Loading pump control - program 4<br />
The loading pump runs when S1 has exceeded the threshold min, the temperature of S1<br />
is diff higher than S2, and S2 has not yet crossed the threshold max.<br />
Program 5<br />
6<br />
The loading pump function has an additional storage limiter max2 via sensor S3.<br />
Program 6<br />
The loading pump function has an additional threshold min2 via sensor S3 and temperature<br />
difference diff2 between S3 and S2. Hence, the system can be switched off via two<br />
energy generators (S1 and/or S3).<br />
Air flap control for an earth collector - program 8<br />
The output switches when S1 < max or > min. An air/water heat pump thus has a flap for<br />
the airflow from the earth collector above the outside ambient temperature min (regeneration)<br />
and below the outside ambient temperature max (heating). S2 and S3 have no function.<br />
Program 9<br />
The output switches when S1 > max or < min. Hence, while program 8 switches above<br />
and below a temperature window, program 9 switches within a temperature window.