Searle MSP- INV: M&S Inverter Packs Part Number 272-000-294 iss3 September 2007

<strong>Searle</strong> <strong>MSP</strong>- <strong>INV</strong>: M&S <strong>Inverter</strong> <strong>Packs</strong><br />

Part Number 272-000-294 iss3 September 2007


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 0. Index<br />

Issue 3 Page - 2 -<br />

September 2007<br />

<strong>MSP</strong>-<strong>INV</strong>, <strong>MSP</strong>L-<strong>INV</strong> & MSHP <strong>Inverter</strong> Pack Sets INDEX<br />

Sheet No’s Issue No<br />

1 Health & Safety 3 1<br />

2 Installations and Commissioning 4 � 12 1<br />

3 Operating Limits 13 1<br />

4 Maintenance Instructions 14 �21 1<br />

5 Guarantee 22 1<br />

6 Wiring Diagrams 23 � 56 1<br />

7 Controls Logic & Settings 57 � 70 1<br />

8 Layout Diagrams 71 � 81 1<br />

9 Spares Lists 82 � 86 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 1. Health & Safety<br />

Issue 3 Page - 3 -<br />

September 2007<br />

1. Health & Safety<br />

This concerns the hazards that may be encountered when installing and maintaining<br />

this equipment. It is therefore important that these instructions are followed.<br />

All Electrical connections to the unit should be made in accordance with IEE regulations,<br />

16 th Edition, with further attention to applicable local by-laws.<br />

All work must be undertaken by trained personnel only.<br />

Before installation<br />

Ensure that the voltage, working fluid and the maximum working pressure stated on the product<br />

nameplate is suitable for the working environment.<br />

Ensure that the proposed method of mounting is adequate to support the total operational weight of the<br />

unit.<br />

During installation and maintenance<br />

Ensure that:<br />

1. the unit is installed and maintained by qualified personnel only.<br />

2. the electrical supply is isolated and secured from accidental reconnection.<br />

3. the working area is adequately ventilated.<br />

4. the temperature of coils with vinyl coated fins does not exceed 150°C (e.g. during brazing) as toxic<br />

fumes would be produced.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 4 -<br />

September 2007<br />

2. Installation and Commissioning INDEX<br />

Page No’s Issue No<br />

2.1 Before Installation 5 1<br />

2.2 Handling & Lifting 6 1<br />

2.3 Installation and Location Guidance 6 1<br />

2.4 Floor / Roof Mounting 6 1<br />

2.5 Pack Assembly 7 1<br />

2.6 Pipework & Brazing 8 1<br />

2.7 Pressure Testing 8 1<br />

2.8 Electrical 9 1<br />

2.9 Evacuation 10 1<br />

2.9.1 Holding Charge 10 1<br />

2.9.2 Open shut off valves 10 1<br />

2.9.3 Compressor crank case heaters 10 1<br />

2.9.4 Evacuation 10 1<br />

2.10 Refrigerant Charging 11 1<br />

2.11 Oil Recovery and Oil Charging 11 1<br />

2.12 Compressor Mounting Feet adjustment 11 1<br />

2.13 Initial Starting / Running 12 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 5 -<br />

September 2007<br />

2.1 Before Installation<br />

Upon receipt and prior to installation of the unit a Post Delivery Inspection should be carried out, with<br />

any discrepancies being reported to the supplier within 7 days.<br />

The unit should be checked for damage and that all loose items have been supplied.<br />

Loose Items Supplied :<br />

Electrical Box Key x 1<br />

Oil separator Spare Element x 1<br />

Polyolester oil, 3.8L x 1<br />

(Loose or pre-charged in separator)<br />

Anti-Vibration Mounting feet x4 (x8 for Split Pack)<br />

Discharge & Suction PRV’s fitted<br />

Unit free from Damage<br />

Comments :<br />

When Shipped Upon Delivery<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 6 -<br />

September 2007<br />

2.2 Handling & Lifting<br />

Lifting lugs in the unit base frame(s) are provided, and it is essential when lifting that stage spreader<br />

bars be used to prevent damage to the unit. When handling the unit into position, it should be kept as<br />

low as possible and should not be tilted more than 30 degrees to the horizontal.<br />

2.3 Installation and Location Guidance<br />

Consideration should be given to pipework associated with the installation, which can become an<br />

obstruction to service and maintenance of the unit.<br />

Consideration should also be given to servicing requirements - there should be adequate space of at<br />

least 1 metre clearance on all access doors and panels.<br />

2.4 Floor / Roof Mounting<br />

The main base frame of the unit must be secured to the intended supporting surface using the antivibration<br />

mounts provided.<br />

Any supporting surface must be rated to support the total operational weight of the unit, including the<br />

additional refrigerant charge and any other equipment that has been added, i.e. pipework, cabling etc.<br />

If the unit is mounted directly to the roof it is recommended that isolation material be used between the<br />

unit frame and the roof itself.<br />

Dry weights of the Split units are :<br />

<strong>MSP</strong>L050-<strong>INV</strong> (Split) = 746 kg<br />

<strong>MSP</strong>L060-<strong>INV</strong> (Split) = 834 kg<br />

<strong>MSP</strong>L080-<strong>INV</strong> (Split) = 871 kg<br />

<strong>MSP</strong>L100-<strong>INV</strong> (Split) = 923 kg<br />

Dry weights of the 1 Piece units are :<br />

<strong>MSP</strong>050-<strong>INV</strong> = 676 kg<br />

<strong>MSP</strong>060-<strong>INV</strong> = 764 kg<br />

<strong>MSP</strong>080-<strong>INV</strong> = 801 kg<br />

<strong>MSP</strong>100-<strong>INV</strong> = 853 kg<br />

Dry weights of the Housed units are :<br />

MSHP050-<strong>INV</strong> = 1923 kg<br />

MSHP060-<strong>INV</strong> = 2011 kg<br />

MSHP080-<strong>INV</strong> = 2048 kg<br />

MSHP100-<strong>INV</strong> = 2100 kg<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 7 -<br />

September 2007<br />

2.5 Pack Assembly (Applies to Split <strong>Packs</strong> only, <strong>MSP</strong>L-<strong>INV</strong>)<br />

The pack is supplied in 2 halves to allow for location and transportation via a standard goods lift.<br />

The unit should be handled with care, avoiding any strain or damage to components whilst being<br />

maneuvered. Do not use any pipework or component fittings to maneuver the unit, use the main<br />

steel frame only.<br />

2<br />

Assemble the two halves of the pack together as follows :-<br />

1. Butt up the two halves of the pack together and mark off the pipework connections for the<br />

Suction and the Discharge interconnection pieces.<br />

2. Remove the pipe clamps at the ends of the headers ready for cutting back.<br />

3. Ensure the holding charge is released carefully, then cut back the 4 connections<br />

4. Ease the halves apart and loosely fit the interconnection pieces to the suction and discharge.<br />

5. Butt the two halves together again, and securely fit the front and back fishplates, using all fixing<br />

positions.<br />

6. Carefully braze the interconnection pieces, at all 4 joints.<br />

7. Unreel the oil return hoses on the LH section, and fit them to the compressor traxoil inlets on<br />

compressors 2, 3 and 4.<br />

8. Pressure test and leak test the assembly and all joints made.<br />

9. Fully evacuate the assembly as described in section 2.10 page 11.<br />

10. Open the compressor control cabinets and remove the front trunking covers.<br />

11. Unreel compressor number 2, 3 and 4’s 10mm2 power cables and feed them through the<br />

trunking, and into the LH control assembly.<br />

12. Securely connect the compressor power cables to the appropriate stud terminal, ensuring all<br />

phasing is correct and in the right rotation.<br />

13. Unreel the compressor 1 cable loom, and fit via the glanding entry point on the RH control box.<br />

14. Plug up the compressor 1 cable loom into the RH control box connections, ensuring all<br />

connections are made ok.<br />

15. Mark off and drill all the mounting feet into the supporting floor, securing with suitable fixings.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 8 -<br />

September 2007<br />

2.6 Pipework & Brazing<br />

Pipework to and from the unit should be selected to suit the application and not the connection size of<br />

the unit. Pipework sizes should be selected to ensure pressure drop does not exceed an equivalent of 2K<br />

at full load conditions.<br />

Pipework must be designed to ensure good oil return, especially during low load conditions.<br />

Pipework should be supported independently from the condensing unit in a way that prevents the<br />

transmission of vibration to the units.<br />

A competent engineer should install the refrigerant pipework to a high standard of refrigeration<br />

practice. All pipework used must be clean and to refrigeration quality, all cuts should be made using a<br />

pipe cutter, never a hacksaw, and care must be taken to remove all burrs and swarf.<br />

Braze using silver bearing brazing rod and ensure that all joints are cleaned before brazing.<br />

During brazing care should be taken to ensure that all components near joints should not be excessively<br />

overheated, a wet cloth should be applied where necessary. Dry nitrogen should be passed through the<br />

pipework during brazing to minimise oxidisation.<br />

During brazing ensure the temperature of coils with vinyl coated fins does not exceed 150°C<br />

as toxic fumes would be produced.<br />

The Suction inlet and Discharge outlet connection stubs are located towards the rear of the, the suction<br />

stub is 2 5/8”, the Discharge stub is 1 5/8”, ensure the holding charge has been safely released and cut<br />

back the stubs and prepare the connections as required to match the system pipework, and braze<br />

accordingly.<br />

When brazing and leak testing are complete the suction line should be insulated with 3/4" thick Class ‘O’<br />

insulation.<br />

2.7 Pressure Testing<br />

The unit has been thoroughly pressure tested during manufacture however after on site brazing is<br />

complete all pipework should be pressure tested for leaks.<br />

When pressure testing it is imperative that low and high side components are not over pressurised.<br />

Low side components must not be subjected to any pressure greater than 12.6 Barg, high side<br />

components must not be subjected to any pressure greater than 22.5 Barg.<br />

Failure to adhere to these pressures will activate the safety bursting discs and relief valves, requiring<br />

replacement.<br />

During pressure testing the main Manual Reset High pressure switches may trip, ensure all switches are<br />

reset, if required, after pressure testing.<br />

Pressure testing must be by a currently recognised method.<br />

Pressure testing using refrigerant must never be undertaken.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 9 -<br />

September 2007<br />

2.8 Electrical<br />

NOTE : All Electrical connections to the unit should be made in accordance with IEE<br />

regulations, 16 th Edition, with further attention to applicable local by-laws.<br />

The units have been designed to accept multiple incoming 63A feeds, or with a single sub-main<br />

supply with the Busbars, fitted to the unit.<br />

IMPORTANT : If Separate incoming feeds are used the Busbars MUST BE REMOVED,<br />

before wiring commences.<br />

For a multiple supply 5 separate feeds are required as follows :<br />

3 x TP&N for Compressor’s<br />

1 x SP&N for Controls<br />

1 x SP&N for RCD Socket, Lighting and Housing Evaporator.<br />

All cabling should be of the correct rating and type, also adhering to M&S specifications.<br />

Incoming connections should be made via the Main’s Incoming compartment situated on the far left of<br />

the pack control panel. Cables should be routed through the bottom Glanding plate as shown in Fig. 2.<br />

Cables should also be glanded or restrained to the glanding plate incorporated in the base of the mains<br />

incoming termination panel.<br />

Fig 2<br />

The glanding plates may be removed for ease<br />

of working.<br />

Note : the glanding plates are not rated<br />

to support weight of the incoming<br />

supply cables, which must be supported<br />

independently from the unit.<br />

Incoming supplies should be connected to the<br />

post terminals ensuring correct phase rotation<br />

in all cases.<br />

All incoming supplies should be properly<br />

identified with special care being taken to<br />

prevent any cross phasing between supplies.<br />

IMPORTANT :<br />

The supply to the RCD Socket MUST be<br />

disconnected before any High Voltage<br />

Insulation tests are carried out. Failure<br />

to so will irrevocably damage the RCD<br />

Socket.<br />

See wiring diagram on page 39 for further<br />

details.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 10 -<br />

September 2007<br />

2.9 EVACUATION<br />

2.9.1 Holding Charge : The unit has been leak tested, dehydrated and filled with a holding charge of<br />

‘dry air’ during manufacture. The holding charge should be released to atmosphere in a controlled<br />

manner via the suction stub, liquid stub, and receiver service ports, not into the housing<br />

compartment. Any valve opened to atmosphere must be closed after releasing the holding<br />

charge.<br />

2.9.2 Ensure that all system shut off valves are open as follows :<br />

1. 2 5/8” Suction Ball Valve, under control panel, open.<br />

2. Compressor Suction Service valves (Back seated with sealing cap on), on rear or top of<br />

compressors.<br />

3. Compressor Discharge Service valves (Back seated with sealing cap on) on top of compressors.<br />

4. Compressor Oil return line shut off valves (Back seated with sealing cap on), on top of oil return<br />

header x4.<br />

5. All Valves in the condensing circuit installation.<br />

6. Receiver service valves, (Back seated with sealing cap on).<br />

7. Liquid filter bypass arrangement, top valve open, centre valve shut, bottom valve open. The<br />

refrigerant flow must go through the drier.<br />

8. Solenoid valves on the oil level floats and compartment cooler should be opened with manual solenoid<br />

valve operating magnets.<br />

Warning : Never energise any Solenoid coil when not fitted to its solenoid stem.<br />

2.9.3 Compressor crank case heaters should be on during evacuation as follows :<br />

1. Turn off all Isolators on the electrical cabinet compartment doors.<br />

2. Open each compressor compartment door.<br />

3. Switch all Compressor Overloads to the Off or ‘0’ position.<br />

4. Switch MCB’s 1CB1, 2CB1, and 3CB1 to the on position<br />

5. Switch all other MCB’s to the off position.<br />

6. Close all electrical compartment doors.<br />

7. Turn on Compressor 1, 2, and 3 isolators ONLY, do not turn on the common controls or Condenser<br />

compartment isolators. The crank case heaters will now be energised.<br />

2.9.4 The entire system should be evacuated prior to charging as follows:<br />

Connect vacuum pump to the 1/4” flare connections on the suction and discharge service valves of<br />

compressor 1 and 2, and if possible the receiver service valves. Ensure each service valve is mid seated,<br />

the valve spindles should be screwed in a few turns from the back seated position to open the ports, and<br />

the sealing caps replaced.<br />

Evacuate the system to below 225 microns (0.3 mbar). The pump should be isolated and the system<br />

pressure monitored. A rapid continuous rise could indicate a leak in the system.<br />

Warning : DO NOT Start or Insulation Test the Compressors under Vacuum.<br />

After evacuation all Solenoid coils MUST be replaced on their solenoid stems.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 11 -<br />

September 2007<br />

2.10 Refrigerant Charging<br />

The unit should be charged with the specified refrigerant R404A until the sight glass is just clear at the<br />

normal operating condition. R404A refrigerant must be charged as a Liquid, and never as a gas.<br />

Charge the unit whilst under vacuum with liquid refrigerant via the access valve on top of the liquid<br />

filter drier. Additional charge should be added at the evaporator distributor or immediately after<br />

the expansion valve.<br />

Liquid charging direct to the suction line is not permitted under any circumstances.<br />

If after charging the unit is left with the power supply turned off, the compressor crankcase heaters<br />

should be switched on for a minimum of 3 hours before the unit is started. This will ensure that the<br />

compressor sumps are free from liquid refrigerant, see section 2.10.3 p12 for further info.<br />

Warning : DO NOT allow Compressors to Short Cycle under low pressure whilst Charging.<br />

2.11 Oil Recovery and Oil Charging<br />

The unit is fitted with a High Pressure oil management system, which must be charged to its final oil<br />

level during initial system operation. The oil separator incorporates an oil reservoir, which is pre-charged<br />

with Polyolester oil, each compressor is also pre-charged with Polyolester oil.<br />

If the unit is installed into a new installation some oil will be lost into the system pipework.<br />

If the unit is installed into an existing installation oil may return to the separator from the rest of the<br />

system due to the increased efficiency of the separator.<br />

For a new installation add oil to maintain a level in the upper sight glass of the reservoir.<br />

For an existing installation maintain an oil level in the lower sight glass of the reservoir.<br />

After two days of system operation the oil level should be checked, and if required add or remove oil to<br />

maintain a level in the upper sight glass of the reservoir for new and existing installations.<br />

Add oil into the service connection on the shut off valve at the base of the separator/reservoir, ensure<br />

the valve is back seated before removing the flare cap. Only suitable Polyolester oil, such as Bitzer BSE<br />

32, or equivalent should be used. During normal operation each oil management float should show a<br />

level between ½ and ¾ full sight glass.<br />

2.12 Compressor Mounting Feet<br />

All compressor mounting feet fixings should be checked to ensure they are<br />

fully tightened, and re-tightened if necessary.<br />

Check the fittings on the top of each compressor foot (1), the fitting (2)<br />

should be firmly screwed on to the centre studding, and not be able to be<br />

moved. See Fig 3.<br />

Fig. 3.<br />

SOLID<br />

MOUNT<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1<br />

2<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 2. Installation & Commissioning<br />

Issue 3 Page - 12 -<br />

September 2007<br />

2.13 Initial Starting / Running<br />

Before operating the unit for the first time, check that components, motors, compressors, mountings and<br />

electrical covers are secure.<br />

When the unit has been installed, the relevant oil and refrigerant charges have been added, and the<br />

correct controller settings entered it may be set in to normal operation as follows :<br />

1. Ensure all shut off valves are open, (suction line, liquid line, condenser inlet valves, receiver inlet<br />

and outlet valves, compartment cooler liquid and suction (MSHP only), and compressor discharge,<br />

suction and oil return shut off valves).<br />

2. Ensure the liquid filter drier bypass valve is closed and the refrigerant directed to pass through the<br />

filter drier.<br />

3. Ensure all solenoid-operating coils removed during evacuation have been replaced.<br />

4. Turn off all electrical compartment isolators.<br />

5. Open all compartments and ensure all MCB’s and Overloads are switched on or in the ‘1’ position.<br />

Close all Compartment doors but leave isolators switched off.<br />

6. Turn on the main control panel isolator and condenser panel isolator (if fitted), leaving compressor<br />

isolators off.<br />

7. Allow the controller to initialise, the suction pressure will be shown on the display, the discharge<br />

pressure can be monitored on the backup millennium controller inside the common controls panel.<br />

8. Turn on the isolator for compressor 1, and energise the evaporator liquid line solenoids. After the<br />

compressor on delay the first stage will start under inverter control, increasing from low speed. Ensure<br />

correct compressor operation.<br />

9. Repeat step 7 one stage at a time until all compressors are running. If all compressors will not run at<br />

the desired suction setting ensure all evaporators are running and that the system is adequately<br />

charged. Ambient temperature conditions may also affect the number of stages required.<br />

10. Check that the remote condenser fans operate and rotate in the correct direction. The airflow<br />

direction is commonly across the motor and out through the fan guard.<br />

11. Allow the unit to operate as normal for 48 hours and then carry out the 48 hours operation after<br />

Initial Start-up Maintenance, as described in section 4.0.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 3. Operating Limits<br />

3. Operating Limits<br />

The <strong>MSP</strong>-<strong>INV</strong> pack is designed for Medium<br />

temperature applications, and its operation<br />

must stay within the application envelope<br />

shown in fig 4.<br />

<strong>MSP</strong>100 and 080-<strong>INV</strong> compressor stages 2 & 3<br />

can operate in the Blue area, compressor stage<br />

1 may safely operate in the Blue and Red areas.<br />

<strong>MSP</strong>060-<strong>INV</strong> and 050-<strong>INV</strong> Compressor stages 2<br />

and 3 can operate in the Blue area, compressor<br />

stage 1 may safely operate in the Blue and Red<br />

areas.<br />

It is important that the Main controller and<br />

Protection/Control pressure switches are not set<br />

outside of the application envelope, otherwise<br />

compressor malfunction may occur.<br />

Failure to observe these limits will void the<br />

compressor warranty.<br />

Condensing Temperature °C<br />

Issue 3 Page - 13 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

60<br />

50<br />

40<br />

30<br />

20<br />

-50 -40 -30 -20 -10 -0 +10<br />

Saturated Suction Temperature [°C]<br />

All Compressor Stages<br />

For R404A the Pressure vs. Temperature relationship is as shown (Fig 5).<br />

R404A<br />

0.5<br />

1<br />

1.5<br />

2<br />

3<br />

4<br />

5<br />

°C<br />

6 7 8 9 10<br />

<strong>MSP</strong>100 & 080 - Comp Stage 1 only<br />

<strong>MSP</strong>050 & 060 - Comp Stages 1 & 2 only<br />

-35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70<br />

BarG<br />

Multiple Evaporator Applications<br />

Where one unit is connected to multiple evaporators, operated independently from one another, it is vital<br />

that the minimum saturated suction temperature remains within the operating envelope when the unit is<br />

operating in low load conditions.<br />

Staging of Compressors<br />

The sequence controller incorporates a maximum number of starts for each compressor stage. This is<br />

factory set to 10 starts per hour for all compressors and must not be raised.<br />

Should plant pressures change rapidly during operation the controller will react accordingly starting and<br />

stopping compressors as required.<br />

Number of starts per hour higher than those above will reduce plant stability, increase power<br />

consumption and lead to reduced component life and possible failure.<br />

Failure to observe these limits will void the compressor warranty.<br />

15<br />

20<br />

25<br />

30<br />

35<br />

Fig 5.<br />

Fig 4.<br />

3


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 14 -<br />

September 2007<br />

4. Maintenance INDEX<br />

Page No’s Issue No<br />

4.1 48 hours operation after Initial Start-up 15 1<br />

4.1.1 Oil Separator Element 15 1<br />

4.1.2 Suction filter elements 15 1<br />

4.1.3 Oil Separator Level 16 1<br />

4.1.4 Liquid Filter Drier / Wetech Indicator 16 1<br />

4.2 Every 3-6 months 17 1<br />

4.3 Every 12 months 17 1<br />

4.4 Suction filters & Compressor Burn out 19 1<br />

4.5 When Necessary 19 1<br />

4.5.1 Changing of Pressure Switches / Transducers 19 1<br />

4.5.2 Replacement of a Compressor 20-21 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

4


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 15 -<br />

September 2007<br />

WARNING! The Unit must be Electrically Isolated before Maintenance Work is undertaken<br />

The following routine maintenance is required:<br />

4.1 48 hours operation after Initial Start-up<br />

4.1.1 Oil Separator Element<br />

The oil separator filter element should be changed for the spare filter supplied, as follows :<br />

1. Turn off all Compressor Isolators, 1, 2, and 3, and the Condenser panel Isolator (If fitted).<br />

2. Front seat all compressor discharge valves.<br />

Warning : DO NOT operate any compressor with the Discharge valve shut or blocked.<br />

3. Front seat the separator’s oil return valve.<br />

4. Close the discharge outlet stub’s ball valve.<br />

5. Connect a reclaim/recovery unit from the schraeder on the separator outlet pipe to the Suction<br />

schraeder, and recover any residual gas in the separator.<br />

6. Disconnect the reclaim unit.<br />

7. Undo the 10 bolts on the top of the separator, and remove the separator lid.<br />

4<br />

8. Undo the bolt on the top of the separator element and remove the used element.<br />

9. Install the new separator element ensuring the ‘O’ ring is in place, and replace the securing nut.<br />

10. Replace the separator lid and bolts, and ensure all bolts are tightened.<br />

11. Connect a vacuum pump to the schraeder connection on the separator outlet, and run pump to<br />

remove any air from the separator.<br />

12. Back seat all compressor discharge valves.<br />

13. Open the condenser isolation valve.<br />

Warning : Check all compressor discharge valves are open before proceeding<br />

14. Turn on the Condenser panel isolator (if fitted), and all Compressor panel isolators.<br />

15. Leak test the separator lid.<br />

4.1.2 Suction filter elements<br />

The suction line filter elements should be removed as follows :<br />

1. Turn off all Compressor Isolators, 1, 2 and 3.<br />

2. Front seat all compressor suction valves.<br />

3. Close the pack suction inlet ball valve.<br />

4. Connect a reclaim/recovery unit from the Suction schraeder after the filter to the Liquid line<br />

schraeder, and recover any residual gas in the suction filter and header. Disconnect the reclaim unit.<br />

5. Remove the insulation cover on the end of the filter shell.<br />

6. Undo the central bolt 1 turn on the filter cap, rotate the cap and remove.<br />

7. Remove the filter cage and store safely within the unit for future use. Permanent use of suction line<br />

filters is not recommended due to increased pressure drop and risk of break up after long periods of<br />

operation.<br />

8. Replace the cap and turn until the alignment marks meet, tighten the centre bolt until hand tight, then<br />

tighten one full turn with a spanner.<br />

9. Connect a vacuum pump to the Suction schraeder after the filter, and run to remove air in the filter.<br />

10. Back seat all compressor suction valves.<br />

11. Open the suction inlet ball valve.<br />

Warning : Check all compressor suction valves are open before proceeding<br />

12. Turn on all Compressor Isolators<br />

13. Leak check the suction filter cap connection, and replace the filter insulation cover.<br />

4.1.3 Oil Separator Level<br />

The separator reservoir oil level should be checked and oil added or removed to maintain a level in the<br />

upper sight glass, as described in section 2.12, page 13.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 16 -<br />

