<strong>Technology</strong>/Method Fold and Form PE Close Fit Liner<br />

I. <strong>Technology</strong> Background<br />

Status Emerging<br />

Date <strong>of</strong> Introduction 2001 in US<br />

Utilization Rates Total HDPE experience worldwide – over 8,000 miles.<br />

Folded HDPE worldwide experience – approximately 6 miles.<br />

Vendor Name(s) InsituGuard TM Folded HDPE<br />

Insitu<strong>for</strong>m Technologies, Inc<br />

17999 Edison Avenue<br />

Chesterfield, MO 63005<br />

Phone: 800-234-2992<br />

Fax: 636-519-8744<br />

Web: http://www.insitu<strong>for</strong>m.com/<br />

Practitioner(s) 1,000 feet <strong>of</strong> 19-24 inches<br />

Steven Tusler<br />

City <strong>of</strong> Colorado Springs<br />

121 S. Tejon<br />

Colorado Springs, CO 80947<br />

719-668-8537<br />

Description <strong>of</strong> <strong>Main</strong><br />

Features<br />

19,000 feet <strong>of</strong> 30 inches<br />

Mr. Dick Fett<br />

IMC Agrico Company<br />

Mulberry, Florida<br />

863-648-9990<br />

3,700 feet <strong>of</strong> 36 inches<br />

Mr. Howard Wellspring<br />

City <strong>of</strong> Baytown, TX<br />

2123 Market St<br />

Baytown, TX 77522<br />

713-424-5508<br />

Inserted into a new or existing pipeline, the polyethylene liner is continuous, and<br />

installed with a close-fit against the inner wall <strong>of</strong> the host pipe. The polyethylene<br />

liner isolates the flow stream from the host pipe wall, eliminating internal<br />

corrosion. InsituGuard stops leaks, and can provide a fully structural solution in<br />

some cases.<br />

<strong>Main</strong> Benefits Claimed • Rapid installation - 40% reduction in diameter<br />

• Drinking water approved<br />

• Negotiates long radius (sweep) bends<br />

• Utilizes high-per<strong>for</strong>mance PE 100 (4710)<br />

<strong>Main</strong> Limitations Cited • Cannot do factory bends<br />

• Bypass required<br />

Applicability<br />

(Underline those that<br />

apply)<br />

• Wall thickness limitation dependent upon diameter.<br />

<strong>Force</strong> <strong>Main</strong> Gravity Sewer Laterals Manholes Appurtenances<br />

Water <strong>Main</strong> Service Lines Other:__________________________<br />

Service Application<br />

II. <strong>Technology</strong> Parameters<br />

<strong>Rehabilitation</strong><br />

Service Connections Service Connections have to be excavated. Fused fittings used to reinstate.<br />

Structural Rating<br />

Claimed<br />

Class 3 or 4 depending upon diameter, pressure and host pipe condition.<br />

Materials <strong>of</strong><br />

Composition<br />

4710 (PE 100)<br />

Diameter Range, inches 12-48 inches<br />

Thickness Range, DR 17 or thinner<br />

inches<br />

Pressure Capacity, psi Pressure rating to 150+ psi <strong>for</strong> Class 3. Class 4 dependent upon DR.<br />

Temperature Range, o F Temperature derating required <strong>for</strong> temperatures over 80 o F. Max temp is 140 o F<br />