<strong>Technology</strong>/Method Subline/Close Fit PE Liner – Fold -and - Form<br />

maintain the reduced shape through insertion. Insertion lengths <strong>of</strong> up to 3,500 feet<br />

are possible. The reduced cross-section PE pipe maintains its shape until<br />

subjected to internal water pressure. The internal pressure breaks the restraining<br />

straps and reverts the pipe back to its original diameter and in close contact with<br />

the host pipe. The string <strong>of</strong> PE pipes can be pulled through a bend <strong>of</strong> up to 45 o .<br />

Proprietary couplings are then attached to the end <strong>of</strong> the exposed pipe sections and<br />

make-up pieces are inserted to reconnect the pipe to the existing main.<br />

QA/QC CCTV the line, after cleaning, to make sure there are no impediments to prevent<br />

insertion and reversion <strong>of</strong> the PE liner. Pressure test after insertion.<br />

IV. Operation and <strong>Main</strong>tenance Requirements<br />

O&M Needs Not available.<br />

Repair Requirements Not available.<br />

<strong>for</strong> Rehabilitated<br />

Sections<br />

V. Costs<br />

Key Cost Factors Not available.<br />

Case Study Costs Not available.<br />

References<br />

VI. Data Sources<br />

www.subterra.co.uk, Subline flyer<br />