September 2007<br />

4.1.4 Liquid Filter Drier / KMC Wetech Moisture Indicator on Receiver Assembly / filter pack<br />

1. Changeover the liquid bypass valve arrangement, Top valve closed, Centre valve open, bottom valve<br />

closed, to divert the refrigerant around the filter drier, see fig 6.<br />

2. Connect a reclaim/recovery unit from the Drier service valve to the Suction schraeder, back seat the<br />

drier service valve and recover any residual gas in the separator. Front seat the drier service valve when<br />

complete.<br />

3. Undo the central bolt 1 turn on the filter cap, rotate the cap and remove<br />

4. Remove the core & cage assembly and unscrew the end.<br />

5. Open the new cores and re-assemble onto the cage.<br />

6. Insert the new core & cage into the drier shell, replacing the holding spring in front of the cage.<br />

7. Replace the cap and turn until the alignment marks meet, tighten the centre bolt until hand tight, then<br />

tighten one full turn.<br />

8. Connect a vacuum pump to the Drier service valve, and run to remove air in the filter. Front seat<br />

the drier service valve when complete, and replace it’s sealing cap.<br />

9. Changeover the liquid bypass valve arrangement, Top Valve open, Centre valve shut, bottom<br />

valve open, to restore the refrigerant flow through the filter.<br />

Warning : The bypass arrangement must not be used for long periods of time as<br />

contaminants and moisture will be allowed to pass through to the rest of the system.<br />

The relative moisture level of the system can be monitored via the KMC (Wetech) detection alarm light<br />

on the main control panel door.<br />

After commissioning the moisture level Alarm light should not illuminate. If the moisture level increases<br />

and the Alarm light illuminates action must be undertaken to reduce system moisture levels.<br />

Fig 6.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

4


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 17 -<br />

September 2007<br />

4.2 Every 3-6 months<br />

The remote condensers should be cleaned to ensure correct operation of the condensing unit. When the<br />

condenser coil is obstructed by dirt or rubbish, the unit will experience high condensing temperatures<br />

which will result in higher running costs, loss of compressor efficiency and ultimately overheating of the<br />

compressor and/or condenser fans.<br />

The pressure drop across all filters should be measured, if above 0.5 Bar the filter elements should be<br />

changed.<br />

The sight glass moisture indicator and Wetech monitor should also be checked, and appropriate action<br />

taken if moisture is shown to be present.<br />

Warning : Safety Goggles must be worn when<br />

inspecting or changing any pressure device.<br />

The pressure relief valves and burst discs should be<br />

inspected for any pressure release.<br />

All burst discs are fitted with indicator gauges, and will<br />

show system pressure if a release has occurred, see Fig 7.<br />

Suction PRV’s should be manually inspected for a release.<br />

Rupture Disc<br />

Intact, No Release<br />

(Needle at zero)<br />

Rupture Disc blown,<br />

Release has occurred<br />

(Needle in Red band)<br />

If a release has occurred or there is a requirement by the<br />

customer maintenance schedule the relief valves and burst discs should be changed.<br />

Main receiver and suction relief devices are connected via a changeover valve.<br />

The changeover valve should be ‘back’ seated to the side requiring maintenance, the burst disc and/or<br />

pressure relief valve can then be changed.<br />

Warning : Beware of any residual refrigerant charge when removing PRV’s and Burst Discs,<br />

Safety Goggles and Gloves must be worn.<br />

The pressure relief valve and burst disc on the liquid filter bypass arrangement should be changed in a<br />

similar fashion to the liquid filter cores, by first putting the liquid path into bypass, then reclaiming any<br />

refrigerant. See section 4.1.4, p18 for further details.<br />

A suitable thread sealant should be applied when fitting replacement equipment. Care must be taken<br />

when tightening the replacement parts, by always using two spanners in a ‘scissor’ motion on the correct<br />

area of the parts. Any replacement parts used must be of an equivalent specification and compliant with<br />

applicable EC Directives.<br />

Note : All PRV’s and Bursting Discs MUST be changed every 3 years , whether they have<br />

vented or not.<br />

4.3 Every 12 months<br />

Check security of fixings, especially fans, motor and compressor mountings.<br />

Check fan motors (fans should rotate freely).<br />

Check refrigerant pipeline for damage and leaks.<br />

Check tightness of all screwed components, including compressor service valves, component service<br />

valves, and all pressure switch connections and hoses.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Fig 7.<br />

4


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 18 -<br />

September 2007<br />

4.4 In the event of Compressor Burn out<br />

If suction line burn out filters are used they must not be left in the system indefinitely, as the pressure<br />

drop across the filter will impair the system performance.<br />

The oil separator element and liquid filter cores should also be replaced.<br />

4.5 When Necessary<br />

Additional maintenance in accordance with customer specifications may also be required.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 19 -<br />

September 2007<br />

4.5.2 Changing of Control Pressure Switches and Transducers<br />

Should any pressure switch or transducer require changing follow the procedures below.<br />

Main Dual HP/LP Pressure Switch<br />

1. Turn off all panel isolators including, common controls, condenser and all compressor panel isolators.<br />

Warning : Safety Goggles and Gloves must be worn whilst changing pressure switches.<br />

Ensure the electrical supply to the component is isolated before commencing. Do not allow<br />

any compressor or the condenser to operate when any control switch is removed.<br />

2. The Dual pressure switch hoses are fitted to a schraeder connection on the pipework end only.<br />

Remove the relevant 1/4" connection from this end first, using two spanners in a ‘scissor’ motion, one on<br />

the schraeder fitting and one on the 1/4" connection.<br />

Warning : Do not disconnect the pressure hose at the switch end first, as this will vent<br />

refrigerant.<br />

3. The dual pressure switch may now be removed, and the hose connections at the switch end<br />

disconnected using 2 spanners in a ‘scissor’ motion.<br />

4<br />

4. Fit and wire in the Dual new pressure switch, ensuring the wiring is correct,<br />

see wiring diagrams on pages 23 and onwards for further details.<br />

5. Oil the cone fittings of the pressure hoses.<br />

6. Reconnect the pressure hose connections at the pressure switch end first using 2 spanners in a<br />

‘scissor’ motion.<br />

7. Reconnect the pressure hose connection at the pipework end, using 2 spanners in a scissor motion.<br />

This connection must be made rapidly to prevent loss of refrigerant.<br />

7. Open the 3/8” Liquid line and 1/2" Suction line shut off valves.<br />

8. Leak test the connection to the replaced switch.<br />

9. Ensure all wiring work undertaken is correct.<br />

10. Turn on all compressor isolators and condenser isolators to return the unit to normal operation.<br />

Compressor Pressure Switches & Transducers<br />

1. Turn off the relevant panel isolators, common controls, condenser and/or compressor panel isolators.<br />

Warning : Safety Goggles and Gloves must be worn whilst changing pressure switches.<br />

Ensure the electrical supply to the component is isolated before commencing. Do not allow<br />

any compressor or the condenser to operate when any control switch is removed.<br />

2. All pressure switches are fitted to a schraeder connection directly on the compressor body. Remove<br />

the relevant pressure switch 1/4" connection using two spanners in a ‘scissor’ motion, one on the<br />

schraeder fitting and one on the Hex part of the switch or transducer.<br />

All transducers are connected via a flexible pressure hose to a common HP or LP manifold.<br />

Unscrew the pressure hose at the manifold end first to isolate the line from the system, then unscrew<br />

the transducer from the 1/4" flare union.<br />

Note : When removing a pressure switch from the compressor body take care not to unscrew the 1/8”<br />

NPT to 1/4" flare adapter beneath the switch connection.<br />

3. Wire in the new pressure switch or transducer, ensuring the wiring is correct,<br />

see wiring diagrams on page 35 onwards for further details.<br />

Warning : Transducers will be irrevocably damaged if wired incorrectly.<br />

4. Oil the cone fittings of the replacement part.<br />

5. Reconnect the pressure switch or transducer to the correct schraeder connection using 2 spanners in<br />

a ‘scissor’ motion. For switches with fixed leads, rotate them 3 turns anticlockwise before fitting, so the<br />

wires are untangled when fitted.<br />

8. Leak test the connection to the replaced switch.<br />

9. Ensure all wiring work undertaken is correct.<br />

10. Turn on all compressor isolators and condenser isolators to return the unit to normal operation.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 20 -<br />

September 2007<br />

4.5.3 Replacement of a Compressor<br />

In the unlikely event that a compressor needs changing, the following procedure should be followed :<br />

Warning : Compressors are heavy, adequate provision must be made for their lifting<br />

without risk to personnel, manual lifting/handling should be avoided.<br />

Ensure the compressor electrical supply is isolated before commencing work.<br />

Any oil spillage must be cleaned up immediately.<br />

Before commencing work familiarise all personnel with the operating instructions supplied with the<br />

compressor, and read the relevant wiring diagrams. If in any doubt consult the equipment supplier via<br />

the approved escalation procedure.<br />

1. Turn off the relevant compressor isolator, and ensure it is secured from accidental re-connection.<br />

The rest of the unit may operate as normal<br />

2. Ensure the faulty compressor suction and discharge service valves are Back seated.<br />

4<br />

3. Connect a Recovery/Reclaim unit from the compressor suction and discharge service ports to the<br />

main suction header schraeder.<br />

4. Front seat the compressor suction and discharge service valves, and the relevant oil return hose<br />

shut off valve.<br />

5. Remove the Traxoil level regulator solenoid coil, and use a magnet to open the solenoid valve.<br />

6. Recover any residual refrigerant in the compressor.<br />

7. Ensure the electrical supply to the compressor is isolated, and open the compressor terminal box.<br />

8. Make note of the connections for future reference, also read the relevant wiring diagrams in section 6.<br />

9. Ensure the electrical supply to the compressor is isolated, and remove all electrical connections from<br />

the main junction box.<br />

10. Unscrew the plastic ‘Kopex’ conduit back nuts in the terminal box connecting to the main control<br />

panel and remove the Kopex and wiring. Leave other Kopex’s and wiring connected until the compressor<br />

is removed.<br />

11. Unscrew the compressor mounting feet top nuts.<br />

12. Unscrew the compressor Discharge and Suction valve rotalock connection, or remove the valve from<br />

the compressor body and ease the compressor pipework away ready for removal.<br />

13. Remove any Magnet fitted to the Traxoil regulator solenoid, and disconnect the oil return line from<br />

the Traxoil regulator’s inlet connection, sealing both connections to avoid oil spillage.<br />

14. Remove HP/LP pressure switches, and the oil pressure sensor if fitted.<br />

Note : Identify the switches before removal, ie. with tape or labels, to simplify replacement.<br />

14. Using a suitable lifting method, lift the compressor above its mounting feet and then out from the<br />

frame.<br />

15. Remove the compressor from the unit to a safe working area.<br />

16. Remove the remaining accessories from the compressor and replace onto the new compressor,<br />

ensuring all connections are made in an identical fashion.<br />

All taper thread connections should be made using a suitable thread sealant.<br />

Tip the compressor away from the oil connection before removing the Traxoil level regulator to minimise<br />

oil loss or spillage.<br />

Warning :<br />

The compressor is charged with Polyolester oil, DO NOT leave it open to atmosphere.<br />

17. Ensure the new compressor terminal box lid is fitted. Open up the required connection holes in the<br />

terminal box, it is recommended that a hole saw is used instead of a hammer to avoid damage to the<br />

box.<br />

18. Important : Re-use the mounting feet on the frame, if the replacement compressor is supplied with<br />

different mounting feet to the original’s DO NOT use the new parts. Observe the correct layout and<br />

usage of any components.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 4. Maintenance<br />

Issue 3 Page - 21 -<br />

September 2007<br />

19. Using a suitable lifting method, lift the compressor into the unit and onto the frame, ensure the<br />

mounting feet locate correctly.<br />

20. Fit and tighten the mounting feet fixings as shown in section 2.1 page 11.<br />

21. Replace any gaskets removed with new gaskets supplied with the compressor. Most gaskets do not<br />

need oiling, check with the compressor literature.<br />

22. Replace the pipework connections, and tighten to the correct torque, see compressor literature.<br />

23. Replace the oil return line to the Traxoil level regulator.<br />

24. Replace the compressor HP/LP pressure switches and oil pressure sensor if fitted.<br />

23. Re-fit the remaining Kopex’s to the terminal box, ensuring all gland back nuts are replaced.<br />

24. Re-wire all remaining connections to the terminal box, following the appropriate wiring diagrams.<br />

25. Check all wiring connections for continuity and check compressor earth bonding.<br />

26. Connect a vacuum pump to the compressor suction and discharge service valves, and run to draw a<br />

vacuum below 225 microns (0.3 mbar). The pump should be isolated and the pressure monitored. A<br />

rapid continuous rise could indicate a leak in the system.<br />

27. Isolate, and remove the vacuum pump.<br />

4<br />

28. When satisfied that all components and connections have been made correctly back seat the<br />

compressor suction and discharge valves.<br />

29. Turn on the compressor isolator and ensure it starts and runs correctly.<br />

30. Leak test all connections.<br />

Warning :<br />

If the removed compressor has ‘burnt-out’ an acid test must be performed on the<br />

refrigerant and oil. If the system is acidic appropriate action must be taken immediately to<br />

prevent further damage to components.<br />

The failed compressor must be sealed from atmosphere and if covered under warranty,<br />

returned to the supplier for warranty purposes. It is recommended that spare valves, sight<br />

glasses etc. from the new compressor be used to seal the faulty compressor, other methods<br />

may not ensure proper sealing.<br />

Leaving a compressor open to atmosphere will invalidate its warranty.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 5. Guarantee<br />

5. Guarantee<br />

The standard supplier guarantee covers the unit from date of delivery as follows :<br />

Compressors : 2 years<br />

All other components : 1 Year<br />

Issue 3 Page - 22 -<br />

September 2007<br />

Warranty matters should be resolved with the supplier as per the Standard Conditions of Sale.<br />

Failure to install, set up or put to work any part of the equipment in a manner specified in<br />

this manual could invalidate the guarantees set out in the <strong>Searle</strong> standard Terms and<br />

Conditions of Sale.<br />

Adjustment of settings outside Operating Limits in section 3 will invalidate warranty.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

5


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

Issue 3 Page - 23 -<br />

September 2007<br />

6. Wiring Diagrams<br />

Note : The wiring diagrams in this document cover all versions of the <strong>MSP</strong> packs, some drawings include extra details for the MSHP housed<br />

packs such as lights etc. or are different for the <strong>MSP</strong>L split pack, dedicated wiring diagrams are shown below where relevant.<br />

Ref Plant Details Drawing Description 050 060 080 100 Page<br />

1 <strong>MSP</strong>-050-670-<strong>INV</strong>.01.drg <strong>MSP</strong>050-<strong>INV</strong> : Plant Details x 24<br />

2 <strong>MSP</strong>-060-670-<strong>INV</strong>.01.drg <strong>MSP</strong>060-<strong>INV</strong> : Plant Details x 25<br />

3 <strong>MSP</strong>-080-670-<strong>INV</strong>.01.drg <strong>MSP</strong>080-<strong>INV</strong> : Plant Details x 26<br />

4 <strong>MSP</strong>-100-670-<strong>INV</strong>.01.drg <strong>MSP</strong>100-<strong>INV</strong> : Plant Details x 27<br />

Ref Main supply tails Drawing Description 050 060 080 100 Page<br />

5 <strong>MSP</strong>-050-600-<strong>INV</strong>.01.drg Main Supply Tails : <strong>MSP</strong>050/100-<strong>INV</strong> x x x x 28<br />

Ref Compressor Start Panels Schematics Drawing Description 050 060 080 100 Page<br />

6 <strong>MSP</strong>-050-611D-<strong>INV</strong>.01.drg Comp 1 SCH (<strong>INV</strong>) - <strong>MSP</strong>050-100-<strong>INV</strong> x x x x 29<br />

7 <strong>MSP</strong>-050-612D-<strong>INV</strong>.01.drg Comp 2 DOL Schematic - <strong>MSP</strong>050/060-<strong>INV</strong> x x 30<br />

8 <strong>MSP</strong>-050-613P-<strong>INV</strong>.01.drg Comp 3 PWS Schematic - <strong>MSP</strong>050/060-(<strong>INV</strong>) x x 31<br />

9 <strong>MSP</strong>-080-612P-<strong>INV</strong>.01.drg Comp2 PWS(OFF/L) - <strong>MSP</strong>080-<strong>INV</strong> x 32<br />

10 <strong>MSP</strong>-080-613P-<strong>INV</strong>.01.drg Comp 3 PWS Schematic - <strong>MSP</strong>080/100-(<strong>INV</strong>) x x 33<br />

11 <strong>MSP</strong>-100-612P-<strong>INV</strong>.01.drg Comp2 PWS(OFF/L) - <strong>MSP</strong>100-<strong>INV</strong> x 34<br />

Ref Common controls Schematics Drawing Description 050 060 080 100 Page<br />

13 <strong>MSP</strong>-050-631-<strong>INV</strong>.01.drg Common Ctrls Sht 1 - <strong>MSP</strong>50-<strong>INV</strong> (Standard) x x x x 35<br />

14 <strong>MSP</strong>-050-632-<strong>INV</strong>.01.drg Common Ctrls Sht 2 - <strong>MSP</strong>050-<strong>INV</strong> (Standard) x x x x 36<br />

15 <strong>MSP</strong>L-050-631-<strong>INV</strong>.01.drg Common Ctrls Sht 1– <strong>MSP</strong>L-050-<strong>INV</strong> (Split) x x x x 37<br />

16 <strong>MSP</strong>L-050-632-<strong>INV</strong>.01.drg Common Ctrls Sht 2– <strong>MSP</strong>L-050-<strong>INV</strong> (Split) x x x x 38<br />

17 MSHP-050-631-<strong>INV</strong>.01.drg Common Ctrls Sht 1– MSHP-050-<strong>INV</strong> (Housed) x x x x 39<br />

18 MSHP-050-632-<strong>INV</strong>.01.drg Common Ctrls Sht 2– MSHP-050-<strong>INV</strong> (Housed) x x x x 40<br />

Ref Compressor panels layouts Drawing Description 050 060 080 100 Page<br />

20<br />

21<br />

22<br />

<strong>MSP</strong>-050-621D-<strong>INV</strong>.01.drg<br />

<strong>MSP</strong>-050-622D-<strong>INV</strong>.01.drg<br />

<strong>MSP</strong>-050-623P-<strong>INV</strong>.01.drg<br />

Comp 1 DOL Layout: <strong>MSP</strong>050/080-<strong>INV</strong><br />

Comp 2 DOL Layout: <strong>MSP</strong>050-<strong>INV</strong><br />

Comp 3 PWS Layout: <strong>MSP</strong>050-<strong>INV</strong><br />

x<br />

x<br />

x<br />

x x 41<br />

6 42<br />

43<br />

23 <strong>MSP</strong>-060-622D-<strong>INV</strong>.01.drg Comp 2 DOL Layout: <strong>MSP</strong>060-<strong>INV</strong> x 44<br />

24 <strong>MSP</strong>-060-623P-<strong>INV</strong>.01.drg Comp 3 PWS Layout: <strong>MSP</strong>060/080-<strong>INV</strong> x x 45<br />

25 <strong>MSP</strong>-080-622P-<strong>INV</strong>.01.drg Comp 2 PWS Layout: <strong>MSP</strong>080-<strong>INV</strong> x 46<br />

26 <strong>MSP</strong>-100-621D-<strong>INV</strong>.01.drg Comp 1 DOL Layout: <strong>MSP</strong>-100-<strong>INV</strong> x 47<br />

27 <strong>MSP</strong>-100-622P-<strong>INV</strong>.01.drg Comp 2 PWS Layout: <strong>MSP</strong>100-<strong>INV</strong> x 48<br />

28 <strong>MSP</strong>-100-623P-<strong>INV</strong>.01.drg Comp 3 PWS Layout: <strong>MSP</strong>100-<strong>INV</strong> x 49<br />

Ref Common Controls Layout Diagrams Drawing Description 050 060 080 100 Page<br />

29 <strong>MSP</strong>-050-634-<strong>INV</strong>.01.drg Common Ctrls Layout : <strong>MSP</strong>-<strong>INV</strong> (Standard) x x x x 50<br />

30 <strong>MSP</strong>L-050-634-<strong>INV</strong>.01.drg Common Ctrls Layout : <strong>MSP</strong>L-<strong>INV</strong> (Split) x x x x 51<br />

31 MSHP-080-363-<strong>INV</strong>.01.drg Common Ctrls Layout : MSHP080-<strong>INV</strong> (Housed) x x x x 52<br />

Ref Controller Settings Drawing Description 050 060 080 100 Page<br />

34 <strong>MSP</strong>-050-630-<strong>INV</strong>.01.drg RDM Pack & Condenser ctrl <strong>MSP</strong>050-<strong>INV</strong> x 53<br />

35 <strong>MSP</strong>-060-630-<strong>INV</strong>.01.drg RDM Pack & Condenser ctrl <strong>MSP</strong>060-<strong>INV</strong> x 54<br />

36 <strong>MSP</strong>-080-630-<strong>INV</strong>.01.drg RDM Pack & Condenser ctrl <strong>MSP</strong>080-<strong>INV</strong> x 55<br />

37 <strong>MSP</strong>-100-630-<strong>INV</strong>.01.drg RDM Pack & Condenser ctrl <strong>MSP</strong>100-<strong>INV</strong> x 56<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

<strong>MSP</strong>050-<strong>INV</strong> PLANT ELECTRICAL DETAILS<br />

MB2 RATING<br />

FLA STARTING MB1 RATING<br />

MODEL<br />

10 TO 16A<br />

DOL<br />

9.2A<br />

4FC-3.2Y<br />

COMPRESSOR 1<br />

10 TO 16A<br />

DOL<br />

10.7A<br />

4EC-4.2Y<br />

COMPRESSOR 2<br />

10 TO 16A<br />

10 TO 16A<br />

PWS<br />

21A<br />

4PCS-10.2Y<br />

COMPRESSOR 3<br />

TOTAL FLA 40.9A<br />

Issue 3 Page - 24 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>050-<strong>INV</strong><br />

01<br />

<strong>MSP</strong>050-<strong>INV</strong> : PLANT DETAILS<br />

<strong>MSP</strong>-050-670-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

29/06/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

NS<br />

NS<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

<strong>MSP</strong>060-<strong>INV</strong> PLANT ELECTRICAL DETAILS<br />

MB2 RATING<br />

FLA STARTING MB1 RATING<br />

MODEL<br />

10 TO 16A<br />

DOL<br />

10.7A<br />

4EC-4.2Y<br />

COMPRESSOR 1<br />

10 TO 16A<br />

DOL<br />

13.5A<br />

4DC-5.2Y<br />

COMPRESSOR 2<br />

10 TO 16A<br />

10 TO 16A<br />

PWS<br />

24A<br />

4NCS-12.2Y<br />

COMPRESSOR 3<br />

TOTAL FLA 48.2A<br />

Issue 3 Page - 25 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>060-<strong>INV</strong><br />

01<br />

<strong>MSP</strong>060-<strong>INV</strong> : PLANT DETAILS<br />

<strong>MSP</strong>-060-670-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

29/06/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

NS<br />

NS<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

<strong>MSP</strong>080-<strong>INV</strong> PLANT ELECTRICAL DETAILS<br />

MB2 RATING<br />

FLA STARTING MB1 RATING<br />

MODEL<br />

10 TO 16A<br />

DOL<br />

13.5A<br />

4DC-5.2Y<br />

COMPRESSOR 1<br />

10 TO 16A<br />

10 TO 16A<br />

PWS<br />

21A<br />

4PCS-10.2Y<br />

COMPRESSOR 2<br />

10 TO 16A<br />

10 TO 16A<br />

PWS<br />

27A<br />

4J-13.2Y<br />

COMPRESSOR 3<br />

TOTAL FLA 61.5A<br />

Issue 3 Page - 26 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>080-<strong>INV</strong><br />

01<br />

<strong>MSP</strong>080-<strong>INV</strong> : PLANT DETAILS<br />

<strong>MSP</strong>-080-670-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

29/06/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

NS<br />

NS<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

<strong>MSP</strong>100-<strong>INV</strong> PLANT ELECTRICAL DETAILS<br />

MB2 RATING<br />

FLA STARTING MB1 RATING<br />

MODEL<br />

16 TO 20A<br />

DOL<br />

15.9A<br />

4CC-6.2Y<br />

COMPRESSOR 1<br />

10 TO 16A<br />

10 TO 16A<br />

PWS<br />

27A<br />

4J-13.2Y<br />

COMPRESSOR 2<br />

16 TO 20A<br />

16 TO 20A<br />

PWS<br />

37A<br />

4G-20.2Y<br />

COMPRESSOR 3<br />

TOTAL FLA 79.9A<br />

Issue 3 Page - 27 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>100-<strong>INV</strong><br />

01<br />

<strong>MSP</strong>100-<strong>INV</strong> : PLANT DETAILS<br />

<strong>MSP</strong>-100-670-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

29/06/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

NS<br />

NS<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

COMPRESSOR 1<br />

1L1<br />

1L2<br />

1L3<br />

1N1<br />

1PE<br />

2L1<br />

2L2<br />

COMPRESSOR 2<br />

2L3<br />

2N1<br />

2PE<br />

3L1<br />

3L2<br />

COMPRESSOR 3<br />

3L3<br />

3N1<br />

3PE<br />

INCOMING SUPPLIES<br />

Issue 3 Page - 28 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

6L1<br />

6N1<br />

6PE<br />

COMMON CONTROLS<br />

7L1<br />

7N1<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

<strong>MSP</strong>-(050 to 100)-620-<strong>INV</strong><br />

MAIN SUPPLY TAILS: <strong>MSP</strong>050/100-<strong>INV</strong><br />

<strong>MSP</strong>-050-600-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

