Pump standstill<br />

The wave packet method (standard) allows for variations in the volume flow by a factor of<br />

10 in 30 increments. If the flow rate is too low, flap valves may cause a system standstill. In<br />

addition, low power stages at low speeds may cause the rotors to stop. Such a standstill may<br />

sometimes be desired, which is why stage 0 is allowed as the lowest stage. The following<br />

parameters determine the lower and upper limit for speeds:<br />

MIN Lower speed limit (ex works = 0)<br />

MAX Upper speed limit (ex works = 30)<br />

The best speed limit is found in a simple test. Use the command TST to set a speed for<br />

testing. Remove the rotor lid to see the rotor. Then lower the speed until the rotor stops. Set<br />

the limit three increments above this point to ensure safe pumping.<br />

Control commands<br />

The following commands provide a test of the system (see pump standstill) and allow you<br />

to monitor the current speed (see stability problems):<br />

ACT 19 The pump is currently running at stage 19 (actual value).<br />

TST 14 The speed stage 14 is currently being tested. Calling TST automatically switches<br />

to manual mode. As soon as the value blinks via the key � (= entry), the pump<br />

runs at the speed displayed.<br />

Setting range: 0 to 30<br />