Correction Tables for the Selection of Solenoid Valves For use with 110 RB, 200 RB, 240 RA and 540 RA Series 86 Valve selection for operating conditions other than nominal: Q n = Q o x K t x K∆p Q n : Nominal valve capacity K t : Correction factor for evaporating and liquid temperature K∆p: Correction factor for pressure drop at valve Q o : Required cooling capacity 1. Suction Gas Application Evaporating Correction Factor K t Temperature Condensing Temperature °C °C +60 +55 +50 +45 +40 +35 +30 +25 +20 +10 1,03 0,97 0,92 0,88 0,84 0,80 0,76 0,74 0,71 0 1,40 1,32 1,25 1,20 1,14 1,10 1,04 1,01 0,96 -10 1,71 1,62 1,53 1,47 1,40 1,34 1,27 1,23 1,18 -20 2,20 2,08 1,97 1,88 1,80 1,72 1,64 1,58 1,51 -30 2,79 2,63 2,50 2,39 2,27 2,19 2,07 2,01 1,92 -40 3,68 3,47 3,29 3,15 3,00 2,89 2,73 2,65 2,53 2. Liquid Application Correction Factor K∆p ∆p (bar) 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40 0,45 0,50 0,55 K∆p 1,73 1,22 1,00 0,87 0,77 0,71 0,65 0,61 0,48 0,55 0,52 Liquid Correction Factor K t Temperature R 134a Evaporating Temperature °C R 22 entering Valve °C +10 0 -10 -20 -30 +10 0 -10 -20 -30 -40 +60 1,33 1,40 1,48 1,56 1,67 1,26 1,30 1,38 1,38 1,44 1,50 +55 1,23 1,29 1,36 1,43 1,52 1,19 1,22 1,29 1,29 1,34 1,39 +50 1,15 1,20 1,26 1,32 1,39 1,12 1,15 1,21 1,22 1,26 1,30 +45 1,08 1,12 1,17 1,22 1,29 1,06 1,08 1,15 1,15 1,18 1,23 +40 1,01 1,05 1,10 1,14 1,20 1,01 1,03 1,09 1,09 1,12 1,16 +35 0,96 0,99 1,03 1,07 1,12 0,96 0,98 1,03 1,03 1,06 1,10 +30 0,91 0,94 0,98 1,01 1,06 0,92 0,94 0,99 0,98 1,01 1,04 +25 0,86 0,89 0,92 0,95 1,00 0,88 0,89 0,94 0,94 0,96 0,99 +20 0,82 0,85 0,88 0,91 0,94 0,84 0,86 0,90 0,90 0,92 0,95 +15 0,78 0,81 0,84 0,86 0,89 0,81 0,82 0,87 0,86 0,88 0,91 +10 0,75 0,77 0,80 0,82 0,85 0,78 0,79 0,83 0,83 0,85 0,87 +5 0,74 0,76 0,78 0,81 0,76 0,80 0,79 0,81 0,83 0 0,71 0,73 0,75 0,78 0,73 0,77 0,77 0,78 0,80 -5 0,70 0,72 0,74 0,74 0,74 0,75 0,77 -10 0,68 0,69 0,71 0,72 0,71 0,73 0,74 Correction Factor K∆p The pressure drop can be calculated with the following formula: ∆p (bar) 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40 0,45 0,50 0,55 0,60 0,65 0,70 0,75 K∆p 1,73 1,22 1,00 0,87 0,77 0,71 0,65 0,61 0,58 0,55 0,52 0,50 0,48 0,46 0,45 2 Q0 ∆ P = ∆P __ 0 n* 2 Qn ∆ P n = 0,15 bar ∆ P n : Pressure drop under nominal conditions A2.5.1/0706/E
2. Liquid Application Liquid Correction Factor K t Temperature R 404A Evaporating Temperature °C R 507 entering Valve 3. Hot Gas Application A2.5.1/0706/E °C +10 0 -10 -20 -30 -40 +10 0 -10 -20 -30 -40 +60 1,74 1,88 2,06 2,28 2,57 2,95 1,71 1,83 1,98 2,18 2,43 2,75 +55 1,46 1,55 1,68 1,83 2,01 2,25 1,43 1,52 1,62 1,76 1,92 2,12 +50 1,26 1,34 1,43 1,54 1,68 1,84 1,24 1,31 1,40 1,49 1,61 1,76 +45 1,12 1,18 1,26 1,34 1,45 1,57 1,11 1,17 1,23 1,31 1,40 1,52 +40 1,02 1,07 1,13 1,20 1,28 1,38 1,01 1,06 1,11 1,17 1,25 1,34 +35 0,93 0,97 1,02 1,08 1,15 1,23 0,93 0,97 1,01 1,07 1,13 1,20 +30 0,86 0,90 0,94 0,99 1,05 1,11 0,86 0,89 0,93 0,98 1,03 1,09 +25 0,80 0,83 0,87 0,92 0,97 1,02 0,80 0,83 