www.dynagen.ca | 1-888-396-2436


<strong>Control</strong>ler Selection Chart<br />

Use our engine and genset controller selection chart to choose the best control<br />

module for your application. For a complete list of features, functions, and ratings,<br />

please refer to the applicable catalog page shown below.<br />

Metering<br />

ES52 ES52 GSC100 GSC200 GSC300 GCP300 GSC400<br />

(special)<br />

Catalog Page 7 7 3 5 9 11 12<br />

<strong>Engine</strong> Compatibility:<br />

Standard yes yes yes yes yes yes yes<br />

Electronic (J1939) - - - - - - yes<br />

Analog AC Meters - - - - - yes -<br />

Speed Signal Types:<br />

<strong>Genset</strong> Mains Output yes opt yes yes yes yes yes<br />

Magnetic Pickup yes opt - - - - yes<br />

Alt Tach yes opt - - - - yes<br />

12V and 24V compatibility yes yes - yes yes yes yes<br />

Built-in Automotive Plug-in Relays yes yes - - yes yes yes<br />

Configuration Method:<br />

Manual yes yes - - yes yes yes<br />

Fixed Settings - yes yes - - - -<br />

Computer - - - yes yes yes yes<br />

Built-in Auto/Off/Test Switch - - - yes yes yes yes<br />

Timers<br />

Pre-heat yes yes - yes yes yes yes<br />

Mid/Post-heat - yes - yes yes yes yes<br />

Cool-down - yes yes yes yes yes yes<br />

Warm-up yes yes - yes yes yes yes<br />

Delay-to-start yes yes yes yes yes yes yes<br />

Energize-to-Stop - - - yes yes yes yes<br />

<strong>Engine</strong> Exerciser - - - yes - - yes<br />

Failures and Warnings<br />

Overspeed,LoOil,HiTemp,Overcrank yes yes yes yes yes yes yes<br />

Underspeed - yes yes yes - - yes<br />

Low Battery - - yes yes yes yes yes<br />

Fuel Level - - - - yes yes yes<br />

Over/Under Volts/Freq/Current - - - - - -<br />

yes<br />

Auxiliary Switched Inputs 1 1 - 2 1 1 8<br />

Auxiliary Switched Outputs 1 1 - 2 1 1 9<br />

Annunciator Outputs 6 6 8 - 8 8 8<br />

Autostart on Low Battery Function - - - - - - yes<br />

Event Log - - - - - - yes<br />

Dummy Load Function - - - - - - yes<br />

Pull/Hold Coil Output - yes - - - - -<br />

Momentary Start/Stop Inputs - yes - - - - -<br />

NFPA 110 Compliant - - - - - - yes<br />

Modbus port - - - - - - yes<br />

Internet/Wireless ready - - - - - - yes<br />

Photocell input - yes - - - - -<br />

- - - yes Recognized yes yes yes<br />

Component<br />

2010<br />

With Basic Indicator Lamps With Instrument Read-Out<br />

Basic Autostart Auto Mains Autostart Autostart w/ <strong>Engine</strong><br />

Failure (transfer w/ <strong>Engine</strong> Instruments & AC<br />

PRODUCT<br />

CATALOG


Contents<br />

GSC100 Autostart <strong>Control</strong>ler<br />

Low Cost OEM solution for Small <strong>Genset</strong>s<br />

Page 3<br />

GSC200 <strong>Genset</strong> <strong>Control</strong>ler<br />

Auto Mains Failure<br />

Single or 3-Phase<br />

Page 5<br />

ES52 Autostart <strong>Engine</strong> <strong>Control</strong>ler<br />

For all <strong>Engine</strong>s and <strong>Genset</strong>s<br />

Page 7<br />

GSC300 Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

Includes 6 <strong>Engine</strong> Instruments<br />

Page 9<br />

GSC400Plus Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

Displays AC Volts & Amps<br />

Standard or Electronic <strong>Engine</strong>s<br />

Page 12<br />

GSC400Plus Accessories:<br />

NFPA110 Remote Annunciator<br />

Remote <strong>Genset</strong> Monitoring<br />

Page 16<br />

Vigilant <strong>Automatic</strong> Transfer Switches<br />

100A thru 1250A<br />

Single or 3-Phase<br />

Page 20<br />

Vigilant Load Center 100A Residential ATS<br />

100A <strong>Automatic</strong> Transfer Switch with Built-in<br />

Breaker Panel<br />

Page 23<br />

Custom OEM Solutions<br />

Page 25<br />

www.dynagen.ca | 1-888-396-2436<br />

1


2<br />

All catalog products carry a 5-year warranty.<br />

Having accumulated research data on the durability of our products<br />

over millions of operational hours in the field, we have the highest<br />

confidence in providing a full five years of warranty coverage on<br />

everything we build.*<br />

Power controls you can trust.<br />

Our manufacturing plants manage product assembly in an experienced<br />

ISO9001-2000 environment giving you assurance of continued high<br />

quality DynaGen products.<br />

Electronics assembly facilities in<br />

Nova Scotia, Canada<br />

Toll-free technical support.<br />

1-888-DYNAGEN (1-888-396-2436)<br />

We offer one toll-free number for all your<br />

technical support and applications<br />

questions.<br />

When you call DynaGen<br />

you get access to the<br />

knowledgeable engineers<br />

who designed your<br />

product and they know<br />

how important it is to get<br />

you up and running as fast<br />

as possible.<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Transfer switch assembly plant and<br />

warehouse in Canton, Ohio<br />

*Please consult factory for warranty information on third-party accessories and custom products.


