<strong>Technology</strong>/Method Fold -and - Form PVC/ Therm<strong>of</strong>ormed<br />

I. <strong>Technology</strong> Background<br />

Status Conventional<br />

Date <strong>of</strong> Introduction 1999<br />

Utilization Rates 200 miles in the past 10 years.<br />

Vendor Name(s) EX Pipe<br />

Miller Pipeline<br />

P.O. Box 34141<br />

Indianapolis, IN 46234<br />

Phone: 800-428-3742<br />

Email: info@millerpipeline.com<br />

Practitioner(s) City <strong>of</strong> Plano – Over 200,000 LF Installed<br />

Steve Spencer<br />

P.O. Box 860358<br />

Plano, Texas 75086<br />

972-769-4140<br />

Description <strong>of</strong> <strong>Main</strong><br />

Features<br />

Anne Arundel Co, MD – Over 130,000 LF Installed<br />

Lew Addison<br />

504 Baltimore Annapolis Blvd.<br />

Severna Park, MD 21146<br />

410-647-2727<br />

Collier County, FL – Over 100,000 LF Installed<br />

Steve Nagy<br />

6027 Shirley St.<br />

Naples, FL 34109<br />

239-591-0186<br />

EX Pipe is a high strength, un-plasticized PVC manufactured in a factory<br />

environment, meeting ASTM F1504. The EX Pipe material is s<strong>of</strong>tened with heat<br />

and continuously inserted into the host pipe via manholes or other access points.<br />

After insertion, the pipe is then expanded approximately 10% to fit tightly within<br />

the host pipe.<br />

<strong>Main</strong> Benefits • Resistant to chemicals and abrasion<br />

Claimed • Stops water infiltration and exfiltration, root intrusion and soil loss<br />

• Smooth pipe finish improves flow characteristics<br />

• Cost to install EX Pipe is much less than conventional trenching techniques<br />

• No styrene odors<br />

• Low coefficient <strong>of</strong> thermal expansion means service cut-outs will not move<br />

<strong>Main</strong> Limitations<br />

Cited<br />

Applicability<br />

(Underline those that<br />

apply)<br />

• Can be installed in lines with 90 o bends and small diameter changes<br />

• Only available in diameters 6 to 15 inches<br />

• Installation by Miller Pipeline only<br />

• Minimal reduction in cross-section<br />

• No long-term pressure or tensile testing to substantiate a hydrostatic design<br />

basis <strong>for</strong> pressure use<br />

<strong>Force</strong> <strong>Main</strong> Gravity Sewer Laterals Manholes Appurtenances<br />

Water <strong>Main</strong> Service Lines Other:<br />

II. <strong>Technology</strong> Parameters<br />

Service Application Not available.<br />

Service Connections Sewer laterals reinstated with robotic cutter and CCTV. No in<strong>for</strong>mation on use<br />

<strong>of</strong> EX Pipe <strong>for</strong> low pressure applications.<br />

Structural Rating Not available.<br />

Claimed<br />

Materials <strong>of</strong><br />

Composition<br />

EX Pipe is made from a base PVC, con<strong>for</strong>ming to ASTM D1784, cell<br />

classification 12334B. The following are physical properties <strong>of</strong> EX Pipe:<br />

Test Method Value<br />

Flexural Modulus, psi ASTM D790 340,000<br />

Flexural Strength, psi ASTM D790 9,000<br />

A-26