Generally for both programs (16, 17):<br />

No thermostat function or differential switching function is activated. Calling one of these<br />

two programs the measuring speed of the outputs S2 and S3 is automatically increased from<br />

MW 16 to MW 4 (see in the menu Men under SENSOR) and the speed control (see in the<br />

menu Men under PDR) is activated as an alternative parameter list with the following factory<br />

settings:<br />

Abs. value control AC….. I 2 Desired value DVA….. 48°C<br />

Differential regulator DC.. N12- Desired value DVD….. 7,0K<br />

Event regulator EC…...... ---<br />

Waveform…………….…. WAVEP<br />

Proportional part PRO…. 3<br />

Integral part INT………… 1<br />

Differential part DIF…….. 4<br />

Minimum speed MIN….... 0 Maximum speed MAX 30<br />

In addition, the set values for the desired hot water temperature (DVA) and the mixing difference<br />

(DVD) is put down in the parameter menu to provide the user with quick access.<br />

For more detailed data related to speed process and stability see: Pump speed control<br />

PDR.<br />