15/03/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

3 Core Screened<br />

696<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Tw/Pr<br />

Inv Cntls to Common Controls Sheet 2<br />

692<br />

Tw/Pr<br />

695<br />

102<br />

628<br />

100<br />

600<br />

112<br />

611<br />

ISOLATOR<br />

Aux<br />

101<br />

606<br />

101<br />

61<br />

13<br />

Brn<br />

Blk<br />

Grey<br />

11<br />

12<br />

1L1<br />

1L2<br />

13<br />

1L3<br />

1MS1/1<br />

61<br />

14<br />

Blu<br />

1N1<br />

101<br />

112<br />

1CB1<br />

4A<br />

1MS1<br />

5<br />

9<br />

101<br />

6<br />

1R1/1<br />

62<br />

1R2/1<br />

9<br />

1<br />

5<br />

10<br />

1R2/2<br />

3<br />

1R2/3<br />

190<br />

100<br />

Blu<br />

62<br />

11<br />

63<br />

3 Core Screened<br />

16<br />

15<br />

14<br />

108<br />

Issue 3 Page - 29 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Tw/Pr<br />

Tw/Pr<br />

102<br />

110<br />

109<br />

101<br />

13<br />

108<br />

1Pl2/Skt2 3<br />

1Pl2/Skt2 2<br />

1Pl2/Skt2 1<br />

1Pl1/Skt1 3<br />

1Pl1/Skt1 2<br />

1Pl1/Skt1 1<br />

1R2<br />

1R1<br />

190<br />

14<br />

R<br />

G G<br />

696<br />

692<br />

695<br />

100<br />

Scrn<br />

Clr<br />

Blk<br />

Red<br />

Blk<br />

Red<br />

TRIP<br />

1R1<br />

TRIP<br />

RELAY<br />

Blk<br />

Red<br />

RUN<br />

RELAY<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

18<br />

27<br />

12<br />

55<br />

53<br />

50<br />

05<br />

04<br />

69<br />

68<br />

Fault 0-5V Inv Run<br />

RS485<br />

Compressor<br />

Box<br />

Terminals<br />

106<br />

105<br />

104<br />

N<br />

<strong>Inverter</strong><br />

Connections<br />

1 2 3 4 5 7 8 9<br />

U V W<br />

L1 L2L3<br />

108<br />

Blk<br />

Brn<br />

Blu<br />

Blu<br />

Brn<br />

N<br />

63<br />

107<br />

Cabling 0.75mm & 1mm<br />

61-69 Brown 230V AC functions<br />

Blue Neutral<br />

100 White 24V 50Hz 0V<br />

101- 149 Violet 24V 50Hz<br />

190,196 Twisted Pair (Inv Control)<br />

192 Small 3 Core Screened<br />

N<br />

62<br />

R Mp 1 2 12 11 14 B1 B2<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

3~ M<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

COMPRESSOR<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMP 1 SCH (<strong>INV</strong>) - <strong>MSP</strong>050/100-<strong>INV</strong><br />

02 692 & 696 CORRECTED<br />

N/A 01/08/06<br />

<strong>MSP</strong>-050-611D-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

202<br />

629<br />

200<br />

600<br />

212<br />

612<br />

ISOLATOR<br />

Aux<br />

201<br />

607<br />

201<br />

71<br />

13<br />

Brn<br />

Blk<br />

Grey<br />

21<br />

22<br />

2L1<br />

2L2<br />

23<br />

2L3<br />

71<br />

14<br />

2MS1<br />

Blu<br />

2N1<br />

203<br />

201<br />

212<br />

2CB1<br />

4A<br />

2MS1<br />

201<br />

3<br />

201<br />

4<br />

13<br />

2R1/1<br />

72<br />

2R2/1<br />

3<br />

2<br />

4<br />

14<br />

2K1/2<br />

21<br />

2K1/1<br />

200<br />

203<br />

Blu<br />

72<br />

22<br />

208<br />

73<br />

Issue 3 Page - 30 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

211<br />

210<br />

208<br />

2Pl2/Skt2 3<br />

2Pl2/Skt2 2<br />

2Pl2/Skt2 1<br />

2Pl1/Skt1 7<br />

2Pl1/Skt1 6<br />

2Pl1/Skt1 5<br />

2K1<br />

202<br />

209<br />

201<br />

26<br />

25<br />

24<br />

2R2<br />

2K1<br />

2R1<br />

R<br />

G G<br />

200<br />

2Pl/Skt1 1-4<br />

CONTACTOR<br />

TRIP<br />

2R1<br />

TRIP<br />

RELAY<br />

26<br />

25<br />

24<br />

E<br />

RUN<br />

RELAY<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

Compressor<br />

Box<br />

Terminals<br />

206<br />

205<br />

204<br />

N<br />

1 2 3 4 5 7 8 9<br />

208<br />

207<br />

Blk<br />

Brn<br />

Blu<br />

Blu<br />

Brn<br />

N<br />

73<br />

Cabling 0.75mm & 1mm<br />

71-79 Brown 230V AC functions<br />

Blue Neutral<br />

200 White 24V 50Hz 0V<br />

201- 249 Violet 24V 50Hz<br />

N<br />

72<br />

R Mp 1 2 12 11 14 B1 B2<br />

3~ M<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

COMPRESSOR<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

COMP 2 DOL SCHEMATIC - <strong>MSP</strong>050/060-<strong>INV</strong><br />

<strong>MSP</strong>-050-612D-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

11/02/04 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

302<br />

630<br />

300<br />

600<br />

312<br />

613<br />

ISOLATOR<br />

Aux<br />

301<br />

608<br />

13<br />

313<br />

13<br />

301<br />

301<br />

4<br />

3R2/1<br />

3<br />

301<br />

312<br />

31 Brn 81<br />

32 Blk<br />

33Grey<br />

Blu<br />

81<br />

3MS1 3MS2<br />

3CB1<br />

4A<br />

3L1<br />

3L2<br />

3L3<br />

14<br />

3MS2<br />

14<br />

3MS1<br />

3N1<br />

303<br />

403<br />

3<br />

13<br />

201<br />

3R1/1<br />

82<br />

311<br />

2<br />

4<br />

14<br />

3K1/2<br />

83<br />

21<br />

3k1/1<br />

300<br />

303<br />

Blu<br />

308<br />

82<br />

22<br />

83<br />

3K1/4<br />

84<br />

Issue 3 Page - 31 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

308<br />

311<br />

310<br />

3Pl2/Skt2 3<br />

3Pl2/Skt2 2<br />

3Pl2/Skt2 1<br />

3Pl1/Skt1 7<br />

3Pl1/Skt1 6<br />

3Pl1/Skt1 5<br />

3K1<br />

3K1<br />

302<br />

314<br />

309<br />

301<br />

3R1<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

3R2<br />

3K1<br />

3K2<br />

3Pl1/Skt1 1-7<br />

R<br />

G G<br />

300<br />

RUN<br />

RELAY<br />

CONTACTOR<br />

CONTACTOR<br />

TRIP<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

TRIP<br />

RELAY<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

E<br />

Compressor<br />

Box<br />

Terminals<br />

306<br />

305<br />

304<br />

N<br />

1 2 3 4 5 7 8 9<br />

308<br />

307<br />

Blk<br />

Brn<br />

Blu<br />

Blu<br />

Brn<br />

N<br />

83<br />

304<br />

303<br />

N<br />

82<br />

Cabling 0.75mm & 1mm<br />

81-89 Brown 230V AC functions<br />

Blue Neutral<br />

300 White 24V 50Hz 0V<br />

301-349 Violet 24V 50Hz<br />

R Mp 1 2 12 11 14 B1 B2<br />

1U1 2U1<br />

37<br />

38<br />

1V1 M 2V1<br />

1W1 2W1<br />

39<br />

E<br />

34<br />

35<br />

36<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMP 3 PWS SCH - <strong>MSP</strong>050/060-<strong>INV</strong><br />

02 3K2 CONTACTOR COIL ADDED<br />

N/A 19/7/06<br />

<strong>MSP</strong>-050-613P-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

214<br />

630<br />

202<br />

629<br />

200<br />

600<br />

212<br />

612<br />

ISOLATOR<br />

Aux<br />

201<br />

607<br />

4<br />

71<br />

13<br />

213<br />

13<br />

201<br />

2R2/1<br />

Brn<br />

Blk<br />

Grey<br />

3<br />

216 201<br />

21<br />

22<br />

2L1<br />

2L2<br />

23<br />

2L3<br />

71<br />

14<br />

2MS2<br />

14<br />

2MS1<br />

Blu<br />

2N1<br />

203<br />

201<br />

212<br />

2MS1 2MS2<br />

2CB1<br />

4A<br />

3<br />

53<br />

201<br />

83<br />

2R1/1<br />

72<br />

217<br />

2K1/3<br />

2<br />

4<br />

54<br />

2K1/2<br />

2<br />

84<br />

21<br />

21<br />

2R3/1<br />

2k2/1<br />

2k1/1<br />

210<br />

3<br />

209<br />

200<br />

203<br />

Blu<br />

72<br />

22<br />

Issue 3 Page - 32 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

8 8<br />

2R2 2R3<br />

1 1<br />

215<br />

8<br />

3R1<br />

210<br />

2Pl3/Sk3 3<br />

2Pl2/Skt2 5 Blu<br />

22<br />

2Pl2/Skt2 4 74<br />

73<br />

2Pl3/Sk3 2<br />

2Pl3/Sk3 1<br />

2Pl2/Skt2 3<br />

2Pl2/Skt2 2<br />

2Pl2/Skt2 1<br />

2K2<br />

2K1<br />

214<br />

202<br />

A1 A1<br />

2K2 2K1<br />

A2 A2<br />

216<br />

217<br />

211<br />

201<br />

2Pl3/Sk3 4<br />

29<br />

28<br />

27<br />

26<br />

25<br />

24<br />

2Pl1/Skt1 1-7<br />

R<br />

G G<br />

1<br />

300<br />

No Connection<br />

To Compressor<br />

LOAD<br />

RELAY<br />

RUN<br />

RELAY<br />

CONTACTORS<br />

TRIP<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

3R1<br />

TRIP<br />

RELAY<br />

29<br />

28<br />

27<br />

26<br />

25<br />

24<br />

E<br />

210<br />

206<br />

205<br />

204<br />

N<br />

Compressor<br />

Box<br />

Terminals<br />

3<br />

11<br />

1 2 3 4 6 8 9 10<br />

209<br />

208<br />

207<br />

Blk<br />

Brn<br />

Blu<br />

Brn<br />

Blu<br />

N<br />

73<br />

204<br />

203<br />

N<br />

72<br />

Cabling 0.75mm & 1mm<br />

71-79 Brown 230V AC functions<br />

Blue Neutral<br />

200 White 24V 50Hz 0V<br />

201-249 Violet 24V 50Hz<br />

R Mp 1 2 12 11 14 B1 B2<br />

Off Loader<br />

1U1 2U1<br />

27<br />

28<br />

1V1 M 2V1<br />

1W1 2W1<br />

29<br />

E<br />

24<br />

25<br />

26<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMP2 PWS(OFF/L) - <strong>MSP</strong>080-<strong>INV</strong><br />

<strong>MSP</strong>-080-612P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

302<br />

630<br />

300<br />

600<br />

312<br />

613<br />

ISOLATOR<br />

Aux<br />

301<br />

608<br />

81<br />

301<br />

4<br />

13<br />

313<br />

13<br />

301<br />

Brn<br />

Blk<br />

Grey<br />

31<br />

32<br />

3L1<br />

3L2<br />

33<br />

3L3<br />

81<br />

Blu<br />

3R2/1<br />

14<br />

3MS2<br />

14<br />

3MS1<br />

3N1<br />

3<br />

303<br />

301<br />

312<br />

3MS1 3MS2<br />

3CB1<br />

4A<br />

13<br />

301<br />

3<br />

13<br />

301<br />

3R1/1<br />

82<br />

13<br />

14<br />

3K2/2<br />

2<br />

4<br />

14<br />

3K1/2<br />

21<br />

3k1/1<br />

309<br />

300<br />

3K2/1<br />

300<br />

303<br />

Blu<br />

14<br />

84<br />

82<br />

22<br />

83<br />

Issue 3 Page - 33 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

309<br />

311<br />

310<br />

3Pl2/Skt2 3<br />

3Pl2/Skt2 2<br />

3Pl2/Skt2 1<br />

3Pl2/Skt2 3<br />

3Pl2/Skt2 2<br />

3Pl2/Skt2 1<br />

3K1<br />

3K1<br />

302<br />

313<br />

314<br />

301<br />

3Pl2/Skt2 5<br />

3Pl2/Skt2 4<br />

3R1<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

3R2<br />

3K1<br />

3K2<br />

3Pl1/Skt1 1-7<br />

R<br />

G G<br />

300<br />

RUN<br />

RELAY<br />

CONTACTORS<br />

TRIP<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

TRIP<br />

RELAY<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

E<br />

306<br />

305<br />

304<br />

N<br />

13<br />

12<br />

11<br />

1 2 3 4 6 8 9 10<br />

309<br />

308<br />

307<br />

Blk<br />

Brn<br />

Blu<br />

Brn<br />

N<br />

73<br />

N<br />

84<br />

Blu<br />

304<br />

303<br />

N<br />

82<br />

Cabling 0.75mm & 1mm<br />

81-89 Brown 230V AC functions<br />

Blue Neutral<br />

300 White 24V 50Hz 0V<br />

301-349 Violet 24V 50Hz<br />

Orn<br />

Blk<br />

Brn<br />

Red<br />

R Mp 1 2 12 11 14 B1 B2<br />

1U1 2U1<br />

37<br />

38<br />

1V1 M 2V1<br />

1W1 2W1<br />

39<br />

E<br />

34<br />

35<br />

36<br />

Oil Diff<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

COMP 3 PWS SCH- <strong>MSP</strong>080/100-<strong>INV</strong><br />

<strong>MSP</strong>-080-613P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

218<br />

625<br />

202<br />

629<br />

200<br />

600<br />

214<br />

612<br />

ISOLATOR<br />

Aux<br />

201<br />

607<br />

4<br />

71<br />

13<br />

213<br />

13<br />

201<br />

2R2/1<br />

Brn<br />

Blk<br />

Grey<br />

3<br />

216 201<br />

21<br />

22<br />

2L1<br />

2L2<br />

23<br />

2L3<br />

71<br />

14<br />

2MS2<br />

14<br />

2MS1<br />

Blu<br />

2N1<br />

203<br />

201<br />

214<br />

2MS1 2MS2<br />

2CB1<br />

4A<br />

3<br />

13<br />

201<br />

33<br />

2R1/1<br />

72<br />

217<br />

2K1/3<br />

2<br />

4<br />

14<br />

2K1/2<br />

2<br />

34<br />

33<br />

21<br />

2R3/1<br />

2k2/1<br />

2k1/1<br />

308<br />

3<br />

209<br />

200<br />

203<br />

Blu<br />

72<br />

22<br />

Issue 3 Page - 34 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

210<br />

215<br />

2Pl3/Sk3 3<br />

2Pl2/Skt2 5 Blu<br />

34<br />

2Pl2/Skt2 4 74<br />

73<br />

2Pl3/Sk3 2<br />

2Pl3/Sk3 1<br />

2Pl2/Skt2 3<br />

2Pl2/Skt2 2<br />

2Pl2/Skt2 1<br />

2K2<br />

2K1<br />

218<br />

202<br />

3R1<br />

29<br />

28<br />

27<br />

26<br />

25<br />

24<br />

2R2<br />

A1 A1<br />

3K2 3K1<br />

A2 A2<br />

216<br />

217<br />

211<br />

201<br />

2Pl3/Sk3 4<br />

2R3<br />

2Pl1/Skt1 1-7<br />

R<br />

G G<br />

300<br />

LOAD<br />

RELAY<br />

RUN<br />

RELAY<br />

CONTACTORS<br />

TRIP<br />

RUN<br />

SUPPLY<br />

HEALTHY<br />

3R1<br />

TRIP<br />

RELAY<br />

29<br />

28<br />

27<br />

26<br />

25<br />

24<br />

E<br />

Compressor<br />

Box<br />

Terminals<br />

206<br />

205<br />

204<br />

N<br />

3<br />

13<br />

12<br />

11<br />

1 2 3 4 6 8 9 10<br />

209<br />

210<br />

208<br />

207<br />

Blk<br />

Brn<br />

Blu<br />

Brn<br />

Blu<br />

N<br />

73<br />

N<br />

74<br />

204<br />

203<br />

N<br />

72<br />

Cabling 0.75mm & 1mm<br />

71-79 Brown 230V AC functions<br />

Blue Neutral<br />

200 White 24V 50Hz 0V<br />

201-249 Violet 24V 50Hz<br />

Orn<br />

Blk<br />

Brn<br />

Red<br />

R Mp 1 2 12 11 14 B1 B2<br />

Off Loader<br />

1U1 2U1<br />

27<br />

28<br />

1V1 M 2V1<br />

1W1 2W1<br />

29<br />

E<br />

24<br />

25<br />

26<br />

Oil Diff<br />

LP Safety<br />

TRAXOIL<br />

HP Safety<br />

THERMISTOR INT69 VS<br />

CRANKCASE<br />

HEATER<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMP2 PWS(OFF/L) -<strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>-100-612P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

11/02/04 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Front Panel<br />

Cabling 0.75mm & 1mm<br />

61-99 Brown 230V AC functions<br />

6N and 7N Blue Neutral<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-659 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

681-689 Twisted Pair<br />

602<br />

602<br />

602<br />

602<br />

601<br />

65<br />

78<br />

2<br />

Low<br />

Liquid<br />

Sensor<br />

1<br />

5<br />

7<br />

7<br />

604<br />

605<br />

6R8/2<br />

6R9/2<br />

6R6/2<br />

X<br />

6CB2 10A<br />

X X<br />

3<br />

6CB1 4A<br />

7CB2 6A<br />

6 6 6<br />

618<br />

617<br />

616<br />

635<br />

1<br />

6R9<br />

8<br />

11<br />

602<br />

600<br />

602<br />

66<br />

78<br />

Primary<br />

Healthy<br />

Backup<br />

Operated<br />

Wetec<br />

Alarm<br />

Low<br />

Liquid<br />

Pressure<br />

Trip<br />

Supply Shutdowm<br />

Healthy Operatted<br />

601<br />

66<br />

HP/LP<br />

Master<br />

200VA<br />

Transformer<br />

230 12<br />

0<br />

1 2 4<br />

6F3 3.15A<br />

6F2 3.15A<br />

6F1 3.15A<br />

12<br />

0<br />

0<br />

603<br />

602<br />

608<br />

607<br />

66<br />

78<br />

L +<br />

230V<br />

24VDC<br />

Millenium PS<br />

N -<br />

Issue 3 Page - 35 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

602<br />

603<br />

RCD 13A<br />

Socket<br />

602 Controllers Supply<br />

603 Controls Feed<br />

7N<br />

75<br />

6N<br />

65<br />

N<br />

L3<br />

L2<br />

L1<br />

671<br />

670<br />

608 Compressor 3 Cabinet<br />

600<br />

6N<br />

E<br />

7N<br />

607 Compressor 2 Cabinet<br />

6ISO<br />

32A<br />

606 Compressor 1 Cabinet<br />

T3<br />

T2<br />

T1<br />

N<br />

613 Compressor 3 Cabinet<br />

612 Compressor 2 Cabinet<br />

7N1<br />

6N1<br />

6L1<br />

7L1<br />

611 Compressor 1 Cabinet<br />

1<br />

6R1<br />

8<br />

1<br />

6R2<br />

8<br />

6R3<br />

8<br />

1<br />

1<br />

6R6<br />

8<br />

600 (24V Return All Cabinets)<br />

671 24V DC+ Supply<br />

670 24V DC OV<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMMON CONTROLS SHT 1 - <strong>MSP</strong>050/100-<strong>INV</strong><br />

02 BACKUP LIGHT R10/3 REFERENCE REMOVED<br />

N/A 18/07/06<br />

<strong>MSP</strong>-050-631-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Suction TX<br />

4<br />

656<br />

3 6R8/1<br />

Wetec Alarm<br />

2<br />

655<br />

3 6R9/1<br />

Liquid Level Alarm<br />

Wet Tech Sensor<br />

Backup control<br />

Cabling 0.75mm<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-669 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

690-696 Red 10V DV<br />

681-689 Twisted Pair<br />

694-699 Twisted Pair<br />

Suction Temperature<br />

Suction TX<br />

671<br />

Auto<br />

653<br />

6R7/1<br />

590R<br />

Wht<br />

Brn<br />

2<br />

3 6R3/1<br />

Comp 3 Fault<br />

2<br />

3 6R2/1<br />

Comp 2 Fault<br />

2<br />

3 6R1/1<br />

Comp 1 Fault<br />

3<br />

NO<br />

1<br />

NC<br />

Man<br />

2<br />

652<br />

4<br />

NO<br />

2<br />

NC<br />

672<br />

3<br />

Blk<br />

Grn<br />

Wht<br />

Red<br />

2x1K<br />

Wht<br />

Brn<br />

NO<br />

3<br />

673<br />

650<br />

657<br />

658<br />

Blk<br />

Red<br />

Reset<br />

651<br />

Not Used<br />

Blk<br />

602<br />

Red<br />

Blk<br />

670<br />

686<br />

Red<br />

4<br />

NO<br />

674<br />

650<br />

683<br />

670<br />

Blk<br />

<strong>Inverter</strong><br />

692<br />

Alarm<br />

683<br />

682<br />

674<br />

672<br />

692<br />

Red<br />

640<br />

641<br />

642<br />

686<br />

671<br />

Red<br />

Red<br />

Blk<br />

Blk<br />

650<br />

655<br />

656<br />

Red<br />

Blk<br />

650<br />

650<br />

651<br />

652<br />

650<br />

653<br />

Com<br />

1<br />

2<br />

Com<br />

3<br />

4<br />

Com<br />

5<br />

6<br />

Com<br />

MERCURY 11-10 STEP CONTROLLER<br />

0-10V OUT<br />

+ - I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12<br />

Analogue Inputs<br />

Com<br />

6<br />

7<br />

Com<br />

8<br />

9<br />

Com<br />

10<br />

11<br />

Com<br />

CH2<br />

CH1<br />

Sig<br />

GND<br />

1<br />

2<br />

Com<br />

3<br />

4<br />

Com<br />

5<br />

Com<br />

24V<br />

DC<br />

Coms<br />

5v INPUTS<br />

Transducers<br />

MERCURY 11-10P<br />

Red<br />

Blk<br />

5v INPUTS<br />

SA20 MILLENIUM CONTROLLER<br />

Relays<br />

Relays<br />

Relays CONTROLLER Relays<br />

Compressors<br />

Danfoss<br />

Master<br />

8 9<br />

Issue 3 Page - 36 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

690<br />

24V<br />

0V<br />

78C<br />

6C<br />

0V<br />

24V<br />

45C<br />

23C<br />

1C<br />

24V<br />

0V<br />

6C<br />

0V<br />

24V<br />

1C<br />

O1 O2 O3 O4 O5 O6 O7 O8<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

N/C<br />

N/O<br />

Com<br />

602<br />

600<br />

600<br />

602<br />

602<br />

600<br />

602<br />

624<br />

604<br />

625<br />

626<br />

604<br />

624<br />

605<br />

625<br />

626<br />

605<br />

600<br />

695<br />

602<br />

622 622<br />

642<br />

640<br />

641<br />

604<br />

605<br />

6R1/25<br />

628Compressor<br />

1<br />

6246<br />

603<br />

602<br />

629 Compressor 2<br />

6R2/2<br />

6 5<br />

6R3/2 5<br />

625<br />

630 Compressor 3<br />

6<br />

626<br />

604<br />

605<br />

<strong>INV</strong> Comms<br />

695<br />

Red<br />

6R7/2 6<br />

7<br />

Red<br />

605<br />

Red<br />

696<br />

<strong>Inverter</strong> control<br />

Clr<br />

Blk<br />

696<br />

696<br />

Clr<br />

5<br />

690<br />

Blk<br />

Blk<br />

1<br />

6R8<br />

8<br />

1<br />

6R7<br />

8<br />

600LV Return<br />

600<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMMON CONTROLS SHT 2 - <strong>MSP</strong>050/100-<strong>INV</strong><br />

02 TERMINAL 695 REMOVED<br />

N/A 02/08/06<br />

<strong>MSP</strong>-050-632-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Front Panel<br />

Cabling 0.75mm & 1mm<br />

61-99 Brown 230V AC functions<br />

6N and 7N Blue Neutral<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-659 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

681-689 Twisted Pair<br />

602<br />

602<br />

602<br />

602<br />

601<br />

65<br />

75<br />

605<br />

2<br />

Low Liqid<br />

Sensor<br />

1 3<br />

5<br />

7<br />

7<br />

604<br />

6R8/2<br />

6R9/2<br />

6R6/2<br />

X<br />

6CB2 10A<br />

X X X X<br />

3 7<br />

6CB1 4A<br />

7CB3 4A<br />

7CB2 6A<br />

7CB1 4A<br />

6R10/3<br />

6 6 6<br />

618<br />

617<br />

616<br />

635<br />

1<br />

6R9<br />

8<br />

602<br />

600<br />

11<br />

602<br />

66<br />

79<br />

78<br />

76<br />

Primary<br />

Healthy<br />

Backup<br />

Operated<br />

Wetec<br />

Alarm<br />

Low<br />

Liquid<br />

Pressure<br />

Trip<br />

Shutdowm<br />

Operatted<br />

Supply<br />

Healthy<br />

76<br />

76<br />

Ligt Sw<br />

601<br />

66<br />

HP/LP<br />

Master<br />

6F3 3.15A<br />

6F2 3.15A<br />

6F1 3.15A<br />

200VA<br />

Transformer<br />

230 12<br />

0<br />

76<br />

77<br />

1 2 4<br />

12<br />

0<br />

0<br />

603<br />

602<br />

608<br />

607<br />

66<br />

JG 5 Cooler<br />

79<br />

78<br />

L +<br />

230V<br />

24VDC<br />

Millenium PS<br />

N -<br />

24V Sloenoid<br />

Maintained<br />

Houising<br />

Fluorescent<br />

Issue 3 Page - 37 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

602<br />

603<br />

Fan<br />

Motor<br />

RCD 13A<br />

Socket<br />

602 Controllers Supply<br />

603 Controls Feed<br />

7N<br />

75<br />

6N<br />

65<br />

N<br />

L3<br />

L2<br />

L1<br />

671<br />

670<br />

608 Compressor 3 Cabinet<br />

600<br />

6N<br />

7N<br />

7N<br />

7N<br />

607 Compressor 2 Cabinet<br />

6ISO<br />

32A<br />

606 Compressor 1 Cabinet<br />

T3<br />

T2<br />

T1<br />

N<br />

613 Compressor 3 Cabinet<br />

612 Compressor 2 Cabinet<br />

7N1<br />

6N1<br />

6L1<br />

7L1<br />

611 Compressor 1 Cabinet<br />

1<br />

6R1<br />

8<br />

1<br />

6R2<br />

8<br />

6R3<br />

8<br />

1<br />

1<br />

6R6<br />

8<br />

600 (24V Return All Cabinets)<br />

671 24V DC+ Supply<br />

670 24V DC OV<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

COMMON CONTROLS SHT 1 - <strong>MSP</strong>L-050-<strong>INV</strong><br />

<strong>MSP</strong>L-050-631-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

