Function check F CHCK:<br />

Some countries only offer subsidies for the installation of solar thermal systems if the control<br />

units have a function check to detect a sensor defect and a lack of circulation. In the<br />

menu command F CHCK, the mechanic can activate this function check for the ESR21. This<br />

function check is disabled ex works.<br />

ON/OFF<br />

FC OFF: The function check is not active.<br />

FC ON: The function check is active. Monitoring makes most sense in solar thermal systems.<br />

The following system statuses and sensors are monitored:<br />

� An interruption or short circuit of sensors 1 or 2.<br />

� Circulation problems - an error message is issued if the output is active and the differential<br />

temperature between collector S1 and tank S2 is greater than 60K for more than 30<br />

minutes.<br />

The error messages are entered in the menu Stat. If Stat is blinking, a malfunction or special<br />

system status has been detected (see “The status display Stat”).<br />