As summarized <strong>in</strong> Table 4-10, the <strong>in</strong>itial thermal program (steps 1-4) was performed to remove any<br />
previous thermal history. The f<strong>in</strong>al heat scan step (step 5) <strong>of</strong> the temperature program was used for<br />
quantification as this scan conta<strong>in</strong>s a known thermal history. The calculated Tg values are summarized <strong>in</strong><br />
Table 4-12.<br />
Table 4-12. Sample Tg Determ<strong>in</strong>ation (Denver 8-<strong>in</strong>. L<strong>in</strong>er)<br />
Sample Run Tg (°C)<br />
Invert 1 122.65<br />
Invert 2 117.52<br />
Crown 1 122.31<br />
Crown 2 119.11<br />
Spr<strong>in</strong>g l<strong>in</strong>e 1 134.63<br />
Spr<strong>in</strong>g l<strong>in</strong>e 2 129.76<br />
Virg<strong>in</strong> Res<strong>in</strong> 1 123.57<br />
Virg<strong>in</strong> Res<strong>in</strong> 2 124.59<br />
The average Tg for the control samples was 124.08°C (+/- 0.72°C) and the average Tg for the field<br />
samples was 124.33°C (+/- 6.57°C) as measured by ASTM Method E1356-08 with DSC. In general, an<br />
<strong>in</strong>crease <strong>in</strong> the Tg is a function <strong>of</strong> cur<strong>in</strong>g and represents the <strong>in</strong>crease <strong>in</strong> the molecular weight <strong>of</strong> the res<strong>in</strong><br />
system (Perk<strong>in</strong>s-Elmer, 2000). The Tg results suggest a similar level <strong>of</strong> cur<strong>in</strong>g between the virg<strong>in</strong> res<strong>in</strong><br />
(control sample) and the aged material samples, with the field samples exhibit<strong>in</strong>g slightly higher<br />
variability <strong>in</strong> Tg values from the spr<strong>in</strong>g l<strong>in</strong>e to <strong>in</strong>vert.<br />
4.2.17 CCTV Inspection <strong>of</strong> Area Sewers for Denver 8-<strong>in</strong>. Site. The City <strong>of</strong> Denver ordered<br />
CCTV scans <strong>of</strong> the l<strong>in</strong>es <strong>in</strong> the area from which the sample was retrieved. Also, historical ma<strong>in</strong>tenance<br />
reports <strong>of</strong> these l<strong>in</strong>es were requested. A total <strong>of</strong> nearly 5,800 ft <strong>of</strong> sewer l<strong>in</strong>e was imaged <strong>in</strong> the period<br />
September 24-28, 2009. A prelim<strong>in</strong>ary review <strong>of</strong> the CCTV reports suggested that the l<strong>in</strong>er is <strong>in</strong> good<br />
condition overall. Several tap break-<strong>in</strong> defects were noted as well as l<strong>in</strong><strong>in</strong>g failure at undercut<br />
connections, which could allow for root <strong>in</strong>trusion between the lateral outer wall and the l<strong>in</strong>er cover<strong>in</strong>g the<br />
<strong>in</strong>terior <strong>of</strong> the ma<strong>in</strong> pipe. This could be attributed to the robotic cutters used by the <strong>in</strong>dustry 25 years ago,<br />
which were far less sophisticated and accurate than the units used today. Some <strong>of</strong> the images reveal root<br />
<strong>in</strong>trusion via tap connections, result<strong>in</strong>g <strong>in</strong> a partial blockage <strong>of</strong> the sewer l<strong>in</strong>e, but the l<strong>in</strong>er itself appears<br />
to be <strong>in</strong>tact <strong>in</strong> these images. On the l<strong>in</strong>e stretch <strong>in</strong> the alley between Garfield Street and Jackson Street<br />
(between 3 rd and 4 th Avenues), at cha<strong>in</strong>age 212.6 ft, there is what appears to be a l<strong>in</strong>er failure <strong>in</strong> the<br />
vic<strong>in</strong>ity <strong>of</strong> a tap break <strong>in</strong>. Another l<strong>in</strong>er failure was found at the alley between Jackson Street and<br />
Garfield Street, from the first manhole north to the first manhole south to 1 st Avenue. At cha<strong>in</strong>age 20.8 ft,<br />
a bulge was found at the <strong>in</strong>vert <strong>of</strong> the l<strong>in</strong>er that prevented further advancement <strong>of</strong> the CCTV equipment.<br />
A third l<strong>in</strong>er failure location was identified <strong>in</strong> the l<strong>in</strong>e runn<strong>in</strong>g <strong>in</strong> the alley between Jackson and Harrison<br />
Streets, as it crosses 3 rd Avenue, at cha<strong>in</strong>age 239.8 ft. This l<strong>in</strong>er failure appears to be attributed to<br />
improper restoration <strong>of</strong> a nearby lateral connection. A significant portion <strong>of</strong> the polyurethane coat<strong>in</strong>g was<br />
hydrolyzed along this l<strong>in</strong>e. A l<strong>in</strong><strong>in</strong>g failure attributed to a connection cut shift was noted at 2 nd Avenue<br />
and Jackson Street. Similar occurrences <strong>of</strong> a l<strong>in</strong>er connection cut shift were noted on a couple <strong>of</strong> other<br />
l<strong>in</strong>es. A location where the l<strong>in</strong>er appears to be detached from the host pipe was located at cha<strong>in</strong>age 39 ft,<br />
<strong>in</strong> the alley between 3 rd Avenue and Garfield Street.<br />
46