06/07/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Suction TX<br />

4<br />

656<br />

6R8/1<br />

Wetec Alarm<br />

2<br />

655<br />

6R9/1<br />

Liquid Level Alarm<br />

Wet Tech Sensor<br />

Backup control<br />

3<br />

Cabling 0.75mm<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-669 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

690-696 Red 10V DV<br />

681-689 Twisted Pair<br />

694-699 Twisted Pair<br />

Suction Temperature<br />

3<br />

Suction TX<br />

653<br />

Suction Temperature<br />

671<br />

PT1000<br />

Auto<br />

2<br />

6R7/1<br />

652<br />

590R<br />

3<br />

Wht<br />

Brn<br />

2<br />

3 6R3/1<br />

Comp 3 Fault<br />

2<br />

3 6R2/1<br />

Comp 2 Fault<br />

2<br />

3 6R1/1<br />

Comp 1 Fault<br />

3<br />

NO<br />

1<br />

NC<br />

Man<br />

4<br />

NO<br />

2<br />

NC<br />

672<br />

673<br />

Wht<br />

Red<br />

602 Blk<br />

Red Grn<br />

2x1K<br />

Wht<br />

NO<br />

3<br />

Brn<br />

Reset<br />

650<br />

657<br />

658<br />

Blk<br />

Red<br />

Blk<br />

Red<br />

Not Used<br />

Blk<br />

Blk<br />

670<br />

Red<br />

4<br />

NO<br />

686<br />

674<br />

651<br />

650<br />

684<br />

683<br />

670<br />

Blk<br />

<strong>Inverter</strong><br />

692<br />

Alarm<br />

670<br />

670<br />

683<br />

682<br />

674<br />

672<br />

692<br />

Red<br />

640<br />

641<br />

642<br />

686<br />

671<br />

671<br />

671<br />

Red<br />

Blk<br />

656<br />

Blk<br />

Red<br />

650<br />

655<br />

Red<br />

Blk<br />

650<br />

650<br />

651<br />

652<br />

650<br />

653<br />

1<br />

2<br />

3<br />

688<br />

MERCURY 11-10 STEP CONTROLLER<br />

0-10V OUT<br />

Com<br />

1<br />

2<br />

Com<br />

3<br />

4<br />

Com<br />

5<br />

6<br />

Com<br />

+ - I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12<br />

Analogue Inputs<br />

Com<br />

6<br />

7<br />

Com<br />

8<br />

9<br />

Com<br />

10<br />

11<br />

Com<br />

CH2<br />

CH1<br />

Sig<br />

GND<br />

1<br />

2<br />

Com<br />

3<br />

4<br />

Com<br />

5<br />

Com<br />

Coms<br />

5v INPUTS<br />

Transducers<br />

5v INPUTS<br />

MERCURY 11-10P<br />

Relays CONTROLLER<br />

Relays<br />

Compressors<br />

690<br />

Red<br />

Blk<br />

SA20 MILLENIUM CONTROLLER<br />

Relays<br />

Relays<br />

PT1000 -V<br />

Out<br />

+V<br />

24V<br />

DC<br />

Danfoss<br />

Master<br />

+-<br />

8 9<br />

Issue 3 Page - 38 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

24V<br />

0V<br />

78C<br />

6C<br />

0V<br />

24V<br />

23C<br />

1C<br />

24V<br />

0V<br />

6C<br />

0V<br />

45C<br />

1C<br />

4<br />

5<br />

6<br />

O1 O2 O3 O4 O5 O6 O7 O8<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

N/C<br />

N/O<br />

Com<br />

602<br />

600<br />

600<br />

602<br />

684<br />

624<br />

604<br />

625<br />

626<br />

604<br />

624<br />

605<br />

625<br />

626<br />

605<br />

600<br />

602<br />

600<br />

602<br />

695<br />

602<br />

622 622<br />

642<br />

640<br />

641<br />

604<br />

605<br />

6R1/25<br />

628Compressor<br />

1<br />

6246<br />

603<br />

602<br />

629 Compressor 2<br />

6R2/2<br />

6 5<br />

6R3/2 5<br />

625<br />

630 Compressor 3<br />

6<br />

626<br />

604<br />

605<br />

<strong>INV</strong> Comms<br />

695<br />

Red<br />

6R7/2 6<br />

7<br />

Red<br />

605<br />

696<br />

<strong>Inverter</strong> control<br />

Red<br />

Clr<br />

Blk<br />

696<br />

696<br />

Clr<br />

5<br />

690<br />

Blk<br />

Blk<br />

1<br />

6R8<br />

8<br />

1<br />

6R7<br />

8<br />

600LV Return<br />

600<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

PART<br />

02<br />

COMMON CONTROLS SHT 2 - <strong>MSP</strong>L050/100-<strong>INV</strong><br />

DATE SCALE<br />

06/07/06 1:1<br />

02 TERMINAL 695 REMOVED<br />

N/A 02/08/06<br />

<strong>MSP</strong>L-050-632-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Front Panel<br />

Cabling 0.75mm & 1mm<br />

61-99 Brown 230V AC functions<br />

6N and 7N Blue Neutral<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-659 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

681-689 Twisted Pair<br />

602<br />

602<br />

602<br />

602<br />

601<br />

65<br />

75<br />

605<br />

2<br />

Low<br />

Liquid<br />

Sensor<br />

1<br />

5<br />

7<br />

7<br />

604<br />

6R8/2<br />

6R9/2<br />

6R6/2<br />

X<br />

6CB2 10A<br />

X X X X<br />

3 7<br />

3<br />

6CB1 4A<br />

7CB3 4A<br />

7CB2 6A<br />

7CB1 4A<br />

6R10/3<br />

6 6 6<br />

618<br />

617<br />

616<br />

635<br />

1<br />

6R9<br />

8<br />

602<br />

600<br />

11<br />

602<br />

66<br />

79<br />

78<br />

76<br />

Primary<br />

Healthy<br />

Backup<br />

Operated<br />

Wetec<br />

Alarm<br />

Low<br />

Liquid<br />

Pressure<br />

Trip<br />

Shutdown<br />

Operated<br />

Supply<br />

Healthy<br />

76<br />

76<br />

Ligt Sw<br />

601<br />

66<br />

HP/LP<br />

Master<br />

6F3 3.15A<br />

6F2 3.15A<br />

6F1 3.15A<br />

76<br />

77<br />

1 2 4<br />

200VA<br />

Transformer<br />

230 12<br />

0<br />

12<br />

0<br />

0<br />

603<br />

602<br />

608<br />

607<br />

606<br />

66<br />

JG 5 Cooler<br />

79<br />

78<br />

L +<br />

230V<br />

24VDC<br />

Millenium PS<br />

N -<br />

24V Sloenoid<br />

Maintained<br />

Houising<br />

Fluorescent<br />

Issue 3 Page - 39 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

602<br />

603<br />

Fan<br />

Motor<br />

RCD 13A<br />

Socket<br />

602 Controllers Supply<br />

603 Controls Feed<br />

7N<br />

75<br />

6N<br />

65<br />

N<br />

L3<br />

L2<br />

L1<br />

671<br />

670<br />

608 Compressor 3 Cabinet<br />

600<br />

6N<br />

7N<br />

7N<br />

7N<br />

607 Compressor 2 Cabinet<br />

6ISO<br />

32A<br />

606 Compressor 1 Cabinet<br />

N<br />

T3<br />

T2<br />

T1<br />

613 Compressor 3 Cabinet<br />

612 Compressor 2 Cabinet<br />

7N1<br />

6N1<br />

6L1<br />

7L1<br />

611 Compressor 1 Cabinet<br />

1<br />

6R1<br />

8<br />

1<br />

1<br />

6R3<br />

8<br />

1<br />

1<br />

6R6<br />

8<br />

600 (24V Return All Cabinets)<br />

8<br />

8<br />

671 24V DC+ Supply<br />

670 24V DC OV<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMMON CONTROLS SHT 1 - MSHP080/100-ECI<br />

MSHP-080-631-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

21/08/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Suction TX<br />

4<br />

656<br />

6R8/1<br />

Wetec Alarm<br />

2<br />

655<br />

6R9/1<br />

Liquid Level Alarm<br />

Wet Tech Sensor<br />

Backup control<br />

3<br />

Cabling 0.75mm<br />

600 White 24V 50Hz 0V<br />

601-649 Violet 24V 50Hz<br />

650 White RDM Com 0V<br />

651-669 Orange RDM 5V<br />

670 Black 24V DC 0V<br />

671-679 Red 24V DC<br />

690-696 Red 10V DV<br />

681-689 Twisted Pair<br />

694-699 Twisted Pair<br />

Suction Temperature<br />

3<br />

Suction TX<br />

671<br />

Auto<br />

653<br />

6R7/1<br />

590R<br />

Wht<br />

2<br />

6R3/1<br />

Comp 3 Fault<br />

2<br />

6R2/1<br />

Comp 2 Fault<br />

2<br />

6R1/1<br />

Comp 1 Fault<br />

NO<br />

1<br />

NC<br />

3<br />

Man<br />

2<br />

Housing Temp (PT1000)<br />

3<br />

652<br />

4<br />

NO<br />

2<br />

NC<br />

3<br />

672<br />

3<br />

673<br />

Blk<br />

Grn<br />

Wht<br />

Red<br />

Brn<br />

2x1K<br />

Wht<br />

Brn<br />

NO<br />

3<br />

3<br />

650<br />

657<br />

658<br />

Red<br />

Blk<br />

Reset<br />

686<br />

651<br />

Blk<br />

Red<br />

Not Used<br />

Red<br />

Blk<br />

602<br />

Blk<br />

670<br />

Red<br />

4<br />

NO<br />

674<br />

650<br />

684<br />

683<br />

670<br />

Blk<br />

<strong>Inverter</strong><br />

692<br />

Alarm<br />

683<br />

682<br />

674<br />

672<br />

692<br />

Red<br />

640<br />

641<br />

642<br />

686<br />

671<br />

671<br />

670<br />

671<br />

Red<br />

Blk<br />

Blk<br />

656<br />

Blk<br />

Red<br />

650<br />

655<br />

Red<br />

Blk<br />

650<br />

650<br />

651<br />

652<br />

650<br />

653<br />

1<br />

2<br />

3<br />

Red<br />

688<br />

MERCURY 11-10 STEP CONTROLLER<br />

0-10V OUT<br />

5<br />

6<br />

3<br />

4<br />

1<br />

2<br />

-V<br />

Out<br />

+V<br />

+ - I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12<br />

Analogue Inputs<br />

Com<br />

6<br />

7<br />

Com<br />

8<br />

9<br />

Com<br />

10<br />

11<br />

Com<br />

CH2<br />

12VDC<br />

CH1<br />

12VDC<br />

Sig<br />

GND<br />

1<br />

2<br />

Com<br />

3<br />

4<br />

Com<br />

5<br />

Com<br />

24V<br />

DC<br />

Coms<br />

5v INPUTS<br />

Transducers<br />

MERCURY 11-10P<br />

5v INPUTS<br />

Blk<br />

Red<br />

SA20 MILLENIUM CONTROLLER<br />

Relays<br />

Relays<br />

Relays CONTROLLER Relays<br />

Compressors<br />

PT1000<br />

Danfoss<br />

Master<br />

+-<br />

8 9<br />

Issue 3 Page - 40 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

690<br />

24V<br />

0V<br />

78C<br />

6C<br />

0V<br />

24V<br />

45C<br />

1C<br />

0V<br />

6C<br />

0V<br />

1C<br />

4<br />

5<br />

6<br />

O1 O2 O3 O4 O5 O6 O7 O8<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

Com<br />

N/O<br />

N/O<br />

N/O<br />

N/C<br />

N/O<br />

Com<br />

600<br />

602<br />

600<br />

602<br />

600<br />

602<br />

605<br />

624<br />

605<br />

625<br />

626<br />

605<br />

627<br />

600<br />

602<br />

604<br />

624<br />

604<br />

625<br />

626<br />

604<br />

627<br />

684<br />

695<br />

602<br />

622 622<br />

642<br />

640<br />

641<br />

604<br />

605<br />

628Compressor<br />

1<br />

629 Compressor 2<br />

630 Compressor 2<br />

Loader<br />

631 Compressor 3<br />

6R1/25<br />

6R2/25<br />

6R2/34<br />

6R3/25<br />

6246<br />

625 6<br />

626 3<br />

627 6<br />

603<br />

602<br />

604<br />

605<br />

<strong>INV</strong> Comms<br />

695<br />

Red<br />

6R7/2 6<br />

7<br />

Red<br />

Red<br />

696<br />

<strong>Inverter</strong> control<br />

Clr<br />

Blk<br />

696<br />

696<br />

Clr<br />

5<br />

690<br />

Blk<br />

Blk<br />

605<br />

623 Cooler Sol<br />

1<br />

6R8<br />

8<br />

1<br />

6R7<br />

8<br />

600LV Return<br />

600<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

PART<br />

01<br />

COMMON CONTROLS SHT 2 - MSHP080/100-<strong>INV</strong><br />

DATE SCALE<br />

21/08/06 1:1<br />

02/08/06<br />

N/A<br />

MSHP-080-632-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

108<br />

100<br />

103<br />

N<br />

63<br />

62<br />

100<br />

63<br />

108<br />

103<br />

N<br />

62<br />

1Pl2/Skt2<br />

1Pl1/Skt1<br />

190<br />

16<br />

15<br />

14<br />

E<br />

Issue 3 Page - 41 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1N1 Main<br />

Earth<br />

N<br />

N<br />

35mm trunking<br />

35mm trunking<br />

1L3<br />

25 mm trunking<br />

1L2<br />

1MS1 1CB1<br />

MCB<br />

260.0<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

T2<br />

4<br />

1L1<br />

1<br />

3<br />

L1 L2 L3<br />

1R1 1R2<br />

10-16A<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

T1<br />

2<br />

606<br />

22<br />

14<br />

13<br />

21<br />

101<br />

14<br />

22<br />

21<br />

13<br />

628<br />

611<br />

600<br />

102<br />

112<br />

100<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

COMP 1 DOL LAYOUT: <strong>MSP</strong>050/080-<strong>INV</strong><br />

<strong>MSP</strong>-050-621D-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

ew<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

26 73<br />

208<br />

200<br />

203<br />

N<br />

72<br />

200<br />

208<br />

203<br />

N<br />

72<br />

73<br />

26<br />

24<br />

E<br />

25<br />

25<br />

2Pl1/Skt1 2Pl2/Skt2<br />

24<br />

E<br />

Issue 3 Page - 42 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

E<br />

Main<br />

Earth<br />

2N1<br />

N<br />

N<br />

2L3<br />

35mm trunking<br />

2K1 2R1 2R2<br />

35mm trunking<br />

2L2<br />

2MS1 2CB1<br />

MCB<br />

260.0<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

T2<br />

4<br />

1 L1 2 L2 3 L3<br />

25 mm trunking<br />

N<br />

N<br />

Test<br />

2L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

12A<br />

607<br />

22<br />

14<br />

13<br />

21<br />

201<br />

14<br />

22<br />

21<br />

13<br />

629<br />

612<br />

600<br />

202<br />

212<br />

200<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-050-622D-<strong>INV</strong><br />

01<br />

COMP 2 DOL LAYOUT<strong>MSP</strong>050-<strong>INV</strong><br />

<strong>MSP</strong>-050-622D-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

ew<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

34<br />

E<br />

E<br />

E<br />

35<br />

308<br />

308<br />

300<br />

300<br />

303<br />

303<br />

N N<br />

84<br />

84<br />

N<br />

N<br />

83<br />

83<br />

82<br />

82<br />

39<br />

38<br />

37<br />

36<br />

3Pl3/Skt3<br />

3Pl2/Skt2<br />

3R2<br />

3Pl1/Skt1<br />

Issue 3 Page - 43 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Main<br />

Earth<br />

3N1<br />

35mm trunking<br />

3K1 3K2 3R1<br />

35mm trunking<br />

3L3<br />

3MS1 3MS2 3CB1<br />

MCB<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

N<br />

N<br />

25 mm trunking<br />

260.0<br />

Test<br />

1 L1 2 L2 3 L3<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

3L2<br />

T2<br />

4<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

3L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

608<br />

22<br />

14<br />

13<br />

21<br />

301<br />

14<br />

22<br />

21<br />

13<br />

630<br />

613<br />

600<br />

302<br />

312<br />

300<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-(050 & 060)-623P-<strong>INV</strong><br />

02<br />

COMP 3 PWS LAYOUT: <strong>MSP</strong>050-<strong>INV</strong><br />

02 TERMINAL 309 CHANGED TO BE 308<br />

N/A 19/07/06<br />

<strong>MSP</strong>-050-623P-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

26 73<br />

208<br />

200<br />

203<br />

N<br />

72<br />

200<br />

208<br />

203<br />

N<br />

72<br />

73<br />

26<br />

24<br />

E<br />

25<br />

25<br />

2Pl1/Skt1 2Pl2/Skt2<br />

24<br />

E<br />

Issue 3 Page - 44 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

E<br />

Main<br />

Earth<br />

2N1<br />

N<br />

N<br />

2L3<br />

35mm trunking<br />

2K1 2R1 2R2<br />

35mm trunking<br />

2L2<br />

2MS1 2CB1<br />

MCB<br />

260.0<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

T2<br />

4<br />

1 L1 2 L2 3 L3<br />

25 mm trunking<br />

N<br />

N<br />

Test<br />

2L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

607<br />

22<br />

14<br />

13<br />

21<br />

201<br />

14<br />

22<br />

21<br />

13<br />

629<br />

612<br />

600<br />

202<br />

212<br />

200<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-060-622D-<strong>INV</strong><br />

01<br />

COMP 2 DOL LAYOUT: <strong>MSP</strong>060-MPI<br />

<strong>MSP</strong>-060-622D-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

ew<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

34<br />

E<br />

E<br />

E<br />

35<br />

309<br />

309<br />

300<br />

300<br />

303<br />

303<br />

N N<br />

84<br />

84<br />

N<br />

N<br />

83<br />

83<br />

82<br />

82<br />

39<br />

38<br />

37<br />

36<br />

3Pl3/Skt3<br />

3Pl2/Skt2<br />

3R2<br />

3Pl1/Skt1<br />

Issue 3 Page - 45 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Main<br />

Earth<br />

3N1<br />

35mm trunking<br />

3K1 3K2 3R1<br />

35mm trunking<br />

3L3<br />

3MS1 3MS2 3CB1<br />

MCB<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

N<br />

N<br />

25 mm trunking<br />

260.0<br />

Test<br />

1 L1 2 L2 3 L3<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

3L2<br />

T2<br />

4<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

3L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

608<br />

22<br />

14<br />

13<br />

21<br />

301<br />

14<br />

22<br />

21<br />

13<br />

630<br />

613<br />

600<br />

302<br />

312<br />

300<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-(060 & 080)-623P-<strong>INV</strong><br />

01<br />

COMP 3 PWS LAYOUT: <strong>MSP</strong>060/080-<strong>INV</strong><br />

<strong>MSP</strong>-060-623P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

24<br />

E<br />

25<br />

210<br />

209<br />

200<br />

203<br />

Not Used<br />

N<br />

73<br />

72<br />

29<br />

28<br />

27<br />

26<br />

210<br />

200<br />

209<br />

203<br />

N<br />

2Pl3/Skt3<br />

74<br />

N<br />

73<br />

2Pl2/Skt2<br />

72<br />

29<br />

38<br />

27<br />

2R2<br />

26<br />

25<br />

24<br />

2Pl1/Skt1<br />

E<br />

Issue 3 Page - 46 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

E<br />

Main<br />

Earth<br />

2N1<br />

35mm trunking<br />

2K1 2K2 2R1<br />

35mm trunking<br />

2L3<br />

2MS1 2MS2 2CB1<br />

MCB<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

N<br />

N<br />

25 mm trunking<br />

260.0<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

12A 12A<br />

Test<br />

1 L1 2 L2 3 L3<br />

2L2<br />

T2<br />

4<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

2L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

608<br />

201<br />

202 629<br />

626<br />

626<br />

212<br />

612<br />

200<br />

600<br />

22<br />

14<br />

13<br />

21<br />

14<br />

22<br />

21<br />

13<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-080-622P-<strong>INV</strong><br />

01<br />

COMP 2 PWS LAYOUT: <strong>MSP</strong>080-<strong>INV</strong><br />

<strong>MSP</strong>-080-622P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

108<br />

100<br />

103<br />

N<br />

63<br />

62<br />

100<br />

63<br />

108<br />

103<br />

N<br />

62<br />

1Pl2/Skt2<br />

1Pl1/Skt1<br />

190<br />

16<br />

15<br />

14<br />

E<br />

Issue 3 Page - 47 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1N1 Main<br />

Earth<br />

N<br />

N<br />

35mm trunking<br />

35mm trunking<br />

1L3<br />

25 mm trunking<br />

1L2<br />

1MS1 1CB1<br />

MCB<br />

260.0<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

T2<br />

4<br />

1L1<br />

1<br />

3<br />

L1 L2 L3<br />

1R1 1R2<br />

16-20A<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

T1<br />

2<br />

606<br />

22<br />

14<br />

13<br />

21<br />

101<br />

14<br />

22<br />

21<br />

13<br />

628<br />

611<br />

600<br />

102<br />

112<br />

100<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

COMP 1 DOL LAYOUT: <strong>MSP</strong>-100-<strong>INV</strong><br />

<strong>MSP</strong>-100-621D-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

ew<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

210<br />

209<br />

200<br />

203<br />

N<br />

74<br />

N<br />

73<br />

72<br />

210<br />

200<br />

209<br />

203<br />

N<br />

2Pl3/Skt3<br />

74<br />

N<br />

73<br />

2Pl2/Skt2<br />

72<br />

24<br />

E<br />

25<br />

29<br />

28<br />

27<br />

26<br />

29<br />

28<br />

27<br />

2R2<br />

26<br />

25<br />

24<br />

2Pl1/Skt1<br />

E<br />

Issue 3 Page - 48 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

E<br />

Main<br />

Earth<br />

2N1<br />

35mm trunking<br />

2K1 2K2 2R1<br />

35mm trunking<br />

2L3<br />

2MS1 2MS2 2CB1<br />

MCB<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

N<br />

N<br />

25 mm trunking<br />

260.0<br />

Test<br />

1 L1 2 L2 3 L3<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

2L2<br />

T2<br />

4<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

2L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

608<br />

201<br />

202 629<br />

626<br />

626<br />

212<br />

612<br />

200<br />

600<br />

22<br />

14<br />

13<br />

21<br />

14<br />

22<br />

21<br />

13<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-100-622P-<strong>INV</strong><br />

01<br />

COMP 2 PWS LAYOUT: <strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>-100-622P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

580.0<br />

25 mm trunking<br />

39<br />

38<br />

37<br />

36<br />

35<br />

34<br />

34<br />

E<br />

E<br />

E<br />

35<br />

309<br />

309<br />

300<br />

300<br />

303<br />

303<br />

N N<br />

84<br />

84<br />

N<br />

N<br />

83<br />

83<br />

82<br />

82<br />

39<br />

38<br />

37<br />

36<br />

3Pl3/Skt3<br />

3Pl2/Skt2<br />

3R2<br />

3Pl1/Skt1<br />

Issue 3 Page - 49 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Main<br />

Earth<br />

3N1<br />

35mm trunking<br />

3K1 3K2 3R1<br />

35mm trunking<br />

3L3<br />

3MS1 3MS2 3CB1<br />

MCB<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

N<br />

N<br />

25 mm trunking<br />

260.0<br />

Test<br />

1 L1 2 L2 3 L3<br />

T3<br />

6<br />

5<br />

22<br />

14<br />

Aux<br />

13<br />

21<br />

PE<br />

PE<br />

3L2<br />

T2<br />

4<br />

N<br />

N<br />

Test<br />

1 L1 2 L2 3 L3<br />

3L1<br />

T1<br />

2<br />

1<br />

3<br />

L1 L2 L3<br />

608<br />

22<br />

14<br />

13<br />

21<br />

301<br />

14<br />

22<br />

21<br />

13<br />

630<br />

613<br />

600<br />

302<br />

312<br />

300<br />

35mm trunking<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>-100-623P-<strong>INV</strong><br />

01<br />

COMP 3 PWS LAYOUT: <strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>-100-623P-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:2<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

