Loading pump control - program 4<br />

The loading pump runs when S1 has exceeded the threshold min, the temperature of S1<br />

is diff higher than S2, and S2 has not yet crossed the threshold max.<br />

Program 5<br />

6<br />

The loading pump function has an additional storage limiter max2 via sensor S3.<br />

Program 6<br />

The loading pump function has an additional threshold min2 via sensor S3 and temperature<br />

difference diff2 between S3 and S2. Hence, the system can be switched off via two<br />

energy generators (S1 and/or S3).<br />

Air flap control for an earth collector - program 8<br />

The output switches when S1 < max or > min. An air/water heat pump thus has a flap for<br />

the airflow from the earth collector above the outside ambient temperature min (regeneration)<br />

and below the outside ambient temperature max (heating). S2 and S3 have no function.<br />

Program 9<br />

The output switches when S1 > max or < min. Hence, while program 8 switches above<br />

and below a temperature window, program 9 switches within a temperature window.