GSC100 Autostart <strong>Control</strong>ler<br />

OEM Autostart Solution for Small <strong>Genset</strong>s:<br />

Portables/Residential/Light Commercial<br />

The GSC100 Series is a low cost, full-featured<br />

autostart for small generator installations.<br />

Factory-fi xed settings prevent unauthorized<br />

fi eld tampering. The GSC100 is conformally<br />

coated to protect against the elements and<br />

carries a 5-year warranty. The unit is supplied<br />

as a circuit card to be mounted within a<br />

customer supplied panel with appropriate<br />

labeling.<br />

Non-Adjustable Settings<br />

• Crank Disconnect (20Hz)<br />

SPECIFICATIONS<br />

Operating Voltage<br />

• Overspeed (69Hz)<br />

• 5 to 16VDC continuous<br />

• Crank Tries (3)<br />

• Standby Current Draw: 8mA at 12VDC<br />

• Crank/Rest (10s)<br />

• Reverse battery protected<br />

General Fault Conditions<br />

• Surge withstand: 1500V for 250μS<br />

Operating Temperature<br />

• Low Oil<br />

• <strong>Control</strong>ler Function: -40 to +85˚C<br />

• High <strong>Engine</strong> Temperature<br />

Physical<br />

• Overcrank<br />

• Dimensions: 4.0”H x 4.0”W x 0.47”D<br />

• Overspeed<br />

• Weight: 0.15 lb<br />

Speed Sensing<br />

• Underspeed (53Hz)<br />

• Generator Output: Up to 300VAC<br />

• Low Battery Voltage (11V)<br />

(no external transformer required)<br />

Not In Auto<br />

Failure Inputs<br />

• Low oil pressure switch failure*<br />

NOT-IN-AUTO LED will illuminate<br />

(closed on failure)<br />

when the external AUTO/OFF/<br />

• High engine temp failure*<br />

TEST switch is not in AUTO.<br />

(closed on failure)<br />

Failure Inputs<br />

*Failure inputs can close to either +battery or<br />

ground. All failure inputs are ignored for a period<br />

Close to +BAT or to Ground.<br />

of 15 seconds at engine startup.<br />

Speed Signal<br />

Outputs<br />

• Fuel & Crank<br />

Accepts up to 300VAC, 60Hz from - 1A relays<br />

Direct Generator Output.<br />

- Switched to battery positive<br />

Time Delay <strong>Engine</strong> Start (TDES) Short circuit & overload protection on<br />

annunciation outputs (rated 300ma max).<br />

Provides a delay (10s) before the Connectors<br />

engine is started.<br />

• Main control mating plug: Dual Row Plug<br />

Optional Cool-Down Period<br />

2x7 Molex 39-01-2140<br />

• Annunciator mating plug: Dual Row Plug 2x5<br />

Wire jumper (2 mins).<br />

Molex 39-01-2100<br />

www.dynagen.ca | 1-888-396-2436<br />

3


GSC100 Autostart <strong>Control</strong>ler<br />

4<br />

Typical Wiring Example<br />

Ordering Information<br />

Part No: GSC102-L-12<br />

Available Accessories:<br />

HAS0025 – Main <strong>Engine</strong> <strong>Control</strong> Wiring Harness<br />

DWG1377– Annunciator Harness 5 ft<br />

DWG1410 – Extra Pre-Crimped wires 5ft (package of 5)<br />

2010<br />

PRODUCT<br />

CATALOG<br />

To find out more visit<br />

www.GSC100.info


GSC200 <strong>Genset</strong><br />

<strong>Control</strong>ler<br />

Auto Mains Failure<br />

Single or 3-Phase<br />

The GSC200 is an Auto<br />

Mains (utility) Failure<br />

<strong>Control</strong> module that<br />

provides Autostart<br />

and a range of engine<br />

monitoring and<br />

protection features. The<br />

GSC200 is designed to<br />

automatically start the generator when the mains (utility) power fails.<br />

When the mains (utility) power is restored the unit will transfer the<br />

load back to the mains (utility) supply and instruct the engine to begin<br />

the cool down timer. The GSC200 is an ideal controller to mate with a<br />

no-logic transfer switch for cost sensitive applications (ask about our<br />

Vigilant ATS without logic). The AMF functions can also be disabled and<br />

used as a conventional autostart control with a full-logic ATS.<br />

• Single or 3-Phase utility sensing<br />

with adjustable Dropout/Pickup.<br />

• <strong>Engine</strong> exerciser for 1, 2, 3 or 4<br />

week intervals (adjustable only<br />

via front panel buttons).<br />

• Timers for: Pre-heat, Mid/Postheat,<br />

Warm-up (Normal to<br />

Emergency), Cool-down, Time<br />

Delay <strong>Engine</strong> Start, and Time<br />

Delay Emergency to Normal.<br />

• Built-in Auto/Off /Test switch.<br />

• Overspeed and Underspeed trips.<br />

• 2 auxiliary outputs can be setup<br />

for Common Warning/Shutdown,<br />

System-in-Auto, Energize-to-<br />

Stop, Warmup, or Preheat.<br />

• 2 auxiliary failure/warning inputs.<br />

• <strong>Engine</strong> Hour Meter display.<br />

• Low battery warning.<br />

• Pluggable Eurostyle terminals.<br />

• Optional Restart on False<br />

Attempts.<br />

Easy-to-Use PC<br />

Confi guration Software<br />

• Optional Fuel OFF during crank<br />

rest.<br />

• 5-Year Warranty.<br />

www.dynagen.ca | 1-888-396-2436<br />

5


GSC200 <strong>Genset</strong> <strong>Control</strong>ler<br />

6<br />

SPECIFICATIONS<br />

Operating Voltage<br />

• 7 to 32VDC with operation to 0VDC for<br />

100mS<br />

• Standby Current Draw: 22mA<br />

• Reverse battery protected<br />

• Surge withstand: 1500V for 250μS<br />

Operating Temperature<br />

• <strong>Control</strong>ler Function: -40 to +85˚C<br />

• Hour Meter Viewing: -16 to +70˚C<br />

Physical<br />

• Dimensions: 4.5”H x 6.75”W x 1.0”D<br />

• Weight: 0.67 lb<br />

Speed Sensing<br />

• Generator AC (up to 300VAC direct)<br />

Typical Wiring Example<br />

Ordering Information<br />

Part No:<br />

GSC200 (no faceplate)<br />

GSC200-L-LS (with faceplate)<br />

(consult factory for faceplate options)<br />

Available Accessories:<br />

GSC300-PGMR – Parallel Port Programming Kit with software<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Inputs<br />

