR OPERATION“.<br />
4. Check that the valves from the unit discharge connection to the overboard line is<br />
fully open.<br />
5. Inspect pump starter relay and verify that it is energised. Check that pump is running.<br />
If running but no falling level (sightglass) De-aereate pump and observe level again.<br />
If not cured, open up the pump for inspection.<br />
6. If the system is operating properly, the problem is an excessive volume of water<br />
entering the system. Check for stuck or leaking flush valves and fixtures.<br />
Issue: 10.06.2009 Instruction Manual <strong>DVZ</strong>-<strong>SKA</strong>-“BIOMASTER“ Page 19 of 37<br />
EOI<strong>SKA</strong>-SD2n