<strong>Technology</strong>/Method Woven Hose Lining/Epoxy Adhesive<br />

I. <strong>Technology</strong> Background<br />

Status Conventional<br />

Date <strong>of</strong> Introduction Not Available<br />

Utilization Rates Not Available<br />

Vendor Name(s) Starline HPL-W<br />

Starline Trenchless <strong>Technology</strong>, LLC<br />

1700 South Mount Prospect Road<br />

Des Plaines, IL<br />

60018-1804<br />

USA<br />

Phone: 847-768-0889<br />

Mail: edward.johnston@gastechnology.org<br />

Practitioner(s) Czech Republic<br />

Description <strong>of</strong> <strong>Main</strong> For use in rehabilitation <strong>of</strong> drinking water mains<br />

Features<br />

<strong>Main</strong> Benefits Not available<br />

Claimed<br />

<strong>Main</strong> Limitations Not available<br />

Cited<br />

Applicability<br />

(Underline those that<br />

apply)<br />

<strong>Force</strong> <strong>Main</strong> Gravity Sewer Laterals Manholes Appurtenances<br />

Water <strong>Main</strong> Service Lines Other:__________________________<br />

II. <strong>Technology</strong> Parameters<br />

Service Application <strong>Rehabilitation</strong><br />

Service Connections Need to be addressed separately. Can be identified externally via digging or<br />

internally via robot.<br />

Structural Rating 430 psi (30 bar) per DVGW<br />

Claimed<br />

Materials <strong>of</strong><br />

Polyester woven liner, adhesive and epoxy coatings<br />

Composition<br />

Diameter Range, 3 to 24 inches<br />

inches<br />

Thickness Range, Not available<br />

inches<br />

Pressure Capacity, Up to 430 psi<br />

psi<br />

Temperature Range, Recommended <strong>for</strong> use up to 78<br />

o<br />

F<br />

o F<br />

Renewal Length, feet Not available<br />

Other Notes Not available<br />

III. <strong>Technology</strong> Design, Installation, and QA/QC In<strong>for</strong>mation<br />

Product Standards All requirements <strong>for</strong> the technology's application in drinking water pipes in<br />

Germany, the KTW recommendations <strong>for</strong> application <strong>of</strong> plastics in drinking water<br />

pipes and the DVGW W270 Recommended Practice (German Association <strong>of</strong> Gas<br />

and Water), have been complied with. The relevant U.S. certificate, NSF 61<br />

(National Sanitation Foundation), has been applied <strong>for</strong> and is expected in 2010.<br />

Design Standards Not available<br />

Design Life Range 50 years per DVGW certification<br />

Installation Standards Not available<br />

Installation<br />

Methodology<br />

The liner has to be pressed through calibrated rollers be<strong>for</strong>e it is pushed into the<br />

pipe. Liner is then wound on a pressure drum and bolted into an inversion cone<br />

attached to the host pipe. The liner is inverted inside the host pipe and the process<br />

ends when the liner reaches the catch basket.<br />

QA/QC Not available<br />

IV. Operation and <strong>Main</strong>tenance Requirements<br />

O&M Needs Not available<br />

Repair Requirements Not available<br />

A-58