• Utility Mains Sensing:<br />

- 120/240 3-wire, single-phase<br />

- 120/208 4-wire, 3-phase<br />

- 120 2-wire, single-phase<br />

• Low oil pressure switch failure* (NO or NC)<br />

• High engine temp failure* (NO or NC)<br />

• 2 Auxiliary failure inputs* (NO or NC)<br />

*Failure inputs must close to ground.<br />

All failure inputs are ignored for an adjustable<br />

bypass period.<br />

Outputs<br />

• Fuel, Crank & 2 Aux Outputs (1A max):<br />

- Switched to Ground<br />

- Short circuit & overload protected<br />

To find out more visit<br />

www.GSC200.info


ES52 Autostart <strong>Engine</strong><br />

<strong>Control</strong>ler<br />

For <strong>Diesel</strong> and <strong>Gas</strong> <strong>Engine</strong>s<br />

The ES52 is designed to provide<br />

autostart control and protection<br />

for all types of diesel and gas<br />

engine-driven equipment. The<br />

module is epoxy sealed in an<br />

ultra-compact package with<br />

mounting compatibility to an<br />

industry standard footprint.<br />

The module is easily configured<br />

using on-board DIP switches and<br />

potentiometer adjustments.<br />

• Epoxy sealed for protection<br />

against vibration, shock, and<br />

moisture.<br />

• Multi-Function Timer Output:<br />

Pre-heat, Slow, Airgate, & Choke.<br />

• Warm-up Timer Output.<br />

• Detects lost speed signal.<br />

• Zero speed restart prevents<br />

starter pinion wear.<br />

• 5-Year Warranty.<br />

ES52 showing on-board 20A relays,<br />

fuses, and annunciator strip<br />

Simple Installation and Servicing<br />

• Plug-in Terminals with no wire<br />

crimping required.<br />

• 20A Removable Relays and<br />

fuses eliminate slave relays and<br />

external fusing.<br />

• Works with Mag Pickup,<br />

Alternator or <strong>Genset</strong> Output<br />

(300V max).<br />

• Field Settings with<br />

potentiometers and DIP switches.<br />

• Setup mode for quick calibration.<br />

BY SPECIAL ORDER<br />

The ES52 also offers the following<br />

features available by special order.<br />

Please contact DynaGen for details.<br />

• Preset Calibration with Fixed Settings<br />

to prevent tampering<br />

• Under-speed shutdown<br />

• Mid-heat & Post-heat functions<br />

(during and after cranking)<br />

• Cool-down timer<br />

• Pull/Hold Coil control for fuel<br />

solenoid<br />

• Momentary inputs for multiple<br />

start/stop locations<br />

• Inputs for Photocell start/stop<br />

control<br />

www.dynagen.ca | 1-888-396-2436<br />

7


8<br />

ES52 Autostart <strong>Engine</strong> <strong>Control</strong>ler<br />

SPECIFICATIONS<br />

Operating Voltage<br />

• 7 to 32 VDC continuous<br />

• Standby Current Draw: 12mA<br />

• Surge Withstand: 1500V for 250μS<br />

• Reverse Polarity Protected<br />

Operating Temperature<br />

• -40 to +85°C<br />

Physical<br />

• Dimensions: 3.3”H x 3.3”W x 1.8”D<br />

• Weight: 0.67 lbs<br />

• Industry standard mounting configuration<br />

• Eurostyle removable connectors<br />

Speed Sensing (user selectable<br />

sensing ranges)<br />

• Magnetic pickup: 1V to 300V<br />

• Generator Output: Up to 300VAC direct<br />

Typical Wiring<br />

Example<br />

Ordering Information<br />

Part No: ES52-0000-12-A-08-LS*<br />

2010<br />

PRODUCT<br />

CATALOG<br />

• Accepts Tach signal from belt driven alternators<br />

Loss of Speed signal protection during cranking<br />

and running (can be disabled while cranking)<br />

Failure Inputs<br />

• Low oil pressure failure* (closed on failure)<br />

• High engine temp failure* (closed on failure)<br />

• Auxiliary failure* (closed on failure)<br />

*Failure inputs can close to either +battery or<br />

ground. All failure inputs are ignored for a period<br />

of 15 seconds at engine startup.<br />

*Comes with 12VDC relays installed.<br />

Consult factory for part numbers for special order controllers.<br />

Available Accessories: RLY0017 – 24V relays<br />

Outputs<br />

• Fuel & Crank: 20A high capacity replaceable<br />

automotive relays<br />

– Switched to battery positive<br />

– 12 or 24 VDC battery system (select<br />

appropriate relay for system voltage)<br />

• Short circuit & overload protection on<br />

annunciation outputs (rated 300max)<br />

To find out more visit<br />

www.ES52.info


GSC300 Digital<br />

<strong>Genset</strong> <strong>Control</strong>ler<br />

Includes 6 <strong>Engine</strong> Instruments<br />

The GSC300 is designed to<br />

provide autostart control,<br />

protection, and engine<br />

instrumentation for all types<br />

of diesel and gas generator<br />

sets. The module is easily<br />

confi gured using either the<br />

front panel buttons<br />

or our PC confi gurator<br />

software. The GSC300<br />

Compact 4.3” x 5.5” x 2.16” Footprint<br />

provides direct mounting<br />

compatibility with other<br />

DynaGen controllers such as the<br />

GSC400 to allow for a full range of options to fi t the application.<br />

Displays:<br />

• Oil Pressure<br />

• <strong>Engine</strong> Temperature<br />

• Fuel Level<br />

• Hour Meter<br />

• Frequency<br />

• Battery Voltage<br />

GSC300 showing 40A removable<br />

relays, replaceable fuses and<br />

annunciator strip<br />

• Conformally coated for<br />

protection against moisture and<br />

contaminants.<br />

• Customizable Screen Messages.<br />

• Confi gurable via front panel or PC.<br />

• Accepts industry standard senders<br />

(VDO, Stewart-Warner, Datcon,<br />

Murphy).<br />

• Zero speed restart prevents starter<br />

pinion wear.<br />

• Timers for: Pre-heat/Warm-up/<br />

Energize-to-stop, Cool-down,<br />

<strong>Engine</strong> Start Delay, Mid-heat and<br />

Post-heat.<br />

• Low Battery Indication.<br />

