Absolute value control = maintaining a sensor<br />

S1 can be kept at one temperature (such as 60°C) very well by using the speed control. If<br />

the solar radiation is reduced, S1 becomes colder. The control unit then lowers the speed<br />

and hence the flow rate. However, that causes the warm-up time of the heat transfer medium<br />

in the collector to increase, thus increasing S1 again.<br />

A constant return (S2) may make sense as an alternative in various systems (such as<br />

boiler feeds). Inverse control characteristics are necessary for this. If S2 increases, the heat<br />

exchanger does not provide enough energy to the tank. The flow rate will then be reduced.<br />

The longer dwell time in the exchanger cools the heat transfer medium more, thus reducing<br />

S2. It does not make sense to keep S3 constant as the variation in the flow rate does not<br />

directly affect S3; hence, no regulator circuit will result.<br />

The absolute control is set via two parameter windows. The example has typical settings<br />

for the hydraulics:<br />

AC N 1 Absolute value control in normal operation, with sensor S1 being kept constant.<br />

Normal operation N means that the speed increases as temperatures do and is<br />

valid for all applications to keep a “feed sensor” constant (collector, boiler, etc.)<br />

Inverse operation I means that the speed decreases as temperatures drop and<br />

is necessary to maintain a return or control the temperature of a heat exchange<br />

outlet via a primary circulating pump (such as hygienic hot water). If the temperature<br />

at the heat exchanger’s outlet is too high, too much energy yield enters<br />

the heat exchanger, thus reducing the speed and hence the input. (ex<br />

works = --)<br />

Setting range: AC N 1 to AC N 3, AC I 1 to AC I 3<br />

AC -- = absolute value control is disabled.<br />

DVA 60 The desired value for absolute value control is 60°C. In the example, S1 is<br />

thus kept at 60°C. (ex works = 0°C)<br />

Setting range: 0 to 99°C in increments of 1°C<br />

Differential control = keeps the temperature constant between two sensors.<br />

Keeping the temperature difference constant between S1 and S2, for instance, allow for<br />

“shifting” operation of the collector. If S1 drops due to lower irradiation, the difference between<br />

S1 and S2 thus drops. The control unit then lowers the speed, which increases the<br />

dwell time of the medium in the collector and hence the difference between S1 and S2.<br />