To Controller<br />

Transducer<br />

Lead Blk/Wht<br />

Red<br />

Blk<br />

Tw Pair<br />

Screened or Tw Pair Red/Brn<br />

670<br />

RDM Termination<br />

Resistor<br />

657<br />

658<br />

650<br />

Sleeved Resistor 590R<br />

Sleeved Resistor(s)<br />

Transducer<br />

Termination<br />

Detail<br />

0<br />

220<br />

230<br />

240<br />

380<br />

400<br />

415<br />

440<br />

6R1<br />

6R2<br />

6R3<br />

6R6<br />

6R7<br />

6L1<br />

7L1<br />

6N<br />

PT1000<br />

200VA Transformer<br />

0<br />

0 12<br />

12<br />

7N<br />

696 Blk 692 Blk<br />

6R8<br />

6R9<br />

Comp 3 Comp 2<br />

6CB16CB27CB1<br />

Red<br />

Blk<br />

Red<br />

Comp 1<br />

Clr<br />

Blk<br />

Pack Control<br />

Backup Primary<br />

600<br />

602<br />

Red Blk 682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk<br />

Liquid level<br />

657 658<br />

NC 650<br />

600<br />

608<br />

613<br />

630<br />

600<br />

607<br />

612<br />

629<br />

600<br />

606<br />

611<br />

628<br />

692<br />

696<br />

E<br />

N<br />

78<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

686<br />

Common Control Items<br />

Issue 3 Page - 50 -<br />

September 2007<br />

6<br />

L1 L2 L3<br />

N<br />

1 2<br />

3 4<br />

24V DC PWS<br />

N<br />

5 6<br />

2 4 6<br />

600<br />

608<br />

613<br />

MCB MCB MCB<br />

630<br />

600<br />

607<br />

612<br />

629<br />

Comp 3 Comp 2<br />

600<br />

606<br />

611<br />

Red<br />

628<br />

Comp 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Blk<br />

692<br />

Red<br />

Clr<br />

Delay<br />

Between<br />

Stage<br />

Increase<br />

5s<br />

696<br />

Blk<br />

10s<br />

15s<br />

E<br />

RESOURCE DATA MANAGEMENT<br />

20s<br />

30s<br />

I1 I12<br />

N<br />

45s<br />

1m<br />

2m<br />

Millenium<br />

SA20<br />

O1 O2 O3/4 O5/6 O7/8<br />

Delay<br />

Between<br />

Stage<br />

Dectease<br />

680<br />

681<br />

686<br />

Red Blk 682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk<br />

78<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

Common Control Items<br />

5m<br />

10m<br />

OK<br />

Liquid level<br />

657 658<br />

NC 650<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

03 DANFOSS COMMS MODULE MOVED<br />

N/A 02/08/06<br />

03<br />

COMMON CNTRLS LAYOUT: <strong>MSP</strong>050/100-<strong>INV</strong><br />

02 TERMINALS 650/661 COND TX REMOVED<br />

N/A 180706<br />

<strong>MSP</strong>-050-634-<strong>INV</strong>.03<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

31/05/06 1:3<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

To Controller<br />

Transducer<br />

Lead Blk/Wht<br />

Blk<br />

Red<br />

Tw Pair<br />

Red/Brn<br />

Screened or Tw Pair<br />

670<br />

N<br />

E<br />

76<br />

77<br />

RDM Termination<br />

Resistor<br />

657<br />

658<br />

650<br />

Sleeved Resistor 590R<br />

Sleeved Resistor(s)<br />

Transducer<br />

Termination<br />

Detail<br />

0<br />

220<br />

230<br />

240<br />

380<br />

400<br />

415<br />

440<br />

Transformer MCB MCB MCB MCB MCB<br />

6CB1 6CB2 7CB1 7CB2 7CB3<br />

6R1<br />

6R2<br />

6R3<br />

6R6<br />

6R7<br />

6L1<br />

7L1<br />

6N<br />

7N<br />

PT1000<br />

200VA<br />

0<br />

0 12<br />

12<br />

696 Blk 692 Blk<br />

6R8<br />

6R9<br />

Comp 3 Comp 2<br />

Busbar<br />

Red<br />

Red<br />

Blk<br />

Red<br />

Blk<br />

Clr<br />

Comp 1<br />

Blk<br />

Pack Control<br />

Backup Primary<br />

600<br />

602<br />

Red Blk 681<br />

670<br />

Red Blk682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk 684<br />

Red Blk 685<br />

Red Blk 686<br />

600<br />

608<br />

613<br />

630<br />

600<br />

607<br />

612<br />

629<br />

600<br />

606<br />

611<br />

628<br />

692<br />

695<br />

696<br />

E<br />

N<br />

76<br />

77<br />

78<br />

79<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

Wht/Brn<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Red/Blk<br />

Wht/Brn<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

Resistor<br />

Common Control Items<br />

Issue 3 Page - 51 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Liquid level<br />

657 658<br />

NC 650<br />

660/661<br />

NC 650<br />

6<br />

L1 L2 L3<br />

1 2<br />

N<br />

3 4<br />

24V DC PWS<br />

5 6 N<br />

2 4 6<br />

600<br />

608<br />

613<br />

630<br />

600<br />

607<br />

612<br />

629<br />

600<br />

Comp 3Comp<br />

2<br />

606<br />

611<br />

Red<br />

628<br />

Blk<br />

Red<br />

Blk<br />

692<br />

695<br />

696<br />

Comp 1<br />

Red<br />

Clr<br />

Blk<br />

Delay<br />

Between<br />

Stage<br />

Increase<br />

5s<br />

E<br />

10s<br />

N<br />

15s<br />

20s<br />

30s<br />

I1 I12<br />

RESOURCE DATA MANAGEMENT<br />

45s<br />

1m<br />

Delay<br />

Between<br />

Stage<br />

Dectease<br />

680<br />

681<br />

Red Blk 681<br />

670<br />

Red Blk 682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk 684<br />

Red Blk 685<br />

Red Blk<br />

76<br />

77<br />

78<br />

79<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

Wht/Brn<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Red/Blk<br />

Wht/Brn<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

Resistor<br />

Common Control Items<br />

2m<br />

Millenium<br />

SA20<br />

O1 O2 O3/4 O5/6 O7/8<br />

5m<br />

10m<br />

1 2 3<br />

-VOut+V<br />

Power<br />

Fail<br />

+ -<br />

4 5 6<br />

OK<br />

686<br />

Liquid level<br />

657 658<br />

NC 650<br />

660/661<br />

NC 650<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

02<br />

COMMON CNTRLS LAYOUT: <strong>MSP</strong>L050/100-<strong>INV</strong><br />

02 DANFOSS COMMS MODULE MOVED<br />

N/A 02/08/06<br />

<strong>MSP</strong>L-050-634-<strong>INV</strong>.02<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

06/07/06 1:3<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

To Controller<br />

Transducer<br />

Lead Blk/Wht<br />

Red<br />

Blk<br />

Tw Pair<br />

Screened or Tw Pair Red/Brn<br />

670<br />

Sleeved Resistor 590R<br />

Sleeved Resistor(s)<br />

1 2<br />

3 4<br />

5 6<br />

Transducer<br />

Termination<br />

Detail<br />

N<br />

E<br />

76<br />

77<br />

RDM Termination<br />

Resistor<br />

657<br />

658<br />

650<br />

PT1000<br />

Busbar<br />

Transformer MCB MCB MCB MCB MCB<br />

6CB1 6CB2 7CB1 7CB2 7CB3<br />

6R1<br />

6R2<br />

6R2<br />

6R3<br />

6R6<br />

6R7<br />

6R2-1/2<br />

6R2-3/4<br />

0<br />

220<br />

230<br />

240<br />

380<br />

400<br />

415<br />

440<br />

L1 L2 L3<br />

N<br />

N<br />

2 4 6<br />

200VA<br />

0<br />

0 12<br />

12<br />

6L1<br />

7L1<br />

6N<br />

7N<br />

600<br />

608<br />

613<br />

696 Blk 692 Blk<br />

6R8<br />

6R9<br />

Comp 3 Comp 2<br />

Red<br />

Blk<br />

Red<br />

Comp 1<br />

Clr<br />

Blk<br />

Issue 3 Page - 52 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Pack Control<br />

Backup Primary<br />

600<br />

602<br />

Red Blk 681<br />

670<br />

Red Blk 682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk 684<br />

Red Blk 685<br />

Red Blk 686<br />

600<br />

608<br />

613<br />

630<br />

600<br />

607<br />

612<br />

625<br />

629<br />

630<br />

600<br />

606<br />

611<br />

628<br />

692<br />

696<br />

E<br />

N<br />

76<br />

77<br />

78<br />

79<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

699<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Red/Blk<br />

Wht/Brn<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

Resistor<br />

630<br />

Comp 3<br />

600<br />

607<br />

612<br />

629<br />

625<br />

630<br />

600<br />

606<br />

Comp 2<br />

611<br />

628<br />

Red<br />

Comp 1<br />

Common Control Items<br />

Blk<br />

692<br />

Red<br />

Clr<br />

696<br />

Blk<br />

E<br />

N<br />

Delay<br />

Between<br />

Stage<br />

Increase<br />

5s<br />

10s<br />

15s<br />

20s<br />

Liquid level<br />

657 658<br />

NC 650<br />

660/661<br />

NC 650<br />

30s<br />

I1 I12<br />

RESOURCE DATA MANAGEMENT<br />

24V DC PWS<br />

Delay<br />

Between<br />

Stage<br />

Dectease<br />

680<br />

681<br />

Red Blk 681<br />

670<br />

Red Blk 682<br />

670<br />

Red Blk 683<br />

602/600<br />

Red Blk 684<br />

Red Blk 685<br />

Red Blk<br />

76<br />

77<br />

78<br />

79<br />

600<br />

602<br />

603<br />

623<br />

Wht/Brn<br />

Resistor<br />

699<br />

Resistor<br />

Wht/Grn<br />

Blk/Red<br />

Red/Blk<br />

Wht/Brn<br />

Wht/Brn<br />

602/600<br />

635<br />

Resistor<br />

PT1000<br />

Resistor<br />

Common Control Items<br />

45s<br />

1m<br />

2m<br />

Millenium<br />

SA20<br />

O1 O2 O3/4 O5/6 O7/8<br />

5m<br />

10m<br />

1 2 3<br />

-VOut+V<br />

Power<br />

Fail<br />

+ -<br />

4 5 6<br />

OK<br />

686<br />

Liquid level<br />

657 658<br />

NC 650<br />

660/661<br />

NC 650<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

CCU-(080 & 100)-636-ECI<br />

02<br />

COMMON CNTRLS LAYOUT: MSHP080/100-ECI<br />

MSHP-080-636-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

24/06/05 1:3<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Pack Controller Settings<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

<strong>MSP</strong>050/060-<strong>INV</strong> RDM STEP CONTROLLER SETTINGS<br />

Site Setting<br />

Value Units<br />

Factory Setting<br />

Value<br />

Low High Default<br />

Parameter Name<br />

Increase Delay 5 secs 10 ins 1 min 20 secs<br />

Decrease Delay 5 secs 10 ins 1 min 20 secs<br />

Number of Stages 1 10 10 3<br />

General Alarm Delay 00:00 15:00 00:10 5:00 mm:ss<br />

Capacity Delay 00:00 99:00 00:10 5:00 mm:ss<br />

Control Fault Delay 01:00 30:00 10:00 10:00 mm:ss<br />

Millenium Software Version:- <strong>MSP</strong>50-100-<strong>INV</strong><br />

Millenium Controller Inputs and Outputs<br />

Input Input Type Application Output Output Application Control Voltage<br />

Type<br />

I1 Digital Exit Backup O1 Relay Backup Signal 24V 50Hz<br />

I2 Digital Enter Backup O2 Relay 24V 50Hz<br />

I3 N/A O3 Relay 24V 50Hz<br />

I4 N/A O4 Relay 24V 50Hz<br />

I5 Analogue Discharge Transducer O5 Relay Load Compressors Signal<br />

24V 50Hz<br />

I6 Analogue Suction Transducer O6 Relay Unload Compressors Signal 24V 50Hz<br />

I7 Analogue Wet Tech Sensor O7 Relay Wet Tech Alarm<br />

24V 50Hz<br />

I8 N/A<br />

O8 Relay 24V 50Hz<br />

I9 N/A<br />

I10 N/A<br />

I11 N/A<br />

I12<br />

P-01 Target Pressure -3.4-38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4-38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4-38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 Default<br />

P-86 Response Off 1-15 1 10 Default<br />

P-04 Number of Starts/hr -60 1 6 10<br />

P-05 Optomise Limit -3.4-38.6 1 30 Default<br />

P-80 Startup delay 0-5 Mins 1 0 Default<br />

P-82 Run Smallest 0=Off 1=On 1 0 Default<br />

P-98 Probe Offset -50<br />

-3.4-38.6<br />

-3.4-38.6<br />

-3.4-38.6<br />

o C 70 o Min/Sec<br />

o<br />

C 0.1 C 0 Default<br />

P-13 HP Alarm Pressure 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure 0.1 BAR 0.2 1.5<br />

P-15 Shut Down Pressure 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0-99 1 Min/Sec 3 Mins Default<br />

P-81 General Alarm Delay 0-60 Mins 1 Min/Sec 4 Mins 45 Mins<br />

P-22 Stage 2 Type Compressor<br />

P-23 Stage 3 Type Compressor<br />

P-24 Stage 4 Type (0) None<br />

Unused<br />

P-25 Stage 5 Type (1)Unused<br />

Unused<br />

P-26 Stage 6 Type (2)Compressor<br />

P-27 Stage 7 Type (3)Loader<br />

P-28 Stage 8 Type (4)Fan<br />

P-29 Stage 9 Type<br />

P-30 Stage 10 Type<br />

P-51 Stage 1 Size 19.8<br />

P-52 Stage 2 Size 25<br />

P-53 Stage 3 Size 55.3<br />

P-54 Stage 4 Size<br />

P-55 Stage 5 Size<br />

0-60<br />

P-56 Stage 6 Size<br />

P-57 Stage 7 Size<br />

P-58 Stage 8 Size<br />

P-59 Stage 9 Size<br />

P-60 Stage 10 Size<br />

P-41 Stage 1 Input Type N/O Compressor 1<br />

P-42 Stage2 Input Type N/O Compressor 2<br />

P-43 Stage 3 Input Type N/O Compressor 3<br />

P-44 Stage 4 Input Type Unused<br />

(0)N/O<br />

P-45 Stage 5 Input Type Unused<br />

(1)N/C<br />

P-46 Stage 6 Input Type N/O Liquid Level<br />

(2)Unused<br />

P-47 Stage 7 Input Type N/O Moisture Detected<br />

P-48 Stage 8 Input Type N/O <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type<br />

P-50 Stage 10 Input Type<br />

Issue 3 Page - 53 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

PART<br />

RDM PACK & CONDENSER CONT <strong>MSP</strong>050-<strong>INV</strong><br />

DATE SCALE<br />

31/05/06 1:1<br />

01<br />

<strong>MSP</strong>-050-630-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Pack Controller Settings<br />

<strong>MSP</strong>050/060-<strong>INV</strong> RDM STEP CONTROLLER SETTINGS<br />

Site Setting<br />

Value Units<br />

Factory Setting<br />

Value<br />

Low High Default<br />

Parameter Name<br />

Increase Delay 5 secs 10 ins 1 min 20 secs<br />

Decrease Delay 5 secs 10 ins 1 min 20 secs<br />

Number of Stages 1 10 10 3<br />

General Alarm Delay 00:00 15:00 00:10 5:00 mm:ss<br />

Capacity Delay 00:00 99:00 00:10 5:00 mm:ss<br />

Control Fault Delay 01:00 30:00 10:00 10:00 mm:ss<br />

Millenium Software Version:- <strong>MSP</strong>50-100-<strong>INV</strong><br />

Millenium Controller Inputs and Outputs<br />

Input Input Type Application Output Output Application Control<br />

Type<br />

Voltage<br />

I1 Digital Exit Backup O1 Relay Backup Signal 24V 50Hz<br />

I2 Digital Enter Backup O2 Relay 24V 50Hz<br />

I3 N/A O3 Relay 24V 50Hz<br />

I4 N/A O4 Relay 24V 50Hz<br />

I5 Analogue Discharge Transducer O5 Relay Load Compressors Signal<br />

24V 50Hz<br />

I6 Analogue Suction Transducer O6 Relay Unload Compressors Signal 24V 50Hz<br />

I7 Analogue Wet Tech Sensor O7 Relay Wet Tech Alarm<br />

24V 50Hz<br />

I8 N/A<br />

O8 Relay 24V 50Hz<br />

I9 N/A<br />

I10 N/A<br />

I11 N/A<br />

I12<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4 - 38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4 - 38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4 - 38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 Default<br />

P-86 Response Off 1-15 1 10 Default<br />

P-04 Number of Starts/hr --60 1 6 10<br />

P-05 Optomise Limit -50-560 1 30 Default<br />

P-80 Startup delay 0-5 Mins 1 0 Default<br />

P-82 Run Smallest 0=Off 1=On 1 0 Default<br />

P-98 Probe Offset -50<br />

-3.4 - 38.6<br />

-3.4 - 38.6<br />

-3.4 - 38.6<br />

o C 70 o Min/Sec<br />

o<br />

C 0.1 C 0 Default<br />

P-13 HP Alarm Pressure 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure 0.1 BAR 0.2 1.5<br />

P-15 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0-99 1 Min/Sec 3 Mins Default<br />

P-81 0-60 Mins 1 Min/Sec 4 Mins 45 Mins<br />

P-22 Stage 2 Type Compressor<br />

P-23 Stage 3 Type Compressor<br />

P-24 Stage 4 Type (0) None<br />

Unused<br />

P-25 Stage 5 Type (1)Unused<br />

Unused<br />

P-26 Stage 6 Type (2)Compressor<br />

P-27 Stage 7 Type (3)Loader<br />

P-28 Stage 8 Type (4)Fan<br />

P-29 Stage 9 Type<br />

P-30 Stage 10 Type<br />

P-51 Stage 1 Size 21<br />

P-52 Stage 2 Size 25.6<br />

P-53 Stage 3 Size 53.4<br />

P-54 Stage 4 Size<br />

P-55 Stage 5 Size<br />

0-60<br />

P-56 Stage 6 Size<br />

P-57 Stage 7 Size<br />

P-58 Stage 8 Size<br />

P-59 Stage 9 Size<br />

P-60 Stage 10 Size<br />

P-41 Stage 1 Input Type N/O Compressor 1<br />

P-42 Stage2 Input Type N/O Compressor 2<br />

P-43 Stage 3 Input Type N/O Compressor 3<br />

P-44 Stage 4 Input Type Unused<br />

(0)N/O<br />

P-45 Stage 5 Input Type Unused<br />

(1)N/C<br />

P-46 Stage 6 Input Type N/O Liquid Level<br />

(2)Unused<br />

P-47 Stage 7 Input Type N/O Moisture Detected<br />

P-48 Stage 8 Input Type N/O <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type<br />

P-50 Stage 10 Input Type<br />

Issue 3 Page - 54 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

PART<br />

RDM PACK & CONDENSER CONT <strong>MSP</strong>060-<strong>INV</strong><br />

DATE SCALE<br />

31/05/06 1:1<br />

01<br />

<strong>MSP</strong>-060-630-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

Pack Controller Settings<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

<strong>MSP</strong>050/060-<strong>INV</strong> RDM STEP CONTROLLER SETTINGS<br />

Site Setting<br />

Value Units<br />

Factory Setting<br />

Value<br />

Low High Default<br />

Parameter Name<br />

Increase Delay 5 secs 10 ins 1 min 20 secs<br />

Decrease Delay 5 secs 10 ins 1 min 20 secs<br />

Number of Stages 1 10 10 3<br />

General Alarm Delay 00:00 15:00 00:10 5:00 mm:ss<br />

Capacity Delay 00:00 99:00 00:10 5:00 mm:ss<br />

Control Fault Delay 01:00 30:00 10:00 10:00 mm:ss<br />

Millenium Software Version:- <strong>MSP</strong>50-100-<strong>INV</strong><br />

Millenium Controller Inputs and Outputs<br />

Input Input Type Application Output Output Application Control<br />

Type<br />

Voltage<br />

I1 Digital Exit Backup O1 Relay Backup Signal 24V 50Hz<br />

I2 Digital Enter Backup O2 Relay 24V 50Hz<br />

I3 N/A O3 Relay 24V 50Hz<br />

I4 N/A O4 Relay 24V 50Hz<br />

I5 Analogue Discharge Transducer O5 Relay Load Compressors Signal 24V 50Hz<br />

I6 Analogue Suction Transducer O6 Relay Unload Compressors Signal 24V 50Hz<br />

I7 Analogue Wet Tech Sensor O7 Relay Wet Tech Alarm<br />

24V 50Hz<br />

I8 N/A<br />

O8 Relay 24V 50Hz<br />

I9 N/A<br />

I10 N/A<br />

I11 N/A<br />

I12<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4-38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4-38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4-38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 Default<br />

P-86 Response Off 1-15 1 10 Default<br />

P-04 -60 1 6 10<br />

P-05 Optomise Limit -3.4-38.6 1 30 Default<br />

P-80 Startup delay 0-5 Mins 1 0 Default<br />

P-82 Run Smallest 0=Off 1=On 1 0 Default<br />

P-98 Probe Offset -50<br />

-3.4-38.6<br />

-3.4-38.6<br />

o C 70 o Min/Sec<br />

o<br />

C 0.1 C 0 Default<br />

P-13 HP Alarm Pressure 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure 0.1 BAR 0.2 1.5<br />

P-15 -3.4-38.6 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0-99 1 Min/Sec 3 Mins Default<br />

P-81 0-60 Mins 1 Min/Sec 4 Mins 45 Mins<br />

P-22 Stage 2 Type Compressor<br />

P-23 Stage 3 Type Loader<br />

P-24 Stage 4 Type (0) None<br />

Compressor<br />

P-25 Stage 5 Type (1)Unused<br />

Unused<br />

P-26 Stage 6 Type (2)Compressor<br />

P-27 Stage 7 Type (3)Loader<br />

P-28 Stage 8 Type (4)Fan<br />

P-29 Stage 9 Type<br />

P-30 Stage 10 Type<br />

P-51 Stage 1 Size 19.2<br />

P-52 Stage 2 Size 17.5<br />

P-53 Stage 3 Size 17.5<br />

P-54 Stage 4 Size<br />

45.8<br />

P-55 Stage 5 Size<br />

0-60<br />

P-56 Stage 6 Size<br />

P-57 Stage 7 Size<br />

P-58 Stage 8 Size<br />

P-59 Stage 9 Size<br />

P-60 Stage 10 Size<br />

P-41 Stage 1 Input Type N/O Compressor 1<br />

P-42 Stage2 Input Type N/O Compressor 2<br />

P-43 Stage 3 Input Type N/O Compressor 2<br />

P-44 Stage 4 Input Type<br />

(0)N/O<br />

N/O<br />

Compressor 3<br />

P-45 Stage 5 Input Type Unused<br />

(1)N/C<br />

P-46 Stage 6 Input Type N/O Liquid Level<br />

(2)Unused<br />

P-47 Stage 7 Input Type N/O Moisture Detected<br />

P-48 Stage 8 Input Type N/O <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type<br />

P-50 Stage 10 Input Type<br />

Issue 3 Page - 55 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

RDM PACK & CONDENSER CONT <strong>MSP</strong>080-<strong>INV</strong><br />

<strong>MSP</strong>-080-630-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

09/03/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

6<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE


This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 6. Wiring Diagrams<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Pack Controller Settings<br />

No. Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure FALSE 0.1 BAR 2 3.5<br />

P-02 Transducer Span FALSE 0.1 BAR 13 18<br />

P-03 Transducer Offset FALSE 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 Default<br />

P-86 Response Off 1-15 1 10 Default<br />

P-04 Number of Starts/hr --60 1 6 10<br />

P-05 Optimise Limit -50-560 1 30 Default<br />

P-80 Startup delay 0-5 Mins 1 Min/Sec 0 Default<br />

<strong>MSP</strong>050/060-<strong>INV</strong> RDM STEP CONTROLLER SETTINGS<br />

Site Setting<br />

Value Units<br />

Factory Setting<br />

Value<br />

Low High Default<br />

Parameter Name<br />

Increase Delay 5 secs 10 ins 1 min 20 secs<br />

Decrease Delay 5 secs 10 ins 1 min 20 secs<br />

Number of Stages 1 10 10 3<br />

General Alarm Delay 00:00 15:00 00:10 5:00 mm:ss<br />

Capacity Delay 00:00 99:00 00:10 5:00 mm:ss<br />

Control Fault Delay 01:00 30:00 10:00 10:00 mm:ss<br />

Millenium Controller Inputs and Outputs<br />

Input Input Type Application Output Output Application Control Voltage<br />

Type<br />

I1 Digital Exit Backup O1 Relay Backup Signal 24V 50Hz<br />

I2 Digital Enter Backup O2 Relay 24V 50Hz<br />

I3 N/A O3 Relay 24V 50Hz<br />

I4 N/A O4 Relay 24V 50Hz<br />

I5 Analogue Discharge Transducer O5 Relay Load Compressors Signal 24V 50Hz<br />

I6 Analogue Suction Transducer O6 Relay Unload Compressors Signal 24V 50Hz<br />

I7 Analogue Wet Tech Sensor O7 Relay Wet Tech Alarm<br />

24V 50Hz<br />

I8 N/A<br />

O8 Relay 24V 50Hz<br />

I9 N/A<br />

I10 N/A<br />

I11 N/A<br />

I12<br />

P-82 Run Smallest 0=Off 1=On 1 0 Default<br />

P-98 Probe Offset -50 o C 70 o o<br />

C 0.1 C 0 Default<br />

P-13 HP Alarm Pressure FALSE 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure FALSE 0.1 BAR 0.2 1.5<br />

