Table 8-7. Preparation and Supervision <strong>of</strong> CIPP Works<br />

Utility Preparation Supervision<br />

Thames Water Jett<strong>in</strong>g Contractor self-certifies to own<br />

method statement<br />

Severn Trent Water Not known Contractor self-certifies to<br />

specification. Some audit by<br />

Severn Trent Water.<br />

Agglomeration de Chartres Jett<strong>in</strong>g and root cutt<strong>in</strong>g Third party project manager<br />

Agglomeration des Hauts-de-Bièvre Jett<strong>in</strong>g and jo<strong>in</strong>t seal<strong>in</strong>g Contractor self-certifies under own<br />

QA scheme<br />

Gött<strong>in</strong>gen Stadtentwässerung Jett<strong>in</strong>g Third party consult<strong>in</strong>g eng<strong>in</strong>eer<br />

Technische Betriebe der Stadt Jett<strong>in</strong>g Third party consult<strong>in</strong>g eng<strong>in</strong>eer<br />

Leverkusen<br />

and Leverkusen<br />

Public Utilities Board S<strong>in</strong>gapore Jett<strong>in</strong>g and jo<strong>in</strong>t seal<strong>in</strong>g PUB supervisor<br />

Queensland Urban Utilities Not known Contractor self-certifies under own<br />

QA scheme<br />

Sydney Water Jett<strong>in</strong>g, jo<strong>in</strong>t seal<strong>in</strong>g, and<br />

rebar trimm<strong>in</strong>g<br />

Sydney Water supervisor<br />

The utilities commented that the cur<strong>in</strong>g and cool<strong>in</strong>g cycle is the element <strong>of</strong> the process that requires<br />

closest supervision and monitor<strong>in</strong>g. This is because contractors try to save time <strong>in</strong> this stage, and this can<br />

result <strong>in</strong> <strong>in</strong>adequate cur<strong>in</strong>g, lead<strong>in</strong>g to problems <strong>of</strong> service life.<br />

8.5 Verification and Test<strong>in</strong>g<br />

Table 8-8 shows the required frequency <strong>of</strong> post-<strong>in</strong>stallation CCTV surveys, as well as those utilities<br />

utiliz<strong>in</strong>g an I/I test for <strong>in</strong>-situ performance test<strong>in</strong>g. The performance test is generally an <strong>in</strong>-situ<br />

watertightness test to look for exfiltration. However, only two utilities appear to have established a clear<br />

pass/fail criterion for this characteristic. Table 8-9 sets out the mechanical characteristics <strong>of</strong> the<br />

<strong>in</strong>stallation that are tested. Most, but not all <strong>of</strong> the utilities, take samples from the <strong>in</strong>stalled l<strong>in</strong>ers for<br />

test<strong>in</strong>g to verify that the <strong>in</strong>stallation meets the specification requirements.<br />

Table 8-8. Post-Works Inspection and In-Situ Test<strong>in</strong>g<br />

Utility CCTV Survey I/I Test Pass/Fail Criterion<br />

Thames Water � Own test �<br />

Severn Trent Water - - -<br />

Agglomeration de Chartres � & after 1 year - -<br />

Agglomeration des Hauts-de-Bièvre � � -<br />

Gött<strong>in</strong>gen Stadtentwässerung - - -<br />

Technische Betriebe der Stadt Leverkusen � & after 4 years - -<br />

Public Utilities Board S<strong>in</strong>gapore � & after 2 and 5 years � -<br />

Queensland Urban Utilities � Pressure test �<br />

Sydney Water � & after 1 year - -<br />

112

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!