<strong>Technology</strong>/Method CIPP/Direct Inversion/Pull -in - Place/Hot Water and Steam Cured<br />

I. <strong>Technology</strong> Background<br />

Status Conventional<br />

Date <strong>of</strong> Introduction 1995<br />

Utilization Rates Install approx. 200 miles <strong>of</strong> liner per year. Have only started pressure pipe<br />

installations in past several years.<br />

Vendor Name(s) National Liner®<br />

National EnviroTech Group<br />

12707 North Freeway, Suite 490<br />

Houston, TX 77060<br />

Phone: 281-874-0111<br />

Email: info@nationalliner.com<br />

Web: www.nationalliner.com<br />

Practitioner(s) Not available.<br />

Description <strong>of</strong> <strong>Main</strong><br />

Features<br />

<strong>Main</strong> Benefits<br />

Claimed<br />

<strong>Main</strong> Limitations<br />

Cited<br />

Applicability<br />

(Underline those that<br />

apply)<br />

National Liner is a CIPP product made <strong>of</strong> a non-woven, needled, polyester felt<br />

that is shop or site impregnated with a thermosetting polyester resin. Vinylester<br />

resins are used <strong>for</strong> pressure applications. A new composite structure,<br />

incorporating glass fiber rein<strong>for</strong>cement, is being developed <strong>for</strong> pressure<br />

applications.<br />

• No-dig (or minimum excavation) renovation.<br />

• Excess resin mechanically locks tube to host pipe by filling in cracks.<br />

• Smooth interior surface <strong>for</strong> improved flow characteristics.<br />

• 7 licensed and trained installation contractors covering US market.<br />

• No ASTM product standard <strong>for</strong> CIPP pressure pipe liners.<br />

• No long-term tensile or pressure regression data <strong>for</strong> pressure applications.<br />

• Limited experience with pressure (<strong>for</strong>ce main) projects.<br />

<strong>Force</strong> <strong>Main</strong> Gravity Sewer Laterals Manholes Appurtenances<br />

Water <strong>Main</strong> Service Lines Other: Storm Sewers<br />

II. <strong>Technology</strong> Parameters<br />

Service Application Gravity and Low Pressure Wastewater<br />

Service Connections Reinstate gravity laterals remotely. No provisions <strong>for</strong> reinstating pressure<br />

connections.<br />

Structural Rating Class II/III – Semi Structural <strong>for</strong> felt, Class IV – Structural <strong>for</strong> glass<br />

Claimed<br />

Materials <strong>of</strong><br />

Non-woven polyester felt material (from Applied Felts) which is saturated with<br />

Composition<br />

either an isophthalic or vinylester polyester resin, depending on application.<br />

<strong>Force</strong> mains use vinylester. A new composite structure that incorporates glass<br />

fiber <strong>for</strong> higher pressure is being developed.<br />

Diameter Range, 6-120 inches<br />

inches<br />

Thickness Range, 4.5 mm to 33.5 mm with felt tube are typical, but greater thickness are possible<br />

inches<br />

Pressure Capacity, psi 50 psi with polyester felt tube, higher with glass fiber composite<br />

Temperature Range, w/PE resin up to 205<br />

o<br />

F<br />

o F; w/VE resins up to 248 o F<br />

Renewal Length, feet Small diameters up to 800 feet; Large diameters up to 2000 feet in one<br />

installation<br />

Other Notes BOH Brothers and Visu-Sewer Clean & Seal both have reported doing sewer<br />

<strong>for</strong>ce mains.<br />

III. <strong>Technology</strong> Design, Installation, and QA/QC In<strong>for</strong>mation<br />

Product Standards ASTM D5813 (Gravity Sewer) – none <strong>for</strong> pressure applications<br />

Design Standards ASTM F1216, Appendix X1, WRc, and standard engineering design using<br />

resources such as RERAU report R4A2-18<br />

Design Life Range 50 years<br />

Installation Standards ASTM F1216, ASTM F1743<br />

Installation<br />

All mains to be cleaned and CCTV inspected be<strong>for</strong>e start <strong>of</strong> lining. The resin<br />

Methodology saturated tube is inverted into the main using a column <strong>of</strong> water or pressurized<br />

A-37