P-15 Shut Down Pressure FALSE 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0-99 1 Min/Sec 3 Mins Default<br />

P-81 General Alarm Delay 0-60 Mins 1 Min/Sec 4 Mins 45 Mins<br />

P-22 Stage 2 Type Compressor<br />

P-23 Stage 3 Type Loader<br />

P-24 Stage 4 Type (0) None<br />

Compressor<br />

P-25 Stage 5 Type (1)Unused<br />

Unused<br />

P-26 Stage 6 Type (2)Compressor<br />

P-27 Stage 7 Type (3)Loader<br />

P-28 Stage 8 Type (4)Fan<br />

P-29 Stage 9 Type<br />

P-30 Stage 10 Type<br />

P-51 Stage 1 Size 17.5<br />

P-52 Stage 2 Size 17.7<br />

P-53 Stage 3 Size 17.7<br />

P-54 Stage 4 Size<br />

47.2<br />

P-55 Stage 5 Size<br />

0-60<br />

P-56 Stage 6 Size<br />

P-57 Stage 7 Size<br />

P-58 Stage 8 Size<br />

P-59 Stage 9 Size<br />

P-60 Stage 10 Size<br />

P-41 Stage 1 Input Type N/O Compressor 1<br />

P-42 Stage2 Input Type N/O Compressor 2<br />

P-43 Stage 3 Input Type N/O Compressor 2<br />

P-44 Stage 4 Input Type N/O<br />

(0)N/O<br />

Compressor 3<br />

P-45 Stage 5 Input Type Unused<br />

(1)N/C<br />

P-46 Stage 6 Input Type N/O Liquid Level<br />

(2)Unused<br />

P-47 Stage 7 Input Type N/O Moisture Detected<br />

P-48 Stage 8 Input Type N/O <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type<br />

P-50 Stage 10 Input Type<br />

Issue 3 Page - 56 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

Millenium Software Version:- <strong>MSP</strong>50-100-<strong>INV</strong><br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

01<br />

RDM PACK & CONDENSER CONT <strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>-100-630-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

01/06/06 1:1<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

EW<br />

EW<br />

ISS MODIFICATION SCN DATE<br />

6


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

Issue 3 Page - 57 -<br />

September 2007<br />

7. Controls Logic INDEX<br />

Page No’s Issue No<br />

7.1 Compressor Sequencing 58 1<br />

7.1.1 Main Control – RDM Controller 58 1<br />

7.1.2 Backup Control, all units 58 1<br />

7.2 Compressor Safety Pressure Switches 59 1<br />

7.3 Controller Settings<br />

7.3.1 <strong>MSP</strong>050-<strong>INV</strong> Main Controller 60 1<br />

7.3.2 <strong>MSP</strong>060-<strong>INV</strong> Main Controller 61 1<br />

7.3.3 <strong>MSP</strong>080-<strong>INV</strong> Main Controller 62 1<br />

7.3.4 <strong>MSP</strong>100-<strong>INV</strong> Main Controller 63 1<br />

7.3.5 <strong>MSP</strong> Comp Backup Controller (RDM) 64 1<br />

7.3.6 <strong>MSP</strong> Main Controller Alarm Alias’s 64 1<br />

7.3.7 Millenium Backup Controller 64 1<br />

7.3.7.1 Millenium Control General 64 1<br />

7.3.7.2 Millenium Setting Adjustment 65 1<br />

7.3.7.3 Millenium Controller Factory Settings 65 1<br />

7.4 <strong>MSP</strong>-<strong>INV</strong>, MSHP, <strong>MSP</strong>L <strong>Inverter</strong> Settings 66 � 70 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.1 Compressor Sequencing<br />

Issue 3 Page - 58 -<br />

September 2007<br />

The <strong>MSP</strong>-<strong>INV</strong> range consists of 4 models, each with nominal capacities of 50, 60, 80 and 100 kw, fitted<br />

with RDM Mercury controls, hence named <strong>MSP</strong>050-<strong>INV</strong>, <strong>MSP</strong>60-<strong>INV</strong>, <strong>MSP</strong>80-<strong>INV</strong>, <strong>MSP</strong>100-<strong>INV</strong>.<br />

The controls are effectively the same for all three units, with the only difference being the <strong>MSP</strong>080 and<br />

100, which include a Cylinder Head unloader on the second compressor.<br />

All main controls are 24V AC 50Hz.<br />

Units also incorporate 240V and 415V Components.<br />

7.1.1 Main Control – RDM Controller<br />

The main control for <strong>MSP</strong>–<strong>INV</strong> unit’s compressor sequencing is the RDM Mercury 11-10V controller. The<br />

controller monitors the suction pressure transducer, it outputs a 0-10V signal to the inverter which runs<br />

the first compressor’s speed from 20Hz to 60Hz in response to the suction pressure changes.<br />

When the first compressor is running at full speed the controller stages in the second and third<br />

compressors as required to achieve the required duty. When a new compressor stage is bought in the<br />

inverter compressor drops back to minimum speed, and then modulates as required.<br />

Compressors 2 and 3 are fixed single speed units.<br />

Compressor control is achieved using the ‘Section 1’ parameters of the controller.<br />

The controller is factory set to maintain a suction pressure of 3.5 Barg (-9°C R404A).<br />

The RDM controller uses ‘Fuzzy-Logic’ to determine which compressors to run based on their equivalent<br />

size and deviation from the measured pressure to the set point.<br />

Fig. 8 RDM Main control<br />

7.1.2 Backup Control, all units<br />

Should the main controller fail or if the millennium controller detects an out of range suction pressure the<br />

backup controller is initiated and control transferred over from the main controller.<br />

The compressor backup controller uses an RDM step controller type 6-10.<br />

RDM 6-10 : the controller receives a signal from the Millennium controller to Stage Down or Stage Up.<br />

When a Stage up signal is received the next compressor stage is brought in after the delay on time,<br />

when a stage down signal is received the last compressor stage running is brought out after the delay<br />

off time.<br />

Compressors are sequenced in a simple 1 on, 2 on, 3 on manner with the first inverter compressor being<br />

run at 100% full speed.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

Issue 3 Page - 59 -<br />

September 2007<br />

Fig. 9 RDM Backup<br />

7.2 Compressor Safety Pressure Switches<br />

All compressors are protected by a pair of safety pressure switches directly mounted to the compressor<br />

heads. The LP switch (200-404-031), will cut the compressor out at 0.7 BarG, and cut back in at 2.2<br />

BarG. The HP switch (200-404-032), will cut the compressor out at 22.0 BarG, and cut back in at 16.0<br />

BarG. Both switches are Auto-Reset.<br />

Compressors fitted with an oil pump are also protected with a Oil Pressure monitoring sensor.<br />

(<strong>MSP</strong>100 = 2 & 3, <strong>MSP</strong>080 = Comp 3, <strong>MSP</strong>060 & <strong>MSP</strong>050 no oil sensors), this device monitors the pump<br />

outlet pressure and trips out should the pressure fall below a set level. The device is factory set and can<br />

not be adjusted. Should an Oil Differential switch trip a manual reset is required.<br />

In addition to this, all compressors are protected by a combined HP/LP switch, which trips should the<br />

unit try to operate outside of its application envelope.<br />

All compressor switches are directly mounted to the compressor HP and LP connections They are<br />

connected to the relevant compressor via a ¼” Schraeder connection.<br />

Should a switch require replacement or disconnection follow the procedure in 4.5.2 on page 21.<br />

Note : When removing a pressure switch from the compressor body take care not to unscrew the<br />

1/8” NPT to 1/4" flare adapter beneath the hose connection.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.3 Controller Settings<br />

7.3.1 <strong>MSP</strong>050-<strong>INV</strong> Main Controller Settings<br />

Issue 3 Page - 60 -<br />

September 2007<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4 – 38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4 – 38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4 – 38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 10<br />

P-86 Response Off 1-15 1 10 10<br />

P-04 Number of Starts/hr 0 - 60 1 6 10<br />

P-05 Optimise Limit -3.4 – 38.6 1 BAR 2 2<br />

P-80 Startup Delay 0 - 5 mins 1 mins/sec 0 0<br />

P-82 Run Smallest 0 = off, 1 = on 1 0 0<br />

P-98 Probe Offset -50°C - 70°C 0.1 °C 0 0<br />

P-13 HP Alarm Pressure -3.4 – 38.6 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure -3.4 – 38.6 0.1 BAR 0.2 1.5<br />

P-15 LP Shut-down Pressure -3.4 – 38.6 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0 - 99 1 mins 3 3<br />

P-81 General Alarm Delay 0 - 60 mins 1 mins/sec 4 45<br />

P-22 Stage 2 Type (0) None, 0 2 (Comp)<br />

P-23 Stage 3 Type (1) Unused, 0 2 (Comp)<br />

P-24 Stage 4 Type (2) Compressor, 0 1<br />

P-25 Stage 5 Type (3) Loader, 0 1<br />

P-26 Stage 6 Type (4) Fan 0 0<br />

P-27 Stage 7 Type 0 0<br />

P-28 Stage 8 Type 0 0<br />

P-29 Stage 9 Type 0 0<br />

P-30 Stage 10 type 0 0<br />

P-51 Stage 1 Size 0-60 1 0 19.8<br />

P-52 Stage 2 size 0 25<br />

P-53 Stage 3 size 0 55.3<br />

P-54 Stage 4 size 0 0<br />

P-55 Stage 5 size 0 0<br />

P-56 Stage 6 size 0 0<br />

P-57 Stage 7 size 0 0<br />

P-58 Stage 8 size 0 0<br />

P-59 Stage 9 size 0 0<br />

P-60 Stage 10 size 0 0<br />

P-41 Stage 1 Input Type (0) N/O 2 0 Compressor 1<br />

P-42 Stage 2 Input Type (1) N/C 2 0 Compressor 2<br />

P-43 Stage 3 Input Type (2) Unused, 2 0 Compressor 3<br />

P-44 Stage 4 Input Type 2 2<br />

P-45 Stage 5 Input Type 2 2<br />

P-46 Stage 6 Input Type 2 0 Liquid Level<br />

P-47 Stage 7 Input Type 2 0 Moisture Detected<br />

P-48 Stage 8 Input Type 2 0 <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type 2 2<br />

P-50 Stage 10 Input Type 2 2<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.3.2 <strong>MSP</strong>060-RDM Main Controller Settings<br />

Issue 3 Page - 61 -<br />

September 2007<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4 – 38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4 – 38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4 – 38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 10<br />

P-86 Response Off 1-15 1 10 10<br />

P-04 Number of Starts/hr 0 - 60 1 6 10<br />

P-05 Optimise Limit -3.4 – 38.6 1 BAR 2 2<br />

P-80 Startup Delay 0 - 5 mins 1 mins/sec 0 0<br />

P-82 Run Smallest 0 = off, 1 = on 1 0 0<br />

P-98 Probe Offset -50°C - 70°C 0.1 °C 0 0<br />

P-13 HP Alarm Pressure -3.4 – 38.6 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure -3.4 – 38.6E 0.1 BAR 0.2 1.5<br />

P-15 LP Shut-down Pressure -3.4 – 38.6 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0 - 99 1 mins 3 3<br />

P-81 General Alarm Delay 0 - 60 mins 1 mins/sec 4 45<br />

P-22 Stage 2 Type (0) None, 0 2 (Comp)<br />

P-23 Stage 3 Type (1) Unused, 0 2 (Comp)<br />

P-24 Stage 4 Type (2) Compressor, 0 1<br />

P-25 Stage 5 Type (3) Loader, 0 1<br />

P-26 Stage 6 Type (4) Fan 0 0<br />

P-27 Stage 7 Type 0 0<br />

P-28 Stage 8 Type 0 0<br />

P-29 Stage 9 Type 0 0<br />

P-30 Stage 10 type 0 0<br />

P-51 Stage 1 Size 0-60 1 0 21<br />

P-52 Stage 2 size 0 25.6<br />

P-53 Stage 3 size 0 53.4<br />

P-54 Stage 4 size 0 0<br />

P-55 Stage 5 size 0 0<br />

P-56 Stage 6 size 0 0<br />

P-57 Stage 7 size 0 0<br />

P-58 Stage 8 size 0 0<br />

P-59 Stage 9 size 0 0<br />

P-60 Stage 10 size 0 0<br />

P-41 Stage 1 Input Type (0) N/O 2 0 Compressor 1<br />

P-42 Stage 2 Input Type (1) N/C 2 0 Compressor 2<br />

P-43 Stage 3 Input Type (2) Unused, 2 0 Compressor 3<br />

P-44 Stage 4 Input Type 2 2<br />

P-45 Stage 5 Input Type 2 2<br />

P-46 Stage 6 Input Type 2 0 Liquid Level<br />

P-47 Stage 7 Input Type 2 0 Moisture Detected<br />

P-48 Stage 8 Input Type 2 0 <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type 2 2<br />

P-50 Stage 10 Input Type 2 2<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.3.3 <strong>MSP</strong>080-RDM Main Controller Settings<br />

Issue 3 Page - 62 -<br />

September 2007<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4 – 38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4 – 38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4 – 38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 10<br />

P-86 Response Off 1-15 1 10 10<br />

P-04 Number of Starts/hr 0 - 60 1 6 10<br />

P-05 Optimise Limit -3.4 – 38.6 1 BAR 2 2<br />

P-80 Startup Delay 0 - 5 mins 1 mins/sec 0 0<br />

P-82 Run Smallest 0 = off, 1 = on 1 0 0<br />

P-98 Probe Offset -50°C - 70°C 0.1 °C 0 0<br />

P-13 HP Alarm Pressure -3.4 – 38.6 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure -3.4 – 38.6 0.1 BAR 0.2 1.5<br />

P-15 LP Shut-down Pressure -3.4 – 38.6 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0 - 99 1 mins 3 3<br />

P-81 General Alarm Delay 0 - 60 mins 1 mins/sec 4 45<br />

P-22 Stage 2 Type (0) None, 0 2 (Comp)<br />

P-23 Stage 3 Type (1) Unused, 0 3 (Loader)<br />

P-24 Stage 4 Type (2) Compressor, 0 2 (Comp)<br />

P-25 Stage 5 Type (3) Loader, 0 1<br />

P-26 Stage 6 Type (4) Fan 0 0<br />

P-27 Stage 7 Type 0 0<br />

P-28 Stage 8 Type 0 0<br />

P-29 Stage 9 Type 0 0<br />

P-30 Stage 10 type 0 0<br />

P-51 Stage 1 Size 0-60 1 0 19.2<br />

P-52 Stage 2 size 0 17.5<br />

P-53 Stage 3 size 0 17.5<br />

P-54 Stage 4 size 0 45.8<br />

P-55 Stage 5 size 0 0<br />

P-56 Stage 6 size 0 0<br />

P-57 Stage 7 size 0 0<br />

P-58 Stage 8 size 0 0<br />

P-59 Stage 9 size 0 0<br />

P-60 Stage 10 size 0 0<br />

P-41 Stage 1 Input Type (0) N/O 2 0 Compressor 1<br />

P-42 Stage 2 Input Type (1) N/C 2 0 Compressor 2<br />

P-43 Stage 3 Input Type (2) Unused, 2 0 Compressor 2<br />

P-44 Stage 4 Input Type 2 0 Compressor 3<br />

P-45 Stage 5 Input Type 2 2<br />

P-46 Stage 6 Input Type 2 0 Liquid Level<br />

P-47 Stage 7 Input Type 2 0 Moisture Detected<br />

P-48 Stage 8 Input Type 2 0 <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type 2 2<br />

P-50 Stage 10 Input Type 2 2<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.3.4 <strong>MSP</strong>100 Main Controller Settings<br />

Issue 3 Page - 63 -<br />

September 2007<br />

Number Parameter Range Step Units Default Factory Setting Site Setting<br />

P-01 Target Pressure -3.4 – 38.6 0.1 BAR 2 3.5<br />

P-02 Transducer Span -3.4 – 38.6 0.1 BAR 13 18<br />

P-03 Transducer Offset -3.4 – 38.6 0.1 BAR 0 0<br />

P-85 Response On 1-15 1 10 10<br />

P-86 Response Off 1-15 1 10 10<br />

P-04 Number of Starts/hr 0 - 60 1 6 10<br />

P-05 Optimise Limit -3.4 – 38.6 1 BAR 2 2<br />

P-80 Startup Delay 0 - 5 mins 1 mins/sec 0 0<br />

P-82 Run Smallest 0 = off, 1 = on 1 0 0<br />

P-98 Probe Offset -50°C - 70°C 0.1 °C 0 0<br />

P-13 HP Alarm Pressure -3.4 – 38.6 0.1 BAR 4.1 7.5<br />

P-14 LP Alarm Pressure -3.4 – 38.6 0.1 BAR 0.2 1.5<br />

P-15 LP Shut-down Pressure -3.4 – 38.6 0.1 BAR 0.1 1.2<br />

P-16 Alarm Delay 0 - 99 1 mins 3 3<br />

P-81 General Alarm Delay 0 - 60 mins 1 mins/sec 4 45<br />

P-22 Stage 2 Type (0) None, 0 2 (Comp)<br />

P-23 Stage 3 Type (1) Unused, 0 3 (Loader)<br />

P-24 Stage 4 Type (2) Compressor, 0 2 (Comp)<br />

P-25 Stage 5 Type (3) Loader, 0 1<br />

P-26 Stage 6 Type (4) Fan 0 0<br />

P-27 Stage 7 Type 0 0<br />

P-28 Stage 8 Type 0 0<br />

P-29 Stage 9 Type 0 0<br />

P-30 Stage 10 type 0 0<br />

P-51 Stage 1 Size 0-60 1 0 17.5<br />

P-52 Stage 2 size 0 17.7<br />

P-53 Stage 3 size 0 17.7<br />

P-54 Stage 4 size 0 47.2<br />

P-55 Stage 5 size 0 0<br />

P-56 Stage 6 size 0 0<br />

P-57 Stage 7 size 0 0<br />

P-58 Stage 8 size 0 0<br />

P-59 Stage 9 size 0 0<br />

P-60 Stage 10 size 0 0<br />

P-41 Stage 1 Input Type (0) N/O 2 0 Compressor 1<br />

P-42 Stage 2 Input Type (1) N/C 2 0 Compressor 2<br />

P-43 Stage 3 Input Type (2) Unused, 2 0 Compressor 2<br />

P-44 Stage 4 Input Type 2 0 Compressor 3<br />

P-45 Stage 5 Input Type 2 2<br />

P-46 Stage 6 Input Type 2 0 Liquid Level<br />

P-47 Stage 7 Input Type 2 0<br />

Moisture<br />

Detected<br />

P-48 Stage 8 Input Type 2 0 <strong>Inverter</strong> Fault<br />

P-49 Stage 9 Input Type 2 2<br />

P-50 Stage 10 Input Type 2 2<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

7.3.5 <strong>MSP</strong> Compressor Backup Controller (RDM Stepper) – All Units<br />

Issue 3 Page - 64 -<br />

September 2007<br />

Parameter Name Low High Default Factory Setting Value Site Setting Value Units<br />

Increase Delay 5 secs 10 ins 1 min 20 secs<br />

Decrease Delay 5 secs 10 ins 1 min 20 secs<br />

Number of Stages 1 10 10 3<br />

General Alarm Delay 00:00 15:00 00:10 5:00 mm:ss<br />

Capacity Delay 00:00 99:00 00:10 5:00 mm:ss<br />

Control Fault Delay 01:00 30:00 10:00 10:00 mm:ss<br />

7.3.6 <strong>MSP</strong> Main Controller Alarm Alias’s (RDM) – All Units<br />

All <strong>MSP</strong> main controllers are factory set with the alarm names or ‘Aliases’ as shown in the tables above,<br />

these relate to the controller input that the alarm is ‘hard-wired’ into.<br />

To simplify identification it is recommended that these alarm Aliases are changed to reflect the nature of<br />

the alarm. This can be done on the Front End Data Director terminal, via the set-up options.<br />

Alarm aliases are as follows :<br />

RDM Controller Reading Alarm Delay Function<br />

(Factory Setting)<br />

(New Alarm Alias)<br />

Section 1 Stage 1 None Compressor No 1 Fault<br />

Section 1 Stage 2 None Compressor No 2 Fault<br />

Section 1 Stage 3 None Compressor No 3 Fault<br />

General Fault 1 45 Mins Low Liquid Level<br />

General Fault 2 45 Mins Moisture Detected<br />

Important : Changes to the Front End information must only be made by authorised<br />

personnel, if in doubt please contact RDM.<br />

The ‘Run Smallest’ setting in the compressor controls options should not be enabled as it<br />

will continue to hold off all other compressors if compressor 1 is held out on it’s anti cycle<br />

timer. This will cause the backup system to intervene and flag up an alarm on the network.<br />

The settings shown in this document must be adhered to, changes to the controller settings<br />

that cause undesirable operation will invalidate the unit warranty.<br />

7.3.7 Millennium Backup Controller<br />

7.3.7.1 General<br />

The Controller will monitor the operation of the Pack arrangement and if the Suction or Discharge<br />

pressures stray above the pre-set limits the controller will intervene and take over control of the Pack. If<br />

and when the suction pressure returns and remains within or below the preset dead band parameters<br />

the <strong>MSP</strong> will return to main control after a period of 10 minutes. Backup can be forced in or cancelled<br />

from the Main Controls panel front switch and reset button. The moisture content of the refrigerant is<br />

also monitored via the KMC moisture sensor, commonly known as Wet Tech and the controller will<br />

provide an alarm to the main RDM controller and controls panel above a preset level.<br />

For MSHP units the controller will monitor the Housing temperature and run the Unit Cooler if required.<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

Issue 3 Page - 65 -<br />

September 2007<br />

Millennium Controller Inputs and Outputs<br />

Input Input Type Application Output Output<br />

Type<br />

Application Control Voltage<br />

I1 Digital Exit Backup O1 Relay Backup Signal 24V DC<br />

I2 Digital Enter Backup O2 Relay 24V 50Hz<br />

I3 N/A O3 Relay 24V 50Hz<br />

I4 N/A O4 Relay 24V 50Hz<br />

I5 Analogue Discharge Transducer O5 Relay Load Compressors Signal RDM Control<br />

I6 Analogue Suction Transducer O6 Relay Unload Compressors Signal RDM Control<br />

I7 Analogue Wet Tech Sensor O7 Relay Wet Tech Alarm 24V 50Hz<br />

I8 N/A<br />

I9 N/A<br />

I10 N/A<br />

I11 N/A<br />

I12 N/A<br />

7.3.7.2 Millenium Controller Settings Adjustment<br />

The Controller Default Settings may entered at any time by pressing the buttons + and – at the same<br />

time. To adjust the parameter values press and hold down button A for 5 seconds. Use either the + or –<br />

buttons to alter the settings, and then press OK to move to the next parameter. To exit press the Esc<br />

button, the controller will exit the setting mode after 3 minutes automatically, see Fig. 10.<br />

Fig. 10<br />

The fixed and adjustable settings are shown below.<br />

‘+’ Button : Raise Parameter setting<br />

OK Button : Move to next Parameter<br />

‘-’ Button : Lower Parameter setting<br />

(Hold both + & - to restore Factory Defaults)<br />

ESC Button : Exit Parameter Setup<br />

Button B : No Function<br />

Button A : Enter Parameter Setup<br />

(Hold for 5 seconds)<br />

7.3.7.3 Millenium Controller Factory Settings<br />

Parameter Max Min Default/Fixed Type Remarks<br />

Backup entry delay from pressure fault NA NA 20 Seconds Fixed (No delay from Panel Switches)<br />

Backup Exit Delay Time NA NA 10 Minutes Fixed (No delay from Panel Switches)<br />

Suction Set point 5 2 3.5 Bar Adjustable<br />

Suction Dead Band 2 0.3 1 Bar Adjustable<br />

Suction Override Set Point NA NA SP +3.5 Bar Default Setting 7 Bar<br />

Wet Tech Set Point 100 10 44 Factor Adjustable<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

7


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

Issue 3 Page - 66 -<br />

September 2007<br />

7.4 <strong>MSP</strong>-<strong>INV</strong> <strong>Inverter</strong> Settings<br />

Please note : All parameters are identical for all unit sizes EXCEPT parameters 102 & 105, which are<br />

model dependent. Parameters shown in Grey are Default Settings.<br />

AKD type code: AKD5011 (<strong>MSP</strong>050 & 060), AKD5016 (<strong>MSP</strong>080 & 100) AK FC bus address: 2<br />

Application: Lead compressor control on <strong>Searle</strong> CCU-ECI units<br />