• Restart on false attempts.<br />

• Optional Fuel OFF during crank<br />

rest period.<br />

• 5-Year Warranty.<br />

www.dynagen.ca | 1-888-396-2436<br />

9


GSC300 Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

10<br />

Incorporates the Functions<br />

of 6 External Gauges<br />

The GSC300 displays 6 critical<br />

engine readings through a backlit<br />

digital display augmented by 8<br />

high-intensity lights for failure<br />

and status conditions. A built-in<br />

Auto/Manual/Off Switch is also<br />

included.<br />

3 On-board Replaceable 40A<br />

Relays & Fuses<br />

The GSC300 is socketed to<br />

accept 3 industry standard 40A<br />

cube relays – each protected by<br />

a replaceable automotive fuse.<br />

The GSC300 eliminates the need<br />

to mount, wire, and fuse external<br />

slave relays for Fuel, Crank, and<br />

Pre-heat.<br />

Computer or Manually<br />

Programmable<br />

The GSC300 can be programmed<br />

manually via front panel buttons<br />

or with our free, easy-to-use<br />

PC software interface that<br />

provides customization of screen<br />

messages, languages, sender<br />

selections, and control settings.<br />

Easy-to-Use PC<br />

Configuration Software<br />

2010<br />

PRODUCT<br />

CATALOG<br />

SPECIFICATIONS<br />

Operating Voltage<br />

• 7 to 30VDC continuous, with zero volts<br />

cranking dropout protection<br />

• Reverse battery protected<br />

• Standby current draw: 40mA<br />

• Surge withstand: 1500V for 250μS<br />

Operating Temperature<br />

• <strong>Control</strong>ler Function: -40 to +85˚C<br />

• Display Screen Viewing: -15 to +70˚C<br />

Physical<br />

• Dimensions: 4.3”H x 5.5”W x 2.16”D<br />

• Weight: 0.75 lb<br />

Speed Sensing<br />

• Generator Output: Up to 300VAC<br />

(no external transformer required)<br />

Inputs<br />

• Oil Pressure Input – Sender (0-500Ω)<br />

or Switch*<br />

• <strong>Engine</strong> Temp Input – Sender (0-500Ω)<br />

or Switch*<br />

• Fuel Level/Aux Input – Sender (0-500Ω)<br />

or Switch*<br />

*Failure inputs must close to ground.<br />

All failure inputs are ignored for a adjustable<br />

bypass period.<br />

Outputs<br />

• Fuel, Crank & Preheat/WarmUp/ETS: 40A high<br />

capacity replaceable automotive relays:<br />

– Switched to battery positive<br />

– 12 or 24 VDC battery system (select<br />

appropriate relay for system voltage)<br />

• Short circuit & overload protection on<br />

annunciation outputs (rated 300ma max.)


GSC300 Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

Typical Wiring Example<br />

Ordering Information<br />

Part No. GSC300-L-12-LS*<br />

*comes with 12VDC relays installed.<br />

Available Accessories:<br />

RLY0043 - 24V relays; RLY0054 - UL Listed 24V relays<br />

ACC0108 – S&W Oil Press Sender (279B-F), 100PSI, 240Ω, 1/8”-27 NPTF<br />

ACC0027 – DATCON Temp Sender 100-280C, 1/8”-27 NPTF<br />

GSC300-PGMR – Parallel Port Programming Kit with software<br />

GSC300-USB-PGMR – USB Programming Kit with software<br />

ENC0057 – NEMA 1 Enclosure with vibration mounts<br />

<strong>Control</strong> <strong>Panels</strong> with GSC300 in NEMA 1<br />

enclosure with selector switch, AC Volts &<br />

Amps meters, CTs, and vibration mounts:<br />

GCP300-L-____A-300V-2-12VDC (1Ph, 300V)<br />

GCP300-L-____A-600V-3-12VDC (3Ph, 600V)<br />

(100, 200, 300, 500, 600, 1000, or 1500A<br />

meters & CTs available)<br />

Also available in a control panel with<br />

AC meters – see left for ordering<br />

information<br />

To find out more visit<br />

www.GSC300.info<br />

www.dynagen.ca | 1-888-396-2436<br />

11


NEW<br />

12<br />

GSC400Plus Digital<br />

<strong>Genset</strong> <strong>Control</strong>ler<br />

Displays AC Volts/Amps<br />

Standard or Electronic <strong>Engine</strong>s<br />

The GSC400Plus is designed<br />

to provide complete control,<br />

protection, AC metering, and<br />

engine instrumentation for<br />

both standard and electronic<br />

engines and gensets. The<br />

module is easily confi gured<br />

using either the front panel<br />

buttons or our PC confi gurator Compact 4.3” x 5.5” x 2.75” Footprint<br />

software. The GSC400Plus<br />

provides direct mounting<br />

compatibility with other DynaGen controllers such as the GSC300 to<br />

allow for a full range of options to fi t any application.<br />

Displays:<br />

• Oil Pressure • <strong>Engine</strong> Temperature<br />

• Fuel Level • Oil Level<br />

• Hour Meter • RPM<br />

• 3-Phase AC Volts & Amps<br />

• Frequency • Battery Voltage<br />

• J1939 Diagnostic Codes<br />

Features and Functions:<br />

• SAE J1939 Protocol.<br />

• NFPA Level 1 Compliant.<br />

• 3 On-Board 40A Relays.<br />

• Real-Time Clock.<br />

• 100 Event Failure Log.<br />

• Conformally coated for<br />

protection against moisture and<br />

contaminants.<br />

• 8 Confi gurable Switched Inputs<br />

& 9 Confi gurable Switched<br />

Outputs.<br />

• Autostart on Low Battery function.<br />

• Built-in <strong>Engine</strong> Exerciser.<br />

• Free PC Confi gurator Software.<br />

• Front or Rear Mountable.<br />

• Password protected.<br />

2010<br />

PRODUCT<br />

CATALOG<br />

GSC400Plus showing 40A<br />

removable relays, replaceable<br />

fuses and annunciator strip<br />

• Modbus Port to connect remote<br />

annunciators and other devices.<br />

• Options for remote monitoring<br />

over Internet and cellular.<br />

• Accepts common senders (VDO,<br />

Datcon, Murphy, and more).<br />

• Custom senders confi gurable<br />

with PC software.<br />

• Dummy Load function to prevent<br />

wet stacking.<br />

• Options for Fuel OFF during<br />

Crank Rest, Restart on False<br />

Attempt and Locked Rotor.<br />

• 5-Year Warranty.