0,87 0,91 0,95 1,01 +20 0,75 0,78 0,81 0,85 0,90 0,95 0,75 0,78 0,81 0,85 0,89 0,93 +15 0,71 0,73 0,76 0,80 0,84 0,88 0,71 0,73 0,76 0,79 0,83 0,87 +10 0,67 0,69 0,72 0,75 0,79 0,83 0,67 0,69 0,72 0,74 0,78 0,81 +5 0,66 0,68 0,71 0,74 0,78 0,65 0,68 0,70 0,73 0,76 0 0,63 0,65 0,68 0,71 0,74 0,62 0,64 0,66 0,69 0,72 -5 0,62 0,65 0,67 0,70 0,61 0,63 0,65 0,68 -10 0,60 0,62 0,64 0,67 0,58 0,60 0,62 0,64 Liquid Correction Factor K t Temperature R 407C Evaporating Temperature °C entering Valve °C +10 0 -10 -20 +60 +55 1,28 1,34 1,40 1,48 +50 1,17 1,22 1,27 1,33 +45 1,08 1,12 1,17 1,22 +40 1,01 1,04 1,08 1,13 +35 0,94 0,98 1,01 1,05 +30 0,89 0,92 0,95 0,99 +25 0,84 0,87 0,90 0,93 +20 0,80 0,82 0,85 0,88 +15 0,76 0,78 0,81 0,84 +10 0,73 0,75 0,77 0,80 +5 0,72 0,74 0,76 0 0,69 0,71 0,73 -5 0,68 0,70 -10 0,65 0,67 Correction Factor K∆p ∆p (bar) 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40 0,45 0,50 0,55 0,60 0,65 0,70 0,75 K∆p 1,73 1,22 1,00 0,87 0,77 0,71 0,65 0,61 0,58 0,55 0,52 0,50 0,48 0,46 0,45 Correction Factor K t Evaporating Temperature °C +10 +5 0 -5 -10 -15 -20 -25 -30 -35 -40 K t 0,96 1,00 1,03 1,06 1,10 1,13 1,17 1,20 1,24 1,29 1,33 Correction Factor K∆p ∆p (bar) 0,35 0,50 0,70 1,00 1,50 2,00 2,50 3,00 4,00 K∆p 1,72 1,49 1,22 1,00 0,86 0,78 0,73 0,70 0,65 87
- Page 37 and 38: Universal Driver Modules Series EXD
- Page 39 and 40: Accessories Type Part No. Terminal
- Page 41 and 42: Coldroom Controller Series EC3 Temp
- Page 43 and 44: Block Diagram EC3-33x Coldroom Cont
- Page 45 and 46: Selection table TCP/IP LON Descript
- Page 47 and 48: Rack and Condenser Controllers Seri
- Page 49 and 50: Block Diagrams EC3-81x Dual Ciruit
- Page 51 and 52: Network Accessories Description Cab
- Page 53 and 54: Pressure Transmitter Series PT4 A2.
- Page 55 and 56: Electronic Fan Speed Power Module F
- Page 57 and 58: A2.5.1/0706/E Thermo ® -Expansion
- Page 59 and 60: A2.5.1/0706/E Example Cooling capac
- Page 61 and 62: TIS(E) Valve bodies - solder type m
- Page 63 and 64: Capacity kW Valve Type TI..-M.... C
- Page 65 and 66: Condensing Temperature R 22 Capacit
- Page 67 and 68: R 407C Nominal less MOP with Standa
- Page 69 and 70: A2.5.1/0706/E Available upon specia
- Page 71 and 72: Liquid Correction Factor K t Temper
- Page 73 and 74: Thermo ® -Expansion Valve Series Z
- Page 75 and 76: Liquid Correction Factor K t Temper
- Page 77 and 78: Accessories A2.5.1/0706/E Available
- Page 79 and 80: Accessories Description Type Part N
- Page 81 and 82: Liquid Correction Factor K t Temper
- Page 83 and 84: A2.5.1/0706/E Solenoid Valves 81
- Page 85 and 86: Coils ASC Type Part No. Voltage Pow
- Page 87: 2-Way Solenoid Valves Series 540 No
- Page 91 and 92: A2.5.1/0706/E Mechanical Pressure R
- Page 93 and 94: Hot Gas Bypass Regulators Series AC
- Page 95 and 96: Head Pressure Control Valves Series
- Page 97 and 98: Evaporator and Crankcase Pressure R
- Page 99 and 100: A2.5.1/0706/E Fan Speed Controllers
- Page 101 and 102: Technical Data Function Diagram A2.