Parameter<br />

number<br />

Parameter description<br />

Operation and display Factory setting Setup 1 Factory Set up Setting<br />

001 Language English<br />

002 Local/remote control Remote control<br />

003 Local reference 30.0<br />

004 Active setup Setup 1 Multi Setup<br />

005 Programming setup Active setup<br />

006 Copying of setups No copying Copy from 1 to 2<br />

007 LCP copy No copying<br />

008 Display scaling of motor frequency 1<br />

009 Display line 2 Frequency [Hz]<br />

010 Display line 1.1 Reference [%]<br />

011 Display line 1.2 Motor current [A]<br />

012 Display line 1.3 Power [kW]<br />

013 Local control/configuration LCP digital control/as par 100<br />

014 Local stop Possible Disabled (After Setup)<br />

017 Local reset of trip Possible Enable<br />

018 Lock for data change Not locked Lock (After Setup)<br />

019 Power up Action Auto Restart Auto Restart<br />

Load and motor Factory setting Setup 1 Factory Set up Setting<br />

100 Configuration Speed control, open loop Speed Open Loop Open Loop 0<br />

101 Torque characteristics High - constant torque H-Constant Torque High C/T<br />

CCU050= 5.4kW<br />

1<br />

102 Motor power Depends on the unit Nameplate kW<br />

CCU060= 6.4kW<br />

CCU080= 8.0kW<br />

CCU100= 9.0kW<br />

103 Motor voltage Depends on the unit 400V Nameplate 415Volts<br />

104 Motor frequency 50 Hz / 60 Hz 50Hz Nameplate 50Hz<br />

CCU050=9.2A<br />

105 Motor current Depends on the unit Amps Nameplate<br />

CCU060=10.7A<br />

CCU080=13.5A<br />

CCU100=15.9A<br />

106 Rated motor speed Depends on the unit RPM Nameplate<br />

Run Adaptation<br />

1440rpm<br />

107 Automatic motor adaptation, AMA Adaptation off<br />

during commissioning<br />

108 Stator resistor Depends on the unit<br />

109 Stator reactance Depends on the unit<br />

113 Load compensation, low speed 100%<br />

114 Load compensation, high speed 100%<br />

115 Slip compensation 0%<br />

116 Slip compensation, time constant 0.5 sec<br />

117 Resonance Damp 100%<br />

118 Damp time constant<br />

120 Start Delay 0<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

121 Coast/Delay time start function<br />

122 Function at stop Coasting<br />

123 Min F Func Stop 0.00Hz<br />

124 DC holding current 0%<br />

125 DC braking current 50 %<br />

126 DC braking time 10.0 sec.<br />

127 DC brake cut-in frequency Off<br />

128 Motor thermal protection No protection No protection<br />

130 Start Frequency 0%<br />

131 Initial Voltage 0V<br />

Issue 3 Page - 67 -<br />

September 2007<br />

References and limits Factory setting Setup 1 Factory Set up Setting<br />

201 Output frequency low limit 30.0 Hz 30 Hz 20Hz<br />

202 Output frequency high limit 60.0 Hz 60 Hz 60Hz<br />

204 Minimum reference 30.0 Hz 0.000Hz 20Hz<br />

205 Maximum reference 60.0 Hz 60 Hz 60Hz<br />

207 Ramp-up time 1 0.7 sec. 5 sec 3sec<br />

208 Ramp-down time 1 1.0 sec. 5 sec 1sec<br />

209 Ramp-up time 2 5s<br />

210 Ramp-down time 2 1s<br />

211 Jog Ramp time 1s<br />

213 Jog Frequency 0.1Hz<br />

214 Reference function Sum External/Preset<br />

215 Preset reference 1 0.00 % 66% (Typical)<br />

216 Preset reference 2 0.00 %<br />

217 Preset reference 3 0.00 %<br />

218 Preset reference 4 0.00 %<br />

221 Torq. Limit motor 160% 110-180% 152<br />

223 Warning: Low Current 0.0 A 5.0A<br />

224 Warning: High current I,AKD,MAX (Maximum AKD "Amp")<br />

225 Warning: Low frequency 0 Hz 0 Hz<br />

226 Warning: High frequency 132 Hz 92<br />

227 Warning: Low feedback -4000.000<br />

228 Warning: High feedback 4000.000<br />

229 Frequency bypass, bandwidth OFF<br />

230 Frequency bypass 1 0.0 Hz<br />

231 Frequency bypass 2 0.0 Hz<br />

232 Frequency bypass 3 0.0 Hz<br />

233 Frequency bypass 4 0.0 Hz<br />

234 Motor Phase Monitor Enable<br />

Inputs and outputs Factory setting Setup 1 Factory Set up Setting<br />

300 Terminal 16, input No function [0] Reset<br />

301 Terminal 17, input No function [0]<br />

302 Terminal 18, start, input Start Start<br />

303 Terminal 19, input No Function<br />

304 Terminal 27, input Quick stop inverse [0] Coast Inverse<br />

305 Terminal 29, input No Function<br />

306 Terminal 32, input No function [0] Preset Reference On<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

307 Terminal 33, input Reset<br />

Setup Select LSB<br />

Speed Down<br />

308 Terminal 53, analogue input voltage Reference Reference<br />

Issue 3 Page - 68 -<br />

September 2007<br />

309 Terminal 53, min. scaling 0.0 V 0.0 V 0 volt<br />

310 Terminal 53, max. scaling 10.0 V 10.0 V 10 volt<br />

311 Terminal 54, analogue input voltage Thermistor No Function<br />

312 Terminal 54, min. scaling 0.0 V<br />

313 Terminal 54, max. scaling 10.0 V<br />

314 Terminal 60, analogue input current Reference<br />

315 Terminal 60, min. scaling 0.0 mA<br />

316 Terminal 60, max. scaling 20.0 mA<br />

317 Live zero time out 10 sec.<br />

318 Function after time out Freeze output [1]<br />

319 Terminal 42, output No function [0] Above Frequency Low<br />

Out Current Range<br />

321 Terminal 45, output No function [0]<br />

(Digital)<br />

323 Relay 01, output Ready signal [2] Alarm/Warning<br />

324 Relay 1-3 on delay 0.0 sec 60.0 sec<br />

325 Relay 1-3 off delay 0.0 sec 1.0 sec<br />

326 Relay 04, output Unit Ready/REM CTRL Alarm/Warning<br />

Special functions Factory setting Setup 1 Factory Set up Setting<br />

405 Reset function Automatic x 3 [3] Automatic x 3 [3]<br />

406 Automatic restart function 5 min<br />

407 Mains Failure No Function<br />

408 N/A<br />

409 Trip delay torq. OFF 15-30 sec (or as required) 20<br />

411 Switch frequency Depends on unit Factory Default 3.0 kHz<br />

Output frequency dependent switching<br />

412 frequency Disable<br />

414 Minimum feedback 0.000<br />

415 Maximum feedback 1500.000<br />

416 Process unit Bar<br />

422 U 0 voltage at 0 Hz 20.0 V<br />

423 U 1 voltage parameter 103<br />

424 F 1 frequency parameter 104<br />

425 U 2 voltage parameter 103<br />

426 F 2 frequency parameter 104<br />

427 U 3 voltage parameter 103<br />

428 F 3 frequency parameter 104<br />

429 U 4 voltage parameter 103<br />

430 F 4 frequency parameter 104<br />

431 U 5 voltage parameter 103<br />

432 F5 frequency parameter 104<br />

437 Process PID Normal/inverse control Normal<br />

438 Process PID anti windup On<br />

439 Process PID start frequency 0.0 Hz<br />

440 Process PID proportional gain 0.01<br />

441 Process PID integral time OFF<br />

444 Process PID lowpass filter time 0.01<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

445 Flying start Enable<br />

446 Switch Pattern SFAVM<br />

Issue 3 Page - 69 -<br />

September 2007<br />

Serial communications Factory setting Setup 1 Factory Set up Setting<br />

500 Address 1 2 2<br />

507 Selection of setup Logic or<br />

513 Bus time interval 1sec.<br />

514 Bus time interval function Off<br />

515 Data read-out: Reference % Via Lon or par 009-012<br />

516 Data read-out: Reference unit Via Lon or par 009-012<br />

517 Data read-out: Feedback Via Lon or par 009-012<br />

518 Data read-out: Frequency Via Lon or par 009-012<br />

520 Data read-out: Current Via Lon or par 009-012<br />

522 Data read-out: Power, kW Via Lon or par 009-012<br />

523 Data read-out: Power, HP Via Lon or par 009-012<br />

524 Data read-out: Motor voltage Via Lon or par 009-012<br />

525 Data read-out: DC link voltage Via Lon or par 009-012<br />

526 Data read-out: Motor temp. Via Lon or par 009-012<br />

527 Data read-out: AKD temp. Via Lon or par 009-012<br />

528 Data read-out: Digital input Via Lon or par 009-012<br />

Data read-out: Terminal 53, analogue<br />

529 input Via Lon or par 009-012<br />

Data read-out: Terminal 54, analogue<br />

530 input Via Lon or par 009-012<br />

Data read-out: Terminal 60, analogue<br />

531 input Via Lon or par 009-012<br />

533 Data read-out: External reference % Via Lon or par 009-012<br />

534 Data read-out: Status word, binary Par 009-012<br />

537 Data read-out: Heat sink temperature Via Lon or par 009-012<br />

538 Data read-out: Alarm word, binary Par 009-012<br />

539 Data read-out: AKD control word, binary Par 009-012<br />

540 Data read-out: Warning word, 1 Par 009-012<br />

541 Data read-out: Extended status word Par 009-012<br />

557 Data read-out: Motor RPM Via Lon or par 009-012<br />

558 Data read-out: Motor RPM x scaling Via Lon or par 009-012<br />

Technical functions Factory setting Setup 1 Factory Set up Setting<br />

600 Operating data: Operating hours<br />

601 Operating data: Hours run<br />

602 Operating data: kWh counter<br />

603 Operating data: Number of power-up’s<br />

Operating data: Number of over<br />

604 temperatures<br />

605 Operating data: Number of over voltages<br />

606 Data log: Digital input<br />

607 Data log: Bus commands<br />

608 Data log: Bus status word<br />

609 Data log: Reference<br />

610 Data log: Feedback<br />

611 Data log: Motor frequency<br />

612 Data log: Motor voltage<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 7. Controls Logic<br />

613 Data log: Motor current<br />

614 Data log: DC link voltage<br />

615 Fault log: Error code<br />

616 Fault log: Time<br />

617 Fault log: Value<br />

618 Reset of kWh counter No reset<br />

619 Reset of hours-run counter No reset<br />

620 Operating mode Normal function Normal function<br />

621 Nameplate: AKD type<br />

622 Nameplate: Power section<br />

623 Nameplate: AKD ordering number<br />

624 Nameplate: Software version no.<br />

625 Nameplate: LCP identification no.<br />

626 Nameplate: Database identification no.<br />

Nameplate: Power section identification<br />

627 no.<br />

628 Nameplate: Application option type<br />

Nameplate: Application option ordering<br />

629 no.<br />

630 Nameplate: Communication option type<br />

Nameplate: Communication option<br />

631 ordering no.<br />

Issue 3 Page - 70 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

Issue 3 Page - 71 -<br />

September 2007<br />

8. Layout Diagrams INDEX<br />

Page No’s Issue No<br />

8.1 Pipework Schematics<br />

8.1.1 <strong>MSP</strong>050-<strong>INV</strong> Pipework Schematic 72 1<br />

8.1.2 <strong>MSP</strong>060-<strong>INV</strong> Pipework Schematic 73 1<br />

8.1.3 <strong>MSP</strong>080-<strong>INV</strong> Pipework Schematic 74 1<br />

8.1.4 <strong>MSP</strong>100-<strong>INV</strong> Pipework Schematic 75 1<br />

8.2 Unit Dimensions 1<br />

8.2.1 <strong>MSP</strong>050 & 060-<strong>INV</strong> Dimensions 76 1<br />

8.2.2 <strong>MSP</strong>080 & 100-<strong>INV</strong> Dimensions 77 1<br />

8.2.3 <strong>MSP</strong>L-<strong>INV</strong> Dimensions 78 1<br />

8.2.4 MSHP Housing Dimensions 79 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.1.1 <strong>MSP</strong>050-<strong>INV</strong> Pipework Schematic<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

IF IN DOUBT ASK<br />

A2 DO NOT SCALE<br />

THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

DUAL PRV<br />

(24.8 BAR)<br />

INDICATOR<br />

GAUGES<br />

CHARGING<br />

Vv<br />

TEV<br />

ORIFICE 3<br />

ROTALOCK<br />

VALVE<br />

ROTALOCK<br />

VALVE<br />

RECEIVER<br />

ASSY.<br />

FILTER DRIER &<br />

SIGHTGLASS<br />

ASSY.<br />

CCU-JG5 EVAPORATOR<br />

: IMPORTANT :<br />

THIS DRAWING SHOWS THE POSITION<br />

OF THE COMPONENTS WITHIN THE<br />

REFRIGERATION SYSTEM. IT DOES NOT SHOW<br />

THE PHYSICAL POSITION OF COMPONENTS IN<br />

THE UNIT OR THEIR PRECISE APPEARANCE<br />

RUPTURE<br />

DISCS<br />

CHANGEOVER<br />

VALVE<br />

KMC MOISTURE<br />

SENSOR (WETECH)<br />

LIQUID<br />

FILTER<br />

DRIER<br />

LIQ LEVEL<br />

SIGHT GLASSES<br />

& ALARM<br />

LIQUID<br />

RECEIVER<br />

INDICATOR<br />

GAUGE PRV<br />

(24.8 BAR)<br />

S1<br />

TEV<br />

BULB<br />

EVAP<br />

SOLENOID<br />

DRAIN LINE<br />

RUPTURE<br />

DISC<br />

1 3/8"<br />

B.V.<br />

EQ. LINE<br />

REMOTE CONDENSER<br />

1 3/8"<br />

B.V.<br />

SCHR<br />

SCI<br />

SCO<br />

LIQUID BYPASS<br />

ARRANGEMENT<br />

1 3/8"<br />

B.V.<br />

HOUSING<br />

COOLING<br />

(MSHP ONLY)<br />

HGI1<br />

LO 1<br />

SIGHT<br />

GLASS<br />

VIB<br />

ELIM<br />

LIQUID STUB<br />

1 3/8" ODS<br />

SCHR<br />

SCHR<br />

HP / LP<br />

SAFETY<br />

COMPRESSOR<br />

<strong>INV</strong>ERTER<br />

ASSY<br />

3/8"<br />

B.V.<br />

1 5/8"<br />

BALL Vv.<br />

<strong>INV</strong>ERTER<br />

DISCHARGE HEADER<br />

MAIN HP<br />

TRANSDUCER<br />

BACKUP HP<br />

TRANSDUCER<br />

Issue 3 Page - 72 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1 5/8"<br />

N.R.V.<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

1/2"<br />

B.V.<br />

HP LP<br />

HP LP<br />

ROTALOK<br />

Vv<br />

HP LP<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

COALESCENT<br />

OIL SEPARATOR<br />

RESERVOIR<br />

CCH<br />

COMP 1<br />

4FC3.2Y (DOL)<br />

3/8"<br />

HOSE<br />

CCH<br />

3/8"<br />

HOSE<br />

CCH<br />

OIL<br />

SOV<br />

HOSE COMP 2<br />

4EC4.2Y (DOL)<br />

OIL<br />

SOV<br />

HOSE COMP 3<br />

4PCS10.2Y (PWS)<br />

3/8"<br />

HOSE<br />

OIL<br />

SOV<br />

OIL RETURN<br />

S.O.V.<br />

SCHR<br />

LIQUID STUB<br />

1 3/8" ODS<br />

MAIN LP<br />

TRANSDUCER<br />

BACKUP LP<br />

TRANSDUCER<br />

DUAL PRV<br />

(14 BAR)<br />

20mm CLASS 'O'<br />

INSULATION<br />

SUCTION HEADER<br />

SUCTION<br />

STRAINER<br />

2 5/8"<br />

B.V.<br />

CHANGE OVER<br />

VALVE<br />

3/8" MALE<br />

FLR PORT<br />

VIB<br />

ELIM<br />

SUCTION STUB<br />

2 5/8" ODS<br />

MATERIAL FINISH<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

01<br />

DATE SCALE PART<br />

PART No. ISS<br />

23/05/03 1:1 CCU050-ECI PIPEWORK SCHEMATIC<br />

DRAWN CHECKED FOR<br />

JOB No. DRG. FILE REF<br />

NS NS <strong>MSP</strong> N/A <strong>MSP</strong>-050-800-<strong>INV</strong>.01<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.1.2 <strong>MSP</strong>060-<strong>INV</strong> Pipework Schematic<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

IF IN DOUBT ASK<br />

A2 DO NOT SCALE<br />

THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

DUAL PRV<br />

(24.8 BAR)<br />

INDICATOR<br />

GAUGES<br />

CHARGING<br />

Vv<br />

TEV<br />

ORIFICE 3<br />

ROTALOCK<br />

VALVE<br />

ROTALOCK<br />

VALVE<br />

RECEIVER<br />

ASSY.<br />

FILTER DRIER &<br />

SIGHTGLASS<br />

ASSY.<br />

CCU-JG5 EVAPORATOR<br />

: IMPORTANT :<br />

THIS DRAWING SHOWS THE POSITION<br />

OF THE COMPONENTS WITHIN THE<br />

REFRIGERATION SYSTEM. IT DOES NOT SHOW<br />

THE PHYSICAL POSITION OF COMPONENTS IN<br />

THE UNIT OR THEIR PRECISE APPEARANCE<br />

RUPTURE<br />

DISCS<br />

CHANGEOVER<br />

VALVE<br />

KMC MOISTURE<br />

SENSOR (WETECH)<br />

LIQUID<br />

FILTER<br />

DRIER<br />

LIQ LEVEL<br />

SIGHT GLASSES<br />

& ALARM<br />

LIQUID<br />

RECEIVER<br />

INDICATOR<br />

GAUGE PRV<br />

(24.8 BAR)<br />

S1<br />

TEV<br />

BULB<br />

EVAP<br />

SOLENOID<br />

DRAIN LINE<br />

RUPTURE<br />

DISC<br />

1 3/8"<br />

B.V.<br />

EQ. LINE<br />

REMOTE CONDENSER<br />

1 3/8"<br />

B.V.<br />

SCHR<br />

SCI<br />

SCO<br />

LIQUID BYPASS<br />

ARRANGEMENT<br />

1 3/8"<br />

B.V.<br />

HOUSING<br />

COOLING<br />

(MSHP ONLY)<br />

HGI1<br />

LO 1<br />

SIGHT<br />

GLASS<br />

VIB<br />

ELIM<br />

LIQUID STUB<br />

1 3/8" ODS<br />

SCHR<br />

SCHR<br />

HP / LP<br />

SAFETY<br />

COMPRESSOR<br />

<strong>INV</strong>ERTER<br />

ASSY<br />

3/8"<br />

B.V.<br />

1 5/8"<br />

BALL Vv.<br />

<strong>INV</strong>ERTER<br />

DISCHARGE HEADER<br />

MAIN HP<br />

TRANSDUCER<br />

BACKUP HP<br />

TRANSDUCER<br />

Issue 3 Page - 73 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1 5/8"<br />

N.R.V.<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

1/2"<br />

B.V.<br />

HP LP<br />

HP LP<br />

ROTALOK<br />

Vv<br />

HP LP<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

COALESCENT<br />

OIL SEPARATOR<br />

RESERVOIR<br />

CCH<br />

COMP 1<br />

4EC-4.2Y (DOL)<br />

3/8"<br />

HOSE<br />

CCH<br />

3/8"<br />

HOSE<br />

CCH<br />

OIL<br />

SOV<br />

HOSE COMP 2<br />

4DC-5.2Y (DOL)<br />

OIL<br />

SOV<br />

HOSE COMP 3<br />

4NCS-12.2Y (PWS)<br />

3/8"<br />

HOSE<br />

OIL<br />

SOV<br />

OIL RETURN<br />

S.O.V.<br />

SCHR<br />

LIQUID STUB<br />

1 3/8" ODS<br />

MAIN LP<br />

TRANSDUCER<br />

BACKUP LP<br />

TRANSDUCER<br />

DUAL PRV<br />

(14 BAR)<br />

20mm CLASS 'O'<br />

INSULATION<br />

SUCTION HEADER<br />

SUCTION<br />

STRAINER<br />

2 5/8"<br />

B.V.<br />

CHANGE OVER<br />

VALVE<br />

3/8" MALE<br />

FLR PORT<br />

VIB<br />

ELIM<br />

SUCTION STUB<br />

2 5/8" ODS<br />

MATERIAL FINISH<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

01<br />

DATE SCALE PART<br />

PART No. ISS<br />

23/05/03 1:1 <strong>MSP</strong>060-<strong>INV</strong> PIPEWORK SCHEMATIC<br />

DRAWN CHECKED FOR<br />

JOB No. DRG. FILE REF<br />

NS NS <strong>MSP</strong> N/A <strong>MSP</strong>-060-800-<strong>INV</strong>.01<br />

16/03/06<br />

N/A<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.1.3 <strong>MSP</strong>080-RDM Pipework Schematic<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

IF IN DOUBT ASK<br />

A2 DO NOT SCALE<br />

THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

DUAL PRV<br />

(24.8 BAR)<br />

INDICATOR<br />

GAUGES<br />

CHARGING<br />

Vv<br />

TEV<br />

ORIFICE 3<br />

ROTALOCK<br />

VALVE<br />

ROTALOCK<br />

VALVE<br />

RECEIVER<br />

ASSY.<br />

FILTER DRIER &<br />

SIGHTGLASS<br />

ASSY.<br />

CCU-JG5 EVAPORATOR<br />

: IMPORTANT :<br />

THIS DRAWING SHOWS THE POSITION<br />

OF THE COMPONENTS WITHIN THE<br />

REFRIGERATION SYSTEM. IT DOES NOT SHOW<br />

THE PHYSICAL POSITION OF COMPONENTS IN<br />

THE UNIT OR THEIR PRECISE APPEARANCE<br />

RUPTURE<br />

DISCS<br />

CHANGEOVER<br />

VALVE<br />

KMC MOISTURE<br />

SENSOR (WETECH)<br />

LIQUID<br />

FILTER<br />

DRIER<br />

LIQ LEVEL<br />

SIGHT GLASSES<br />

& ALARM<br />

LIQUID<br />

RECEIVER<br />

INDICATOR<br />

GAUGE PRV<br />

(24.8 BAR)<br />

S1<br />

TEV<br />

BULB<br />

EVAP<br />

SOLENOID<br />

DRAIN LINE<br />

RUPTURE<br />

DISC<br />

1 3/8"<br />

B.V.<br />

EQ. LINE<br />

REMOTE CONDENSER<br />

1 3/8"<br />

B.V.<br />

SCHR<br />

SCI<br />

SCO<br />

LIQUID BYPASS<br />

ARRANGEMENT<br />

1 3/8"<br />

B.V.<br />

HOUSING<br />

COOLING<br />

(MSHP ONLY)<br />

HGI1<br />

LO 1<br />

SIGHT<br />

GLASS<br />

VIB<br />

ELIM<br />

LIQUID STUB<br />

1 3/8" ODS<br />

SCHR<br />

SCHR<br />

HP / LP<br />

SAFETY<br />

<strong>INV</strong>ERTER<br />

COMPRESSOR<br />

<strong>INV</strong>ERTER<br />

ASSY<br />

3/8"<br />

B.V.<br />

1 5/8"<br />

BALL Vv.<br />

DISCHARGE HEADER<br />

MAIN HP<br />

TRANSDUCER<br />

BACKUP HP<br />

TRANSDUCER<br />

Issue 3 Page - 74 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1 5/8"<br />

N.R.V.<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

1/2"<br />

B.V.<br />

HP LP<br />

HP LP<br />

ROTALOK<br />

Vv<br />

OFFLOADER<br />

HEAD<br />

HP LP<br />

OIL PUMP<br />

SENSOR<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

COALESCENT<br />

OIL SEPARATOR<br />

RESERVOIR<br />

CCH<br />

COMP 1<br />

4DC5.2Y (DOL)<br />

3/8"<br />

HOSE<br />

CCH<br />

3/8"<br />

HOSE<br />

CCH<br />

OIL<br />

SOV<br />

HOSE COMP 2<br />

4PCS10.2Y (PWS)<br />

OIL<br />

SOV<br />

HOSE COMP 3<br />

4J-13.2Y (PWS)<br />

3/8"<br />

HOSE<br />

OIL<br />

SOV<br />

OIL RETURN<br />

S.O.V.<br />

SCHR<br />

LIQUID STUB<br />

1 3/8" ODS<br />

MAIN LP<br />

TRANSDUCER<br />

BACKUP LP<br />

TRANSDUCER<br />

DUAL PRV<br />

(14 BAR)<br />

20mm CLASS 'O'<br />

INSULATION<br />

SUCTION HEADER<br />

SUCTION<br />

STRAINER<br />

2 5/8"<br />

B.V.<br />

CHANGE OVER<br />

VALVE<br />

3/8" MALE<br />

FLR PORT<br />

VIB<br />

ELIM<br />

SUCTION STUB<br />

2 5/8" ODS<br />

MATERIAL FINISH<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

01<br />

DATE SCALE PART<br />

PART No. ISS<br />

23/05/03 1:1 <strong>MSP</strong>080-<strong>INV</strong> PIPEWORK SCHEMATIC<br />

DRAWN CHECKED FOR<br />

JOB No. DRG. FILE REF<br />

NS NS MSU N/A <strong>MSP</strong>-080-800-<strong>INV</strong>.01<br />

16/03/06<br />

N/A<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.1.4 <strong>MSP</strong>100-RDM Pipework Schematic<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

