07.01.2013 Views

Rxf - Johnson Controls Inc.

Rxf - Johnson Controls Inc.

Rxf - Johnson Controls Inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

070.410-IOM (JUL 11)<br />

Page 16<br />

COMPRESSOR OIL COOLING SYSTEMS<br />

The RXF unit can be equipped with one of several systems<br />

for controlling the compressor oil tempera ture. They are<br />

single or dual-port liquid injection, thermosyphon, or watercooled<br />

oil coolers. Each system is automati cally controlled,<br />

independent of compressor loading or unloading.<br />

Oil cooling systems maintain oil temperature within the following<br />

ranges for R-717 and R-22:<br />

Liquid Injection Oil Cooling - 130 - 150°F<br />

External* Oil Cooling - 120 - 140°F<br />

* Thermosyphon Oil Cooling (TSOC) or Water-Cooled Oil<br />

Cooling (WCOC).<br />

SINGLE-PORT LIQUID INJECTION<br />

The single-port liquid injection system is desig ned to permit<br />

liquid refrigerant injection into one port on the compressor<br />

at any given moment and operates as outlined.<br />

The liquid injection solenoid valve is energized by the microprocessor<br />

when the temperature sensor, in stalled in the<br />

compressor discharge, exceeds the setpoint. High-pressure<br />

liquid refriger ant is then supplied to the motorized expansion<br />

valve. Refer to P & I DIAGRAMS section for piping and<br />

instrumentation drawings.<br />

DUAL-PORT LIQUID INJECTION<br />

The dual-port liquid injection system is design ed to obtain<br />

the most efficient compressor performance at high and low<br />

compression ratios by permitting injection of liquid refriger ant<br />

into one of two ports optimally located on the com pressor.<br />

Figure 21<br />

• Press [ 1 ] on the keypad to drive the output to the low<br />

end. Using numbers [ 4 ], [ 7 ], and [ 0 ] on the keypad to<br />

increase and decrease the output and change the “Delta<br />

For Changing Output Percentage” setpoint, set the output<br />

to 4mA.<br />

RXF ROTARY SCREW COMPRESSOR UNITS<br />

OPERATION<br />

This minimizes the performance penalty incurred with liquid<br />

injection oil cooling.<br />

The dual-port system contains all the com ponents of the<br />

single-port system with the addition of a double-acting<br />

solenoid valve and operates as outlined.<br />

The liquid injection solenoid valve is energized by the<br />

micro processor when the temperature sensor, in stalled in<br />

the compressor discharge, exceeds the setpoint. Liquid<br />

refrigerant is then passed through the motorized expansion<br />

valve to the doub le-acting solenoid valve. Depending on the<br />

compressor’s operating volume ratio (Vi), the micropro cessor<br />

will select the flow of the liquid refrigerant to the optimum<br />

com pressor port.<br />

QUANTUMLX EZ-COOL LIQUID<br />

INJECTION ADJUSTMENT PROCEDURE<br />

Use the following directions to set up and tune the EZ-Cool LIOC with a QuantumLX Control Panel. Also refer to publication<br />

090-022 O, QuantumLX Operation, for an overview<br />

of PID control.<br />

First, complete calibration of the analog output used for EZ-Cool <br />

LIOC. Typically, this will be analog output #1 for PID #1.<br />

• Power down the panel and remove the two control wires<br />

for the valve from terminals 1 & 2 of the P11A terminal<br />

strip of analog board #1.<br />

• Place the leads of a calibrated, quality meter to terminal<br />

one (positive) and terminal two (negative). Set the meter<br />

to read mA DC and power up the panel.<br />

• Set operating session to Session 2 and go to the screen<br />

shown in Figure 21 by pressing [Menu] >[Calibration] ><br />

[Analog Outputs] > [Output Calibration].<br />

• If the read value is less than the objective of 4 or 20mA<br />

use [ 7 ] on the keypad to increase the output by the<br />

Delta. If the read value is more than the objective, use<br />

[ 4 ] to decrease the value by the Delta.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!