- Page 103 and 104: Selection Dependent on Product Comb
- Page 105 and 106: A2.5.1/0706/E Pressure Controls and
- Page 107 and 108: A2.5.1/0706/E Standards and Regulat
- Page 109 and 110: Single Pressure Controls Series PS1
- Page 111 and 112: Dual Pressure Controls PS2 TÜV / E
- Page 113 and 114: Pressure Controls Series PS3 / Stan
- Page 115 and 116: Differential Pressure Controls Seri
- Page 117 and 118: Function of contacts A2.5.1/0706/E
- Page 119 and 120: Type Part No. Adjustment Range Lowe
- Page 121 and 122: A2.5.1/0706/E System Protectors, Mo
- Page 123 and 124: Bi-flow Filter Driers Series BFK he
- Page 125 and 126: Nominal Operating Conditions Nomina
- Page 127 and 128: Connections Type Part Connection A2
- Page 129 and 130: Filter-Drier Shells With Quick-Cap
- Page 131 and 132: Correction Tables for Filter Driers
- Page 133 and 134: Suction Line Filters and Filter Dri
- Page 135 and 136: BTAS - Water and Acid Adsorption Ca
- Page 137 and 138: Moisture Liquid Indicators Series A
2. Liquid Application<br />
Liquid Correction Factor K t<br />
Temperature R 404A Evaporating Temperature °C R 507<br />
entering Valve<br />
3. Hot Gas Application<br />
A2.5.1/0706/E<br />
°C +10 0 -10 -20 -30 -40 +10 0 -10 -20 -30 -40<br />
+60 1,74 1,88 2,06 2,28 2,57 2,95 1,71 1,83 1,98 2,18 2,43 2,75<br />
+55 1,46 1,55 1,68 1,83 2,01 2,25 1,43 1,52 1,62 1,76 1,92 2,12<br />
+50 1,26 1,34 1,43 1,54 1,68 1,84 1,24 1,31 1,40 1,49 1,61 1,76<br />
+45 1,12 1,18 1,26 1,34 1,45 1,57 1,11 1,17 1,23 1,31 1,40 1,52<br />
+40 1,02 1,07 1,13 1,20 1,28 1,38 1,01 1,06 1,11 1,17 1,25 1,34<br />
+35 0,93 0,97 1,02 1,08 1,15 1,23 0,93 0,97 1,01 1,07 1,13 1,20<br />
+30 0,86 0,90 0,94 0,99 1,05 1,11 0,86 0,89 0,93 0,98 1,03 1,09<br />
+25 0,80 0,83 0,87 0,92 0,97 1,02 0,80 0,83 0,87 0,91 0,95 1,01<br />
+20 0,75 0,78 0,81 0,85 0,90 0,95 0,75 0,78 0,81 0,85 0,89 0,93<br />
+15 0,71 0,73 0,76 0,80 0,84 0,88 0,71 0,73 0,76 0,79 0,83 0,87<br />
+10 0,67 0,69 0,72 0,75 0,79 0,83 0,67 0,69 0,72 0,74 0,78 0,81<br />
+5 0,66 0,68 0,71 0,74 0,78 0,65 0,68 0,70 0,73 0,76<br />
0 0,63 0,65 0,68 0,71 0,74 0,62 0,64 0,66 0,69 0,72<br />
-5 0,62 0,65 0,67 0,70 0,61 0,63 0,65 0,68<br />
-10 0,60 0,62 0,64 0,67 0,58 0,60 0,62 0,64<br />
Liquid Correction Factor K t<br />
Temperature R 407C Evaporating Temperature °C<br />
entering Valve<br />
°C +10 0 -10 -20<br />
+60<br />
+55 1,28 1,34 1,40 1,48<br />
+50 1,17 1,22 1,27 1,33<br />
+45 1,08 1,12 1,17 1,22<br />
+40 1,01 1,04 1,08 1,13<br />
+35 0,94 0,98 1,01 1,05<br />
+30 0,89 0,92 0,95 0,99<br />
+25 0,84 0,87 0,90 0,93<br />
+20 0,80 0,82 0,85 0,88<br />
+15 0,76 0,78 0,81 0,84<br />
+10 0,73 0,75 0,77 0,80<br />
+5 0,72 0,74 0,76<br />
0 0,69 0,71 0,73<br />
-5 0,68 0,70<br />
-10 0,65 0,67<br />
Correction Factor K∆p<br />
∆p (bar) 0,05 0,10 0,15 0,20 0,25 0,30 0,35 0,40 0,45 0,50 0,55 0,60 0,65 0,70 0,75<br />
K∆p 1,73 1,22 1,00 0,87 0,77 0,71 0,65 0,61 0,58 0,55 0,52 0,50 0,48 0,46 0,45<br />
Correction Factor K t<br />
Evaporating Temperature °C<br />
+10 +5 0 -5 -10 -15 -20 -25 -30 -35 -40<br />
K t 0,96 1,00 1,03 1,06 1,10 1,13 1,17 1,20 1,24 1,29 1,33<br />
Correction Factor K∆p<br />
∆p (bar) 0,35 0,50 0,70 1,00 1,50 2,00 2,50 3,00 4,00<br />
K∆p 1,72 1,49 1,22 1,00 0,86 0,78 0,73 0,70 0,65<br />
87