IF IN DOUBT ASK<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

ROTALOCK<br />

VALVE<br />

DUAL PRV<br />

(24.8 BAR)<br />

INDICATOR<br />

GAUGES<br />

ROTALOCK<br />

VALVE<br />

RUPTURE<br />

DISCS<br />

CHANGEOVER<br />

VALVE<br />

A2 DO NOT SCALE<br />

THIRD ANGLE PROJECTION<br />

TEV<br />

FILTER DRIER &<br />

RECEIVER<br />

ORIFICE 3<br />

CHARGING<br />

SIGHTGLASS<br />

Vv<br />

CCU-JG5 EVAPORATOR<br />

ASSY.<br />

ASSY.<br />

LIQUID<br />

KMC MOISTURE<br />

FILTER<br />

SENSOR (WETECH)<br />

DRIER<br />

: IMPORTANT :<br />

THIS DRAWING SHOWS THE POSITION<br />

OF THE COMPONENTS WITHIN THE<br />

REFRIGERATION SYSTEM. IT DOES NOT SHOW<br />

THE PHYSICAL POSITION OF COMPONENTS IN<br />

THE UNIT OR THEIR PRECISE APPEARANCE<br />

LIQ LEVEL<br />

SIGHT GLASSES<br />

& ALARM<br />

LIQUID<br />

RECEIVER<br />

INDICATOR<br />

GAUGE PRV<br />

(24.8 BAR)<br />

S1<br />

TEV<br />

BULB<br />

EVAP<br />

SOLENOID<br />

DRAIN LINE<br />

RUPTURE<br />

DISC<br />

1 3/8"<br />

B.V.<br />

EQ. LINE<br />

REMOTE CONDENSER<br />

1 3/8"<br />

B.V.<br />

SCHR<br />

SCI<br />

SCO<br />

LIQUID BYPASS<br />

ARRANGEMENT<br />

1 3/8"<br />

B.V.<br />

HOUSING<br />

COOLING<br />

(MSHP ONLY)<br />

HGI1<br />

LO 1<br />

SIGHT<br />

GLASS<br />

VIB<br />

ELIM<br />

LIQUID STUB<br />

1 3/8" ODS<br />

SCHR<br />

SCHR<br />

HP / LP<br />

SAFETY<br />

<strong>INV</strong>ERTER<br />

COMPRESSOR<br />

<strong>INV</strong>ERTER<br />

ASSY<br />

3/8"<br />

B.V.<br />

1 5/8"<br />

BALL Vv.<br />

DISCHARGE HEADER<br />

MAIN HP<br />

TRANSDUCER<br />

BACKUP HP<br />

TRANSDUCER<br />

Issue 3 Page - 75 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1 5/8"<br />

N.R.V.<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

1/2"<br />

B.V.<br />

HP LP<br />

HP LP<br />

ROTALOK<br />

Vv<br />

OFFLOADER<br />

HEAD<br />

HP LP<br />

OIL PUMP<br />

SENSOR<br />

OIL PUMP<br />

SENSOR<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

ROTALOK<br />

Vv<br />

COALESCENT<br />

OIL SEPARATOR<br />

RESERVOIR<br />

CCH<br />

COMP 1<br />

4CC-6.2Y (DOL)<br />

3/8"<br />

HOSE<br />

CCH<br />

3/8"<br />

HOSE<br />

CCH<br />

OIL<br />

SOV<br />

HOSE COMP 2<br />

4J-13.2Y (PWS)<br />

OIL<br />

SOV<br />

HOSE COMP 3<br />

4G-20.2Y (PWS)<br />

3/8"<br />

HOSE<br />

OIL<br />

SOV<br />

OIL RETURN<br />

S.O.V.<br />

SCHR<br />

LIQUID STUB<br />

1 3/8" ODS<br />

MAIN LP<br />

TRANSDUCER<br />

BACKUP LP<br />

TRANSDUCER<br />

DUAL PRV<br />

(14 BAR)<br />

20mm CLASS 'O'<br />

INSULATION<br />

SUCTION HEADER<br />

SUCTION<br />

STRAINER<br />

2 5/8"<br />

B.V.<br />

CHANGE OVER<br />

VALVE<br />

3/8" MALE<br />

FLR PORT<br />

VIB<br />

ELIM<br />

SUCTION STUB<br />

2 5/8" ODS<br />

MATERIAL FINISH<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

01<br />

DATE SCALE PART<br />

PART No. ISS<br />

23/05/03 1:1 <strong>MSP</strong>100-<strong>INV</strong> PIPEWORK SCHEMATIC<br />

DRAWN CHECKED FOR<br />

JOB No. DRG. FILE REF<br />

NS NS <strong>MSP</strong> N/A <strong>MSP</strong>-100-800-<strong>INV</strong>.01<br />

16/03/06<br />

N/A<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.1 <strong>MSP</strong>050-<strong>INV</strong> Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

86<br />

62 62<br />

243<br />

180<br />

475 MNTG CTRS<br />

POSITION OF M10 MOUNTING<br />

BOLT, TO COMPRESSOR PACK<br />

BASE FRAME.<br />

145<br />

DETAIL OF ISOLATOR FIXINGS<br />

TYPICAL 4 POSITIONS.<br />

SCALE ~ .1:5 1910 MNTG CTRS<br />

M8 CLEARANCE HOLE FOR<br />

FIXING OF ISOLATOR<br />

296<br />

1691 UNIT HEIGHT<br />

Issue 3 Page - 76 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1.5/8" DISCHARGE<br />

CONNECTION<br />

835<br />

244<br />

30<br />

825<br />

2.5/8" SUCTION<br />

CONNECTION<br />

2488<br />

863 UNIT WIDTH<br />

2689 OVERALL LENGTH<br />

FINISH<br />

MATERIAL<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>050-<strong>INV</strong><br />

PART<br />

01<br />

COMPRESSOR PACK: <strong>MSP</strong>050-<strong>INV</strong><br />

1:20<br />

DATE SCALE<br />

26/06/06<br />

<strong>MSP</strong>050-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

CDS<br />

CDS<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.2 <strong>MSP</strong>060-<strong>INV</strong> Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

62 62<br />

86<br />

145 475 MNTG CTRS 243<br />

180<br />

POSITION OF M10 MOUNTING<br />

BOLT, TO COMPRESSOR PACK<br />

BASE FRAME.<br />

DETAIL OF ISOLATOR FIXINGS<br />

TYPICAL 4 POSITIONS.<br />

SCALE ~ .1:5<br />

M8 CLEARANCE HOLE FOR<br />

FIXING OF ISOLATOR<br />

1910 MNTG CTRS 296<br />

Issue 3 Page - 77 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1.5/8" DISCHARGE<br />

CONNECTION<br />

835<br />

244<br />

30 1695 UNIT HEIGHT<br />

825<br />

2.5/8" SUCTION<br />

CONNECTION<br />

863 UNIT WIDTH<br />

2488<br />

2689 OVERALL LENGTH<br />

FINISH<br />

MATERIAL<br />

TOLERANCES ASSEMBLY<br />

UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>060-<strong>INV</strong><br />

PART<br />

01<br />

COMPRESSOR PACK: <strong>MSP</strong>060-<strong>INV</strong><br />

1:20<br />

DATE SCALE<br />

26/06/06<br />

<strong>MSP</strong>060-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

CDS<br />

CDS<br />

ISS MODIFICATION SCN DATE


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.3 <strong>MSP</strong>080-<strong>INV</strong> Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

62 62<br />

86<br />

145 475 MNTG CTRS 243<br />

180<br />

POSITION OF M10 MOUNTING<br />

BOLT, TO COMPRESSOR PACK<br />

BASE FRAME.<br />

DETAIL OF ISOLATOR FIXINGS<br />

TYPICAL 4 POSITIONS.<br />

SCALE ~ .1:5<br />

M8 CLEARANCE HOLE FOR<br />

FIXING OF ISOLATOR<br />

1910 MNTG CTRS 296<br />

Issue 3 Page - 78 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1.5/8" DISCHARGE<br />

CONNECTION<br />

837<br />

239<br />

30 1781 UNIT HEIGHT<br />

825<br />

2.5/8" SUCTION<br />

CONNECTION<br />

2488<br />

863 UNIT WIDTH<br />

2689 OVERALL LENGTH<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

ASSEMBLY<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>080-<strong>INV</strong><br />

01<br />

COMPRESSOR PACK: <strong>MSP</strong>080-<strong>INV</strong><br />

<strong>MSP</strong>080-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

26/06/06 1:20<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

CDS<br />

CDS<br />

ISS MODIFICATION SCN DATE


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.4 <strong>MSP</strong>100-<strong>INV</strong> Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

62 62<br />

86<br />

145 475 MNTG CTRS 243<br />

180<br />

POSITION OF M10 MOUNTING<br />

BOLT, TO COMPRESSOR PACK<br />

BASE FRAME.<br />

DETAIL OF ISOLATOR FIXINGS<br />

TYPICAL 4 POSITIONS.<br />

SCALE ~ .1:5<br />

M8 CLEARANCE HOLE FOR<br />

FIXING OF ISOLATOR<br />

1910 MNTG CTRS 296<br />

Issue 3 Page - 79 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

2.5/8" DISCHARGE<br />

CONNECTION<br />

838<br />

244<br />

30 1781 UNIT HEIGHT<br />

863 UNIT WIDTH<br />

825<br />

2.5/8" SUCTION<br />

CONNECTION<br />

2689 OVERALL LENGTH<br />

2488<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

ASSEMBLY<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

PART No. ISS<br />

<strong>MSP</strong>100-<strong>INV</strong><br />

01<br />

COMPRESSOR PACK: <strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>100-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

26/06/06 1:20<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

CDS<br />

CDS<br />

ISS MODIFICATION SCN DATE


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.5 <strong>MSP</strong>L050-<strong>INV</strong> Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

62 62<br />

98<br />

86<br />

POSITION OF M10 MOUNTING<br />

BOLT, TO COMPRESSOR PACK<br />

BASE FRAME.<br />

863 FRAMEWORK DEPTH<br />

DETAIL OF ISOLATOR FIXINGS<br />

TYPICAL 4 POSITIONS.<br />

SCALE ~ .1:5<br />

M8 CLEARANCE HOLE FOR<br />

FIXING OF ISOLATOR<br />

90<br />

90<br />

570 MNTG<br />

90 1320 MNTG PAD CTRS<br />

180 PAD CTRS 90<br />

1671 OVERALL HEIGHT<br />

DISCHARGE & SUCTION<br />

VIBRATION ELIMINATORS<br />

SHOWN IN POSITION<br />

FOR INFORMATION ONLY<br />

(SUPPLIED LOOSE)<br />

Issue 3 Page - 80 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

1.5/8" DISCHARGE<br />

CONNECTION<br />

804<br />

542<br />

2.5/8"<br />

SUCTION<br />

CONNECTION<br />

823 MNTG CTRS<br />

750 FRAMEWORK<br />

LENGTH (RH)<br />

923 OVERALL WIDTH<br />

SPACE REQUIRED<br />

FOR FITMENT OF<br />

VIBRATION ELIMINATORS<br />

400<br />

2250 OVERALL LENGTH<br />

1500 FRAMEWORK LENGTH (LH)<br />

FINISH<br />

MATERIAL<br />

TOLERANCES UNLESS OTHERWISE STATED<br />

ASSEMBLY<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

NATURAL<br />

PART No. ISS<br />

<strong>MSP</strong>L050-<strong>INV</strong><br />

01<br />

SPLIT COMPRESSOR PACK: <strong>MSP</strong>L050-<strong>INV</strong><br />

<strong>MSP</strong>L050-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

29/08/06 1:20<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

CDS<br />

CDS<br />

ISS MODIFICATION SCN DATE


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 8.Layout Diagrams<br />

8.2.6 MSHP-<strong>INV</strong> Housing Dimensions<br />

This document is protected by copyright, and the design it contains is protected by<br />

both copyright and design right, all such rights being owned by ICG (UK) Limited.<br />

This document may also contain information which is confidential to that Company.<br />

Neither this document nor the design or information which it contains may therefore<br />

be used, sold, licensed, transferred, copied, lent, disclosed to any third party<br />

or otherwise reproduced in whole or in part in any manner or form other than with<br />

the prior written consent of that Company.<br />

"<br />

DO NOT SCALE IF IN DOUBT ASK<br />

A3 THIRD ANGLE PROJECTION<br />

[20 ] ICG (UK) Limited. All Rights Reserved."<br />

C<br />

Issue 3 Page - 81 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

FINISH<br />

MATERIAL<br />

TOLERANCES ASSEMBLY UNLESS OTHERWISE STATED<br />

MANUFACTURING COMPANY<br />

NEWGATE LANE FAREHAM HANTS PO14 1AR<br />

RAL7036<br />

PART No. ISS<br />

01<br />

80KW M&S HOUSED PACK RDM & <strong>INV</strong>ERTER<br />

MSHP080-<strong>INV</strong>.01<br />

JOB No. DRG. FILE REF<br />

DATE SCALE PART<br />

06/12/05 1:30<br />

DRAWN CHECKED FOR<br />

N/A N/A<br />

GWS<br />

GWS<br />

ISS MODIFICATION SCN DATE<br />

8


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 9. Spares List<br />

Issue 3 Page - 82 -<br />

September 2007<br />

9. Spares List INDEX<br />

Page No’s Issue No<br />

9.1 Compressors & Accessories 83 1<br />

9.2 Compressor Controls 84 1<br />

9.3 Pressure Relief Components 85 1<br />

9.4 Electrical Components 85 1<br />

9.5 Replaceable Elements 86 1<br />

9.6 Fixtures & Fittings 86 1<br />

9.7 Pressure Switches & Pressure Controls 86 1<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

9


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 9. Spares List<br />

9.1 Compressors & Accessories<br />

<strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>080- <strong>INV</strong><br />

<strong>MSP</strong>060- <strong>INV</strong><br />

<strong>MSP</strong>050- <strong>INV</strong><br />

Component<br />

<strong>Searle</strong> Pt No.<br />

Type<br />

<strong>Searle</strong> Pt No.<br />

Type<br />

<strong>Searle</strong> Pt No.<br />

Type<br />

<strong>Searle</strong> Pt No.<br />

Type<br />

Description<br />

200-200-078<br />

4CC-6.2Y<br />

200-200-077<br />

4DC-5.2Y<br />

200-200-076<br />

4EC-4.2Y<br />

200-200-075<br />

4FC-3.2Y<br />

Compressor 1<br />

200-200-088-<br />

ULDH<br />

4J-13.2Y<br />

200-200-096-<br />

ULDH<br />

4PCS-10.2Y<br />

200-200-077<br />

4DC-5.2Y<br />

200-200-076<br />

4EC-4.2Y<br />

Compressor 2<br />

200-200-087<br />

4G-20.2Y<br />

200-200-088<br />

4J-13.2Y<br />

200-200-095<br />

4NCS-12.2Y<br />

200-200-096<br />

4PCS-10.2Y<br />

Compressor 3<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

Oil Float Comp 1<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

200-604-013<br />

OM3-CBB<br />

AL805032<br />

Oil Float Comp 2<br />

Issue 3 Page - 83 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

200-604-014<br />

OM3-CUA<br />

AL805030<br />

Oil Float Comp 3<br />

55-000-201<br />

TRAXOIL<br />

Cable Brkt<br />

55-000-201<br />

TRAXOIL<br />

Cable Brkt<br />

55-000-201<br />

TRAXOIL<br />

Cable Brkt<br />

55-000-201<br />

TRAXOIL<br />

Cable Brkt<br />

Oil Float Cable<br />

Bracket<br />

200-604-015<br />

OM3-P30<br />

AL805151<br />

200-604-015<br />

OM3-P30<br />

AL805151<br />

200-604-015<br />

OM3-P30<br />

AL805151<br />

200-604-015<br />

OM3-P30<br />

AL805151<br />

Oil Float Power<br />

Cable<br />

200-604-016<br />

OM3-N30<br />

AL805141<br />

200-604-016<br />

OM3-N30<br />

AL805141<br />

200-604-016<br />

OM3-N30<br />

AL805141<br />

200-604-016<br />

OM3-N30<br />

AL805141<br />

Oil Float Relay<br />

Cable<br />

49-060-450<br />

90° to 0°<br />

,0.77m<br />

49-060-450<br />

90° to 0°<br />

,0.77m<br />

49-060-450<br />

90° to 0°<br />

,0.77m<br />

49-060-450<br />

90° to 0°<br />

,0.77m<br />

Oil Return Hose<br />

200-200-510<br />

1/4" Flare Vv.<br />

200-200-510<br />

1/4" Flare Vv.<br />

200-200-510<br />

1/4" Flare Vv.<br />

200-200-510<br />

1/4" Flare Vv.<br />

Oil Return Shut off<br />

Valve<br />

291-200-183<br />

1/8" NPT x<br />

1/4" Flr Sch<br />

291-200-183<br />

1/8" NPT x<br />

1/4" Flr Sch<br />

291-200-183<br />

1/8" NPT x<br />

1/4" Flr Sch<br />

291-200-183<br />

1/8" NPT x<br />

1/4" Flr Sch<br />

HP/LP to Comp<br />

Adapter Straight<br />

Schraeder<br />

9


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 9. Spares List<br />

9.2 Compressor Controls<br />

<strong>MSP</strong>100-<strong>INV</strong><br />

<strong>MSP</strong>080-<strong>INV</strong><br />

<strong>MSP</strong>060-<strong>INV</strong><br />

<strong>MSP</strong>050-<strong>INV</strong><br />

Compressor Controls<br />

<strong>Searle</strong> Pt No.<br />

<strong>Searle</strong> Pt No.<br />

<strong>Searle</strong> Pt No.<br />

<strong>Searle</strong> Pt No.<br />

Type<br />

216-112-302<br />

216-112-302<br />

216-112-302<br />

216-112-302<br />

ISOLATOR P3-63/V/SVB KLOCKNER<br />

Isolator (All Compressors)<br />

200-708-201<br />

200-708-201<br />

200-708-201<br />

200-708-201<br />

NEUTRAL POLE FITS P3-ALL (100A MAX)<br />

Isolator Neutral Auxiliary (All Comps)<br />

216-112-005<br />

216-112-005<br />

216-112-005<br />

216-112-005<br />

AUX.CONTACT FOR P1-32 ISOLATOR<br />

Isolator 4th Pole Auxiliary (All Comps)<br />

216-112-002<br />

216-112-002<br />

216-112-002<br />

216-112-002<br />

PROTECT COVER FOR P3-63 ISOLATOR<br />

Isolator Inlet Protect Cover (All Comps)<br />

MOTOR STARTER O'LOAD<br />

200-200-742<br />

200-200-741<br />

200-200-741<br />

200-200-741<br />

Comp 1 Overload/Manual Starter (1MS1)<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

AUX CONTACT 1 NO/1 NC NHI11-PKZ0<br />

Comp 1 Overload/Manual Starter Auxiliary<br />

216-131-011<br />

216-131-011<br />

216-131-005<br />

216-131-005<br />

CONTACTOR DILM N/C AUX 24V COIL<br />

Comp 1 Contactor (1K1)<br />

216-131-021<br />

216-131-021<br />

216-131-021<br />

216-131-021<br />

AUX CONTACT 1N/O 1N/C DILA-XHI1<br />

Comp 1 Contactor Auxilary, NO/NC<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

2 POLE RLY 24VAC COIL DPDT<br />

Comp 1 - 1R1 & 1R2 - Relay<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

RELAY BASE 2 PL 24V<br />

Comp 1 - 1R1 & 1R2 - Relay Base<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

MCB 4A 1POLE C CURVE<br />

Comp 1 - MCB (1CB1)<br />

Issue 3 Page - 84 -<br />

September 2007<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

200-200-742<br />

200-200-742<br />

200-200-741<br />

200-200-741<br />

MOTOR STARTER O'LOAD<br />

Comp 2 Overload/Manual Starter (2MCB1)<br />

200-200-742<br />

200-200-742<br />

N/A<br />

N/A<br />

MOTOR STARTER O'LOAD<br />

Comp 2 Overload/Manual Starter (2MCB2)<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

AUX CONTACT 1 NO/1 NC NHI11-PKZ0<br />

Comp 2 Overload/Manual Starter Auxiliary<br />

216-131-011<br />

216-131-011<br />

216-131-005<br />

216-131-005<br />

CONTACTOR DILM N/C AUX 24V COIL<br />

Comp 2 Contactors (2C1,2C2)<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

AUX CONTACT 1N/O 1N/C DILA-XHI1<br />

Comp 2 Contactor Auxilary, NO/NC<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

2 POLE RLY 24VAC COIL DPDT<br />

Comp 2 - 2R1 & 2R2 - Relay<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

RELAY BASE 2 PL 24V<br />

Comp 2 - 2R1 & 2R2 - Relay Base<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

MCB 4A 1POLE C CURVE<br />

Comp 2 - MCB (2CB1)<br />

200-200-742<br />

200-200-742<br />

200-200-741<br />

200-200-741<br />

MOTOR STARTER O'LOAD<br />

Comp 3 Overload/Manual Starter (3MCB1)<br />

200-200-742<br />

200-200-742<br />

200-200-741<br />

200-200-741<br />

MOTOR STARTER O'LOAD<br />

Comp 3 Overload/Manual Starter (3MCB2)<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

200-200-744<br />

AUX CONTACT 1 NO/1 NC NHI11-PKZ0<br />

Comp 3 Overload/Manual Starter Auxiliary<br />

216-131-011<br />

216-131-011<br />

216-131-011<br />

216-131-005<br />

CONTACTOR DILM N/C AUX 24V COIL<br />

Comp 3 Contactors (3C1,3C2)<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

AUX CONTACT 1N/O 1N/C DILA-XHI1<br />

Comp 3 Contactor Auxilary, NO/NC<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

200-200-755<br />

2 POLE RLY 24VAC COIL DPDT<br />

Comp 3 - 3R1 & 3R2 – Relay<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

200-200-745<br />

RELAY BASE 2 PL 24V<br />

Comp 3 - 3R1 & 3R2 - Relay Base<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

200-709-002<br />

MCB 4A 1POLE C CURVE<br />

9<br />

Comp 3 - MCB (3CB1)


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 9. Spares List<br />

9.3 Pressure Relief Components / Receiver / Filter Assembly<br />

Issue 3 Page - 85 -<br />

September 2007<br />

Pressure Relief Components Type <strong>Searle</strong> Pt No.<br />

High Side PRV (24.8 Bar) PRV 24.8 BARG 3/8 NPT 200-563-025<br />

High Side Burst Disc (24.8 Bar) RUPTURE DISC 24.8 BAR 1/2in NPT 200-564-025<br />

Low Side PRV (14 Bar) HENRY PRV 14BAR 1/2NPT IN 5/8FL 200-563-014<br />

Burst Disc Indicator Gauge Pressure Gauge 200-565-001<br />

Burst Disc Blanking Plug 1/8" NPT Blanking Plug 200-616-012<br />

3 way Changeover Valve 3 way Valve 1/2" FPT 200-562-001<br />

9.4 Electrical Components<br />

Electrical Components<br />

Main Controls Type <strong>Searle</strong> Pt No.<br />

RDM Main Controller RDM MERCURY CONTROL VARIPAC 200-800-483<br />

RDM Backup Controller RDM MERCURY STEP CONTROLLER PR331 200-800-451<br />

Millenium Monitor Controller MILLENIUM CONTROLLER SA20R 24V DC 200-800-457<br />

Temperature Probe PT1000 TEMPERATURE PROBE 200-800-216<br />

Electric box Door Latch 1/4 Turn Latch Assy 200-610-020<br />

Electric box Door Key 5mm Double Bit Key 200-610-021<br />

Transformer TRANSFORMER 200VA 230V TO 12/24VAC 200-200-753<br />

Millenium DC Power Supply MILLENIUM POWER SUPPLY 24V DC 200-800-460<br />

10 amp MCB MCB 10A 1POLE C CURVE 200-200-713<br />

6 amp MCB MCB 6A 1Pole C Curve 200-200-712<br />

4 amp MCB MCB 4A 1Pole C Curve 200-200-745<br />

Isolator ISOLATOR P1-32/V/SVB KLOCKNER 216-112-301<br />

Isolator Neutral Pole NEUTRAL SW FOR P1-32/V/SVB ISOLATOR 200-708-302<br />

Isolator Auxiliary Contact AUX.CONTACT FOR P1-32 ISOLATOR 216-112-005<br />

Suction Transducer TRANSDUCER 0-18 BAR 4-20ma PT4-18S 200-800-221<br />

Liquid Transducer TRANSDUCER 0-30 BAR 4-20ma PT4-30S 200-800-222<br />

Anti Surge Fuses 20mm 3.15A ANTI SURGE GLASS FUSE 216-210-625<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

9


<strong>MSP</strong>-<strong>INV</strong> Installation and Operating Manual 9. Spares List<br />

9.5 Replaceable Elements<br />

Issue 3 Page - 86 -<br />

September 2007<br />

Replacement Filter Elements Type <strong>Searle</strong> Pt No.<br />

Oil Separator Element F592613RFC Replacement Element 200-604-050<br />

Liquid Filter Drier Element (2 reqd) 48" Std Drier Core 200-452-076<br />

Suction Filter Element (2 reqd) 48" Felt Core 200-452-078<br />

Liquid Filter Burn-out Element (2 reqd) 48" Acid removal Core 200-452-101<br />

Suction Filter Burn-out Element (2 reqd) 48" Cleanup Core 200-452-103<br />

9.6 Fixtures & Fittings<br />

Fixtures & Fittings Type <strong>Searle</strong> Pt No.<br />

RCD 230V 3pin Socket 3 Pin RCD Socket Metalclad 200-750-122<br />

9.7 Pressure Switches & Pressure Controls<br />

Pressure Switches & Accessories Type <strong>Searle</strong> Pt No.<br />

Main HP/LP Safety Switch DUAL P S/W AUTO 1/4 FLR CON 200-200-816<br />

Compressor Oil Pump Sensor OIL DIFF SWITCH DIRECT MOUNT BITZER 200-200-098<br />

Compressor HP Switch P100-CP12D 1/4 HP SWITCH AUTO 200-404-032<br />

Compressor LP Switch P100AP LP SWITCH AUTO 0.7BAR CUTOUT 200-404-031<br />

Part Number 272-000-294 <strong>Searle</strong> Manufacturing Company Telephone +44 (0)1329 82334<br />

Issue September07-1 Newgate Lane Fareham Facsimile +44 (0)1329 821243<br />

Hampshire PO14 1AR UK Website http://www.searle.co.uk Email sales@searle.co.uk<br />

9