3 On-board Replaceable<br />

40A Relays & Fuses<br />

The GSC400 is socketed to<br />

accept three industry standard<br />

40A cube relays – each protected<br />

by a replaceable automotive fuse.<br />

The GSC400 eliminates the need<br />

to mount, wire, and fuse external<br />

slave relays for Fuel, Crank, and<br />

Preheat.<br />

Front Panel or PC Configurable<br />

The GSC400 can be programmed<br />

manually via front panel<br />

buttons or with our easy-touse<br />

PC software interface that<br />

provides customization of screen<br />

SPECIFICATIONS<br />

Operating Voltage<br />

• 7 to 32VDC with operation to 0VDC for 50mS<br />

• Standby Current Draw: 50mA<br />

• Reverse battery protected<br />

• Surge withstand: 1500V for 250μS<br />

Operating Temperature<br />

• <strong>Control</strong>ler Function: -40 to +85˚C<br />

• Display Screen Viewing: -20 to +70˚C (consult<br />

factory for optional heater for -40˚C operation)<br />

Physical<br />

• Dimensions: 4.3”H x 5.5”W x 2.75”D<br />

• Weight: 0.97 lb<br />

Speed Sensing<br />

• Via J1939 bus, Magnetic pick-up, or Generator<br />

AC (up to 300VAC direct)<br />

Inputs<br />

• Voltage Sensing:<br />

- Single-phase, 3-phase, Delta, Wye<br />

- Max 700vac<br />

- True RMS, +/- 1% of full scale<br />

• Current Sensing:<br />

- Accepts 5A secondary CTs<br />

- +/- 2% of full scale<br />

• Sensors:<br />

- Inputs 5, 6, 7: Sender (> 500Ω) or Switch*<br />

- Inputs 2, 3, 4: Sender (0-500Ω) or Switch*<br />

*Failure inputs must close to ground. All failure<br />

GSC400Plus Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

messages, sender selections,<br />

control settings, and much more.<br />

Ideal for Mobile <strong>Genset</strong>s<br />

The GSC400 is a great fit<br />

for mobile and trailer genset<br />

applications:<br />

• Ultra-Low Standby Draw<br />

prevents battery drain (50mA).<br />

• Inputs to automatically reconfigure<br />

for up to 4 different<br />

AC voltage topologies.<br />

• Maintenance Timer.<br />

• Inputs for fuel saving Idle Mode*.<br />

* Compatible with Cummins Tier IV idle mode<br />

inputs are ignored for a adjustable bypass period.<br />

• Configurable Switched Inputs:<br />

- Inputs A,B,C,D (Close to Bat)<br />

- Inputs E,F,G,H (Close to Gnd)<br />

Electronic <strong>Engine</strong> Support:<br />

• Standard J1939 <strong>Engine</strong>s (Tier II, II & IV)<br />

• Customized display for Volvo, John Deere,<br />

Cummins, Yanmar, Detroit <strong>Diesel</strong> and more*<br />

* Consult factory for updates<br />

Outputs<br />

• Fuel, Crank & Extra Output – 40A high capacity<br />

replaceable automotive relays:<br />

- Switched to Battery Positive<br />

- 12 or 24 VDC battery system (select<br />

appropriate relays for system voltage)<br />

• Switched Outputs (A-H) - 200mA max:<br />

- Switched to Ground<br />

- Short circuit & overload protected<br />

Communications<br />

• SAE J1939<br />

- Tier II, III, & IV engines<br />

- Address settings for both the GSC400 and the<br />

engine ECM<br />

• Modbus:<br />

- GSC400 operates in RTU Slave mode<br />

- RS485 port (9600, 19200, 38400, 57600 baud)<br />

www.dynagen.ca | 1-888-396-2436<br />

13


14<br />

GSC400Plus Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

Easy-to-Use PC<br />

Configuration Software<br />

Every setting of the feature-rich<br />

GSC400 is easily configured with<br />

its powerful, yet easy-to-use PCbased<br />

software interface.<br />

Here are just some of the<br />

functions made available to you:<br />

Sensor Inputs<br />

(Sender/Switch or J1939)<br />

• High <strong>Engine</strong> Temp<br />

• Low Oil Pressure<br />

• Fuel Level<br />

• Oil Level<br />

• Fuel in Basin<br />

• Low <strong>Engine</strong> Temp<br />

Switched Output<br />

Functions (Select up to 9)<br />

• Warm-up<br />

• Energize-to-Stop<br />

• Pre-heat<br />

• Cool-down<br />

• Overcrank<br />

• High Temp Failure/Warning<br />

• Low Oil Failure/Warning<br />

• Underspeed Failure/Warning<br />

• Overspeed Failure/Warning<br />

• Low Fuel Failure/Warning<br />

• Battery Failure/Warning<br />

• Low Coolant Failure/Warning<br />

• Not-in-Auto<br />

• General Failure<br />

• Crank Rest<br />

• <strong>Engine</strong> Running<br />

• <strong>Engine</strong> Cranking<br />

• Exerciser Alarm<br />

• Battery Recharge Alarm<br />

• Under Voltage Warning<br />

• Over Voltage Warning<br />

• Over Current Warning<br />

• Fuel-in-Basin Warning<br />

2010<br />

• Voltage Regulator<br />

• Low Temperature<br />

• Backlight<br />

• Auxiliary Warning<br />

• Maintenance Timer<br />

• System Ready<br />

• Common Fault<br />

• Dummy Load<br />

• High Fuel Level<br />

• Current Latch<br />

• User Configurable<br />

Warning 1 & 2<br />

• User Configurable<br />

Failure 1 & 2<br />

Timers<br />

• Pre-heat, Mid-heat & Post-heat<br />

• Delay-to-Start<br />

• Warm-up & Cool-down<br />

• Energize-to-Stop<br />

• Programmable <strong>Engine</strong><br />

Exerciser<br />

Battery Functions<br />

• Low/High Battery<br />

Warning & Failure<br />

• Autostart on Low<br />

Battery Function<br />

PRODUCT<br />

CATALOG<br />

AC Functions<br />

• Overspeed/Underspeed<br />

Warning & Failure<br />

• Over/Under Frequency Warning<br />

& Failure<br />

• Over/Under Voltage<br />

Warning & Failure<br />

• Over Current Warning & Failure<br />

• AC Secondary Crank Disconnect<br />

Switched Input Functions<br />

(Select up to 8)<br />

• Emergency Stop<br />

• Low Air Pressure<br />

• Low Hydraulic Pressure<br />

• Low Oil Pressure<br />

• EPS Supplying Load<br />

• Alarm Silence<br />

• Low Coolant<br />

• Voltage Topology Select 1 & 2<br />

• Idle Mode<br />

• Start/Stop<br />

• Charger Fault 1 & 2<br />

• High Fuel Level<br />

• Auxiliary Failure & Warning<br />

• User Configurable Warning 1 & 2<br />

• User Configurable Failure 1 & 2


Typical Wiring Example<br />

Ordering Information<br />

Part No. GSC400-0-12-LSB*<br />

*Comes with 12VDC relays installed.<br />

Available Accessories:<br />

GSC400Plus Digital <strong>Genset</strong> <strong>Control</strong>ler<br />

RLY0043 - 24V relays; RLY0054 - UL Listed 24V relays<br />

ACC0108 – S&W Oil Press Sender (279B-F) 100PSI, 240 Ohm, 1/8”-27 NPTF<br />

ACC0027 – DATCON Temp Sender 100-280C, 1/8”-27 NPTF<br />

GSC400-PGMRB – USB/Serial Programming Kit with software<br />

ENC0057 – NEMA 1 Enclosure with vibration mounts<br />

Current Transformers:<br />

ACC0045 (100A), ACC0046 (200A), ACC0047<br />

(300A), ACC0048 (500A), ACC0049 (600A),<br />

ACC0050 (1000A), ACC0057 (1500A)<br />

Starter Harness Kits:<br />

Harness kits are prewired in connector plugs<br />

and populated with common connection<br />

points for most applications. Extra crimp wires<br />

are available for further flexibility.<br />

ACC0086 – 5ft Starter Kit (AC Current Sensing,<br />

Switched Inputs, and Sensor Inputs)<br />

DWG1373 – 5ft J1939 Cable<br />

DWG1377 – 5ft Switched Outputs Cable<br />

DWG1410 – Pre-Crimped individual wires (pkg of 5)<br />

DWG1454 - 5ft RS485/Modbus Cable<br />

Also available with an optional control<br />

panel enclosure (ENC0057)<br />

To find out more visit<br />

www.GSC400.info<br />

www.dynagen.ca | 1-888-396-2436<br />

15


GSC400Plus Companion Products – RA400 Remote Annunciator<br />

16<br />

RA400 Remote Annunciator<br />

For NFPA110 Applications<br />

The RA400 remote serial<br />

annunciator monitors the<br />

condition of the generator set<br />

from a remote location when<br />

it is equipped with a DynaGen<br />

GSC400Plus <strong>Genset</strong> <strong>Control</strong>ler.<br />

If a generator alarm condition<br />

occurs, the remote annunciator<br />

alerts the operator through lamps<br />

and an audible alarm.<br />

• Connects via 3-wire Modbus<br />

to the GSC400Plus genset<br />

controller up to 2800 ft.<br />

• 20 Lamp Indicator for Warnings,<br />

Status, and Failures.<br />

• NFPA-110, NFPA 99<br />

& CSA 282-00 compliant.<br />

• 2 User configurable lamps with<br />

writable surfaces.<br />

• Extra switched inputs for System<br />

Enable/Disable and <strong>Genset</strong> Start/<br />

Stop.<br />

• Audible Alarm.<br />

• Modbus RTU serial connection.<br />

• Surface or flush-mounted. Also<br />

fits in a standard 203 mm x 203<br />

mm (8 in. x 8 in.) Hoffman box.<br />

• Conformal coated circuit board<br />

for moisture protection.<br />

• Up to 4 RA400 annunciators can<br />

be easily connected to the same<br />

wiring.<br />

• Powered by 12 or 24VDC.<br />

• Optional 120 VAC Power Supply.<br />

• 5-Year Warranty.<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Shown with<br />

optional enclosure.<br />

Type LED Indication<br />

Green Amber Red<br />

Overcrank X X<br />

Overspeed X X<br />

Emergency Stop X<br />

High <strong>Engine</strong> Temperature X X<br />

Low Oil Pressure X X<br />

Low Coolant Level X<br />

Low Coolant Temperature X<br />

Low Fuel Level X X<br />

Communication Status X X<br />

Not In Auto X X<br />

High Battery Volts X X<br />

Low Battery Volts X X<br />

Common Fault X X<br />

Low Cranking Volts X<br />

Battery Charger Failure X<br />

User Configurable 1 X<br />

User Configurable 2 X X<br />

System Ready X X<br />

Generator Running X<br />

EPS Supplying Load X


GSC400Plus Companion Products – RA400 Remote Annunciator<br />

SPECIFICATIONS<br />

Power Supply<br />

• 6 to 30VDC<br />

• Meets SAE J-1113 Load Dump<br />

• Reverse Battery Protected<br />

• Current Draw: 100mA – 250mA<br />

Operating Temperature<br />

• -40˚C to +85˚C<br />

Physical<br />

• Dimensions: 8.0” x 8.0” x 1.5”<br />

• Weight: 1.5 lbs<br />

Audible Alarm<br />

• 71 to 86db at 2ft<br />

Ordering Information<br />

Part No. RA400-LS<br />

Available Accessories:<br />

Communications<br />

• Modbus RTU (RS-485)<br />

• Max Distance: 2800ft using Belden 9841 cable<br />

or equivalent<br />

• Master or Slave configuration<br />

• 9600 or 19200 Baud<br />

• Optical Isolation for surge immunity<br />

Switched Inputs<br />

• 2 Inputs for System Enable/Disable and<br />

<strong>Genset</strong> Start/Stop<br />

• 2 wire ground/positive input to trigger<br />

DWG1454 – 5ft pigtail harness for Modbus connection to GSC400<br />

ACC0109 – 8”x8”x4” Pull Box (Hoffman ASE8X8X4)<br />

ACC0111 – 120VAC to 24VDC power adaptor (Mean Well ELN-60-24)<br />

www.dynagen.ca | 1-888-396-2436<br />

17


GSC400Plus Companion Products – DynaLink Remote Monitoring<br />

18<br />

DynaLink Remote <strong>Genset</strong> Monitoring<br />

The DynaLink genset monitoring system allows you to monitor and<br />

control generator sets over LAN, Internet, telephone modem, or wireless<br />

cellular connections. The system contains built-in features such as an<br />

alarm handler (SMS, Email and SNMP), data logger (with trend graphs)<br />

and a built-in web server for monitoring and control.<br />

The DynaLink WS100 module connects to the Internet via its builtin<br />

Ethernet port to a GSC400Plus <strong>Genset</strong> <strong>Control</strong>ler at a facility. The<br />

DynaLink system makes the data<br />

available in an internal web server that<br />

can be accessed by the user using a<br />

standard web browser, like Internet<br />

Explorer. This makes it possible<br />

for the user to instantly read<br />

any parameter available from<br />

a remote location. Optionally,<br />

a PSTN dial-up modem<br />

can be connected to the<br />

WS100 to provide access via<br />

conventional telephone lines.<br />

The WS200 module adds<br />

the additional capability<br />

of using its built-in quad<br />

band GSM/GPRS cellular<br />

modem with any standard<br />

SIM card for remote or<br />

mobile gensets without<br />

Internet. It also supports<br />

an external GPS receiver<br />

which makes it possible to<br />

use it for applications where the<br />

geographical position is important, such as<br />

rental fleets.<br />

2010<br />

PRODUCT<br />

CATALOG


GSC400Plus Companion Products – DynaLink Remote Monitoring<br />

• Ability to reset faults and restart<br />

genset.<br />

• Full start/stop/enable/disable<br />

control.<br />

• Monitoring of all warnings,<br />

failures, status, sensor readings,<br />

AC metering, including J1939<br />

engine information.<br />

Ordering Information<br />

Part No. WS100 – Ethernet only<br />

Part No. WS200 – Ethernet and built-in GSM/GPRS cellular modem<br />

Available Accessories:<br />

ACC0112 – Accessory Kit (Power Adapter and Cables)<br />

SMA quadband antenna options:<br />

ACC0113 – Straight<br />

ACC0114 – Right angle<br />

ACC0115 – Magnetic foot<br />

Cables for SMA antennae:<br />

ACC0116 – 9.8ft<br />

ACC0117 – 16.4ft<br />

ACC0118 – 32.8ft<br />

ACC0118 - Optional GPS receiver (SA-920) for WS200<br />

Dial-Up Telephone Modem for WS100 (consult factory)<br />

• Alarm & Status handler<br />

(notifications via SMS, E-mail and<br />

SNMP).<br />

• Data logging with trend graph<br />

presentation (can be downloaded<br />

to a spreadsheet).<br />

• Ability to access GSC400Plus<br />

internal event log.<br />

• Password restricted access<br />

control.<br />

• DIN rail mounting.<br />

• Optional, fee-based Web Site<br />

access to multiple sites<br />

• Easily connects to GSC400Plus<br />

via 3-wire Modbus/RS485 port.<br />

• 1-Year Warranty.<br />

www.dynagen.ca | 1-888-396-2436<br />

19


20<br />

Vigilant <strong>Automatic</strong> Transfer<br />

Switches<br />

100A to 1250A<br />

The Vigilant Series ATS is<br />

designed to automatically<br />

transfer critical loads in the<br />

event of a power outage. It<br />

consists of a simple, rugged<br />

design while maintaining the<br />

fl exibility required to meet the<br />

needs of residential, agricultural,<br />

and light industrial applications.<br />

• Rugged Contactor Design –<br />

Double Throw, Mechanically<br />

Interlocked.<br />

• Galvanized Steel Enclosure.<br />

• Externally accessible Exerciser<br />

Clock and Lamps.<br />

• 5-Year Warranty.<br />

DynaGen’s VTSC100 <strong>Control</strong>ler<br />

Board<br />

The VTSC100 Logic <strong>Control</strong>ler<br />

Board is at the heart of every<br />

Vigilant <strong>Automatic</strong> Transfer Switch.<br />

It is designed to provide all basic<br />

transfer switch control functions<br />

with simplicity, fl exibility, and<br />

durability.<br />

Features include:<br />

• Powered from genset battery for<br />

isolation against line transients.<br />

• Integrated voltage and frequency<br />

sensing.<br />

• Adjustable transfer delays using<br />

on-board potentiometers.<br />

• Fused remote start contact<br />

relays.<br />

• Adjustable drop-out &<br />

pick-up values for voltage<br />

and frequency.<br />

• Internal test switch included.<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Conformally Coated<br />

Every VTSC controller board is<br />

thoroughly conformally coated<br />

to create an eff ective barrier<br />

against moisture, fungus and other<br />

contaminants that can cause:<br />

• Short circuits.<br />

• Corrosion of conductors and<br />

solder joints.<br />

• Electrical leakage between<br />

circuits.<br />

• Mechanical stress of components.<br />

• Loss of insulation protection.


Galvanized Corrosion Protection<br />

Standard on all Vigilant<br />

Enclosures<br />

The Vigilant enclosure is made from<br />

duplex coated, galvanized G90 grade<br />

steel and meets American Society<br />

for Testing and Materials (ASTM)<br />

standard A653. The service life of our<br />

galvanized steel enclosures is more<br />

than twice that of regular steel.<br />

Specifi cations (Standard Withstand Models)<br />

Vigilant <strong>Automatic</strong> Transfer Switches<br />

Operator Interface with external access<br />

DynaGen’s easy-to-use, 7-day exerciser<br />

clock gives you full control over day and<br />

time. The exerciser clock and indicator<br />

lamps are both accessible from outside<br />

the transfer switch. There’s no need to<br />

open the door to adjust the clock or<br />

view the status of the transfer switch,<br />

even with the NEMA 3 enclosure option.<br />

Operating Temperature: -20 to +70˚C; Operating Humidity: 0-95% Relative, Non-Condensing<br />

VTSC100 ATS <strong>Control</strong>ler Specifications<br />

12 or 24VDC (factory jumpers); Standby Draw: 25mA<br />

www.dynagen.ca | 1-888-396-2436<br />

21


22<br />

Vigilant <strong>Automatic</strong> Transfer Switches<br />

Ordering Information<br />

VTS2 – 0400 – 2 – 240 – 12 – X – N3 –LS<br />

Ampere<br />

Rating<br />

0100<br />

0200<br />

0400<br />

0600<br />

1000<br />

1250<br />

Number<br />

Poles<br />

2 = 2 Pole<br />

3 = 3 Pole<br />

4 = 4 Pole<br />

Example: VTS2-0400-2-240-12-X-N3<br />

ATS Rated 400 Amp, Single-Phase 2-Pole, 120/240V, NEMA 3 enclosure<br />

Note: Please consult factory for “LM” version that provides compatibility to Briggs and Stratton generators with<br />

Power Management System.<br />

Available Accessories:<br />

ACC0107 – Keyed Locks for Enclosure<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Voltage<br />

240 = 120/240<br />

208 = 120/208<br />

480 = 277/480<br />

Delay-on-<br />

Neutral<br />

X = Standard<br />

D = Delayon-Neutral<br />

(standardon<br />

600Aandabove)<br />

Enclosure<br />

Type<br />

N1 = Nema 1<br />

N3 = Nema 3<br />

(N1comes<br />

with<br />

knock-outs.<br />

N3isstandard<br />

To find out more visit<br />

www.VigilantATS.info


Vigilant Load Center<br />

100A <strong>Automatic</strong> Transfer Switch<br />

with Breaker Panel<br />

The Vigilant Load Center is ideally suited for<br />

residential and light commercial applications.<br />

It eliminates the need for a separate sub-panel<br />

and fi ts snugly between two studs. The unit also<br />

includes the full-featured VTSC100 controller which<br />

allows easy adjustment of time delays and voltage/<br />

frequency settings.<br />

• Rugged contactor-based double throw switch.<br />

• Eliminates the need for separate sub-panel.<br />

• Robust full-featured controls (see VTSC100 controls on page 20).<br />

• Externally accessible Exerciser Clock and LED’s.<br />

• Square D QO panel accepts 12 Regular or 24 Mini Circuit Breakers<br />

(optionally supplied).<br />

• 5-Year Warranty.<br />

Flexible and Easy-to-Use Exerciser<br />

Specifi cations<br />

Operating Temperature: -20 to +70˚C; Operating Humidity: 0-95% Relative, Non-Condensing<br />

AC Rating Voltage<br />

UL Withstand<br />

Ratings*<br />

Poles<br />

100 Amp 120/240 10KA 2<br />

Lightweight and Easy to Install – the<br />

Vigilant Load Center fi ts snugly<br />

between two studs and has plenty of<br />

conveniently placed knock-outs<br />

Enclosure<br />

(H x W x D)<br />

26” x 14.25”<br />

x 6”<br />

Lbs. Lug Capacities<br />

<strong>Control</strong>ler – See Page 21 for VTSC100 controller specifi cations<br />

*Please consult factory for specifi c protective device specifi cations and ratings. UL1008 – Optional Standby<br />

Systems<br />

45<br />

1/0 to 14Cu<br />

or 1/0 to<br />

www.dynagen.ca | 1-888-396-2436<br />

23


Vigilant Load Center<br />

24<br />

Ordering Information<br />

VLC2 – 0100 – 2 – 240 – 12 – X – N1 – LS<br />

Ampere<br />

Rating<br />

Number<br />

Poles<br />

Example: VLC2-0100-2-240-12-X-N1-LS<br />

100Amp, single-phase 2-pole, 120/240, Nema 1 enclosure, with breakers*.<br />

*Breakers supplied:<br />

• Five 15A single pole<br />

• Three 20A single pole<br />

• One 20A double pole<br />

Note: Consult factory for ‘No Logic’ version supplied without VSTC-100 controller.<br />

2010<br />

PRODUCT<br />

CATALOG<br />

Voltage Enclosure Breakers<br />

0100 2 = 2 Pole 240 = 120/240<br />

N1 = NEMA 1<br />

LS = w/breakers*<br />

LX = w/o breakers<br />

To find out more visit<br />

www.VigilantATS.info


Custom OEM Solutions<br />

When an off-the-shelf controller just won’t do the job, call DynaGen.<br />

Our proven control platforms can be adapted to just about any special<br />

application. Think of us as your product design team!<br />

DynaGen’s integrated design philosophy centers around the use of<br />

flexible, microprocessor control modules that can be integrated to<br />

deliver many value-added features in a single, low-cost package. The<br />

result is the elimination of many costly external components and<br />

increased reliability.<br />

Our capabilities<br />

• Testing to Mil-Spec standards.<br />

• Mobile and special transfer<br />

switch applications.<br />

• Battery management.<br />

• Graphic display panels for<br />

engines and gensets.<br />

• Air/Fuel & Spark <strong>Control</strong> for gas<br />

engines.<br />

• Electronic Governors.<br />

• CANbus/J1939.<br />

• Remote telemetry by satellite,<br />

cellular and internet.<br />

Sample applications from recent<br />

projects<br />

• Locomotive <strong>Engine</strong> <strong>Control</strong>.<br />

• Marine <strong>Engine</strong> Management<br />

System.<br />

• Truck APU control and remote<br />

display.<br />

• Vehicle transfer switch.<br />

• Residential no-logic transfer<br />

switch.<br />

www.dynagen.ca | 1-888-396-2436<br />

25


POWER CONTROLS<br />

YOU CAN TRUST<br />

The US Army<br />

conducted a series<br />

of tests to establish<br />

the ruggedness of<br />

a battlefield communications system<br />

on a Humvee genset outfitted with a<br />

DynaGen controller. The rough treatment<br />

even included jolting chopper transport.<br />

The Result: Over 10 years of trouble-free<br />

deployment around the globe.<br />

NASA and Carnegie-<br />

Mellon University took a<br />

Nomad Lunar Rover to<br />

the harsh Atacama Desert<br />

in Peru for a series of<br />

punishing tests. Their on-board controller?<br />

A DynaGen. The Result: The Nomad<br />

traveled an unprecedented 215 km in 45<br />

days, under full remote control.<br />

<strong>Genset</strong> <strong>Control</strong> <strong>Panels</strong><br />

<strong>Diesel</strong> & <strong>Gas</strong> <strong>Engine</strong> <strong>Control</strong>lers<br />

<strong>Automatic</strong> Transfer Switches<br />

75 Akerley Boulevard, Dartmouth, Nova Scotia, Canada B3B 1R7<br />

1-888-396-2436 (1-888-DYNAGEN) | www.